SanyoメーカーKMH0922の使用説明書/サービス説明書
ページ先へ移動 of 18
SERVICE MANUAL (Basic Information) CMH1822 / KMH0922 ( ✕ 2) SPLIT SYSTEM AIR CONDITIONER 8526481017400 REFERENCE NO. WM – 700700 W Indoor Unit Outdoor Unit CMH1822 KMH0922 92-144 S/M (Basic) 00.
92-144 S/M (Basic) 00.12.13 10:32 AM ページ B.
ii WM – 700700 SER VICE MANUAL CMH1822 / KMH0922 ( × 2) (Basic Information) 92-144 S/M (Basic) 00.12.13 10:32 AM ページ ii.
WM – 700700 IMPORT ANT! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
T able of Contents Page 1. OPERA TING RANGE ............................................................................................................................... 1 2. SPECIFICA TIONS ..........................................................
1 WM – 700700 1. OPERA TING RANGE Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 95°F DB / 71°F WB 115°F DB Minimum 67°F DB / 57°F WB 67°F DB CMH1822 / KMH0922 ( × 2) 92-144 S/M (Basic) 00.
DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Cooling: Outside air temperature 95°F DB / 75°F WB Indoor unit entering air temperature 80°F DB / 67°F WB Heating: Outside air temperature 47°F DB / 43°F WB Indoor unit entering air temperature 70°F DB Model No.
3 WM – 700700 DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Cooling: Outside air temperature 95°F DB / 75°F WB Indoor unit entering air temperature 80°F DB / 67°F WB Heating: Outside air temperature 47°F DB / 43°F WB Indoor unit entering air temperature 70°F WB Model No.
WM – 700700 4 3. DIMENSIONAL DA T A Outdoor Unit: CMH1822 Indoor Unit: KMH0922 O.D. 3/8" wide tubing service valve 2-9/32 3-3/4 11-7/32 1-3/16 2-1/4 32-11/16 3/4 24-13/16 Air discharge Air intake Air intake 21-3/16 5-3/4 12-3/12 13-1/4 4 × 15/32 dia.
4. COOLING CAP ACITY 230V CMH1822 / KMH0922 ( × 1) 5 WM – 700700 TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mar.
6 WM – 700700 208V CMH1822 / KMH0922 ( × 1) TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mark) are: Outside ambie.
7 WM – 700700 5. HEA TING CAP ACITY 1 Phase 60Hz 230V Model Name: CMH1822 / KMH0922 ( × 1) Indoor Entering Air Temperature 70 ° F Temperature of Air Entering Outdoor Coil ( ° F D.B. at 75% RH) Heating Capacity (BTU/h) 30,000 25,000 20,000 15,000 10,000 5,000 23 ( – 5) 32 (0) 41 (5) 50 59 (15) 68 (20) 75 ° F (23.
8 WM – 700700 1 Phase 60Hz 208V Model Name: CMH1822 / KMH0922 ( × 1) Indoor Entering Air Temperature 70 ° F Temperature of Air Entering Outdoor Coil ( ° F D.B. at 75% RH) Heating Capacity (BTU/h) 30,000 25,000 20,000 15,000 10,000 5,000 23 ( – 5) 32 (0) 41 (5) 50 59 (15) 68 (20) 75 ° F (23.
Heat exchanger Narrow tube O. D. 1/4" (6.35mm) Wide tube O.D. 3/8" (9.52mm) Service valve Muffler Accumulator Compressor A Reversing valve Service valve Dehydrator Capillary tube ( ) Check valve Strainer Heat exchanger Narrow tube O.D. 1/4" (6.
10 WM – 700700 7. ELECTRICAL DA T A ● Electrical Characteristics CMH1822 / KMH0922 ( × 1) Remarks: Rating conditions are: Cooling: Outside air temperature 95°F DB / 75°F WB Indoor unit entering.
11 WM – 700700 ● Electrical Wiring Diagram Outdoor Unit: CMH1822 CMA S C R BLK RED Compressor motor A PTC. A WHT BLK WHT OLR. A CMB R C S RED Compressor motor B WHT OLR. B BLK WHT BLK PTC. B BLK 1 2 7 6 5 4 3 2 1 3 4 12 3 4 12 1 2 1 2 CONTROLLER S.
12 WM – 700700 Indoor Unit: KMH0922 1 1 2 1 2 1 1 12 12 2 2 5 5 4 4 3 3 1 1 5 5 4 4 3 3 1 1 2 2 6 6 Thermistor 2P Supply CONTROLLER Remote control switch Fan motor FM 2 3 1 2 1 2 BRN PNK GRY YEL WHT.
For parts or service contact SFS Corporation: 1200 West Artesia Blvd., Compton, California 90220 Printed in U.S.A. CORPORATION 1991/Nov./12M SANYO Canada Inc.: Toronto, Ont. M4H 1M6 In Canada WM – 700700 H407/12M Printed in U.S.A. 92-144 S/M (Basic) 00.
デバイスSanyo KMH0922の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Sanyo KMH0922をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSanyo KMH0922の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Sanyo KMH0922の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Sanyo KMH0922で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Sanyo KMH0922を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSanyo KMH0922の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Sanyo KMH0922に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSanyo KMH0922デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。