SER VICE MANUAL (Basic Information) CM3212 / KMS0712 ( ✕ 2) + KMS1812 SPLIT SYSTEM AIR CONDITIONER 8526481017300 REFERENCE NO. WM – 700699 W Indoor Unit Outdoor Unit CM3212 KMS0712 KMS1812 92-131 .
92-131 S/M (Basic) 2/21/01 4:49 PM Page B.
ii WM – 700699 SER VICE MANU AL CM3212 / KMS0712 ( × 2) + KMS1812 (Basic Inf ormation) 92-131 S/M (Basic) 2/21/01 4:49 PM Page ii.
WM – 700699 iii IMPORT ANT! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
T able of Contents Page 1. OPERA TING RANGE ............................................................................................................................... 1 2. SPECIFICA TIONS ..........................................................
1 WM – 700699 1. OPERA TING RANGE Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 95°F DB / 71°F WB 115°F DB Minimum 67°F DB / 57°F WB 67°F DB CM3212 / KMS0712 ( × 2) + K.
DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Outside air temperature 95°F DB / 75°F WB Indoor unit entering air temperature 80°F DB / 67°F WB 2 WM – 700699 Model No. Outdoor unit CM3212 Applicable indoor unit KMS0712, KMS1812 Cooling No.
3 WM – 700699 DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Outside air temperature 95°F DB/ 75°F WB Indoor unit entering air temperature 80°F DB/67°F WB Model No. KMS0712 Type Wall-mounted Cooling Capacity BTU/ h 7,000 / 7,700 kW 2.
4 WM – 700699 DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Outside air temperature 95°F DB/ 75°F WB Indoor unit entering air temperature 80°F DB/67°F WB Model No. KMS1812 Type Wall-mounted Cooling Capacity BTU/ h 18,000 / 17,600 kW 5.
WM – 700699 5 3. DIMENSION AL D A T A Outdoor Unit: CM3212 Air intake 21/32 Air intake Air intake 21/32 25-1/16 26-3/8 21/32 26-3/8 25-1/16 4 × 15/32 dia.
6 WM – 700699 Indoor Unit: KMS0712 Indoor Unit: KMS1812 Wireless remote control unit 31-1/2 7-3/32 7-11/64 17-23/32 Rear panel (center point of gravity) 6-23/32 13-19/32 1-49/64 3-3/4 15/32 1-49/64 1-3/8 5-1/2 1-49/64 Center of tubing hole (for right rear) O.
4. COOLING CAP A CITY 230V CM3622 / KMS0712 × 1 7 WM – 700699 TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mark) .
8 WM – 700699 208V CM3622 / KMS0712 × 1 TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mark) are: Outside ambient t.
9 WM – 700699 230V CM3622 / KMS1812 TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mark) are: Outside ambient temper.
10 WM – 700699 208V CM3622 / KMS1812 TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mark) are: Outside ambient tempe.
OUTDOOR UNIT INDOOR UNIT UNIT A Heat exchanger Heat exchanger INDOOR UNIT UNIT B Heat exchanger INDOOR UNIT UNIT C Heat exchanger Narrow tube service valve Capillary tube Drier A B C Check port A Check port B Check port C Accumulator Accumulator Accumulator Compressor C Compressor B Compressor A Narrow tube O.
12 WM – 700699 6. ELECTRICAL D A T A ● Electrical Characteristics CM3212 / KMS0712 × 1 Remarks: Rating conditions are: Outside air temperature 95°F DB / 75°F WB Indoor unit entering air tempera.
13 WM – 700699 CM3212 / KMS0712 + KMS1812 Remarks: Rating conditions are: Outside air temperature 95°F DB / 75°F WB Indoor unit entering air temperature 80°F DB/ 67°F WB Performance at Indoor Units Outdoor Unit Complete Unit 230/208V – 1ø – 60Hz Fan Motor Compressor Rating Conditions A 0.
14 WM – 700699 ● Electrical Wiring Diagram Outdoor Unit: CM3212 CMA S C R WHT BLK RED CMB S C R BLK WHT RED CMC S C R BLK WHT RED 2 3 TO INDOOR UNIT A 1 2 3 1 2 3 1 2 Power supply 1 5 3 2 6 4 78 F.
15 WM – 700699 Indoor Unit: KMS0712 1 3 3 2 2 1 1 2 2 1 1 1 2 1 2 1 1 9 9 5 5 4 4 3 3 2 2 1 1 5 5 4 4 3 3 2 2 1 1 6 6 BLK BLK Thermistor 1 2 1 2 BLK BLK Thermistor 2P TH1 2P TH2 2P CM 3P Supply CONT.
16 WM – 700699 Indoor Unit: KMS1812 3 1 1 2 2 3 3 1 1 2 2 1 9 5 5 4 4 3 3 2 2 1 1 2P TH2 3P Supply CONTROLLER Switch assy Switch assy 2 1 1 2 1 2 5P FM GRY YEL VLT 2P LM Capacitor 1 2 1 2 2P SEC S P.
For parts or service contact SFS Corporation: 1200 West Artesia Blvd., Compton, California 90220 Printed in U.S.A. CORPORATION 1991/Nov./12M SANYO Canada Inc.
デバイスSanyo KMS1812の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Sanyo KMS1812をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSanyo KMS1812の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Sanyo KMS1812の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Sanyo KMS1812で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Sanyo KMS1812を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSanyo KMS1812の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Sanyo KMS1812に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSanyo KMS1812デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。