Project Name / Date Division 23 52 33.13 - 1 DIVISION 23 52 33.13 FINNED WATER-TU BE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes gas-fired, copp er finned-tube hydronic heating boilers B. Related Sections Specifier Note: Use as needed 1. Building Services Piping – Division 23 21 00 2.
Project Name / Date Division 23 52 33.13 - 2 2. Product: Hi Delta SS™ copper finned-tube hydronic boiler(s) 2.2 BOILERS A. General 1. The boiler(s) shall be fired with gas at a rated input of BTU/hr. 2. The boiler(s) shall be CSA tested and certified with a minimum ther mal efficiency of 84 percent at full fire.
Project Name / Date Division 23 52 33.13 - 3 1. Provide internal LED displaying the following boiler status/faults: a. Steady on – Internal control failure b. One flash – Air flow fault c. Two flashes – Erroneous flame signal d. Three flashes – Ignition lockout I.
Project Name / Date Division 23 52 33.13 - 4 PART 3 - EXECUTION 3.1 INSTALLATION A. Must comply with: 1. Local, state, provincial, and national codes, laws, re gulations and ordinances 2. National Fuel Gas Code, ANSI Z223.1/NFPA 54 – latest edition 3.
デバイスRaypak HD401の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Raypak HD401をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはRaypak HD401の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Raypak HD401の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Raypak HD401で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Raypak HD401を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はRaypak HD401の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Raypak HD401に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちRaypak HD401デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。