APC by Schneider Electric MGE GALAXY 5000 Data Center Grade Three Phase Uninterruptible Power Supply Parallel Module - Guide Specifications 40-130 kVA UPS 1.0 GENERAL 1.1 SUMMARY This specification describes a three-phase, on-li ne, double conversion, solid state Uninterruptible Power System hereafter referred to as the UPS.
outline, connection diagram for external cabling, internal wiring diagram, and written instruction for installation. 1.4 FINAL SUBMITTALS Upon delivery of the UPS system the following submittals shall be included: A. A complete set of installation drawings showing all the information stated in section 1.
UPS Module Operating : 0° to 40°C (32°F to 104°F) Non-Operating : -20° to +45°C (-4°F to 113°F) B. Relative humidity (operating and storage): 0 to 95% non-condensing C. Barometric Pressure: Up to 1000 meters above sea level (up to 2000 meters with ambient temperature less than 28°C) / (up to 12,000 meters above sea level non operating) D.
static switch, battery plant, graphical stat us/control panel, dry contact and communications ports, and synchronizing circuitry as described herein. 2.2 SYSTEM DESCRIPTION A. UPS Design Requirements 1. Output Pow er Continuous Rating : The continuous output power rating of the UPS shall be [ ] kVA at a 0.
+ 1% for loss or return of AC input power or manual transfer at full load 6. Voltage Recovery Time : Return to within 1% of nominal value within 16.67 milliseconds (one cycle) 7. Phase Angle Displacement : 120° + 1° for balanced load; 120° + 3° for 100% unbalanced load 8.
Incoming AC power shall be converted to a regulated DC output voltage by an IGBT (insulated gate bipolar transistor) power factor co rrection (PFC) rectifier. The PFC rectifier shall provide high quality DC power to charge the batteries and power the inverter and shall have the following characteristics: 1.
1. Uninterrupted Transfer : The static bypass transfer swit ch shall automatically cause the bypass source to assume the critical load wit hout interruption after the logic senses one of the following.
o The graphic display shall assist the user by providing step by step help in the user's language. o LED mimic diagram o The mimic diagram shall enable display of installation parameters, configuration, operating status and alarms and indication of operator instructions for switching operations (e.
Bypass voltage Bypass input frequency UPS output voltage (Ph-Ph and Ph-N) UPS output current per phase UPS output frequency UPS output % load UPS output kVA UPS output .
D. Audible Alarm Reset : The UPS shall provide an audible alarm that can be stopped using the user interface. If a new al arm is sensed after the original alarm has been silenced, it will reactivate the audible alarm.
3.2 BATTERY The UPS module shall use a valve regulated s ealed lead acid heavy-duty industrial battery, designed for auxiliary power service in a UPS applic ation. The primary battery shall be furnished with impact resistant plastic cases and housed in a matching cabinet(s) next to the UPS module.
2. RS232 or RS485 JBus/Modbus Card (66061) : The U-Talk protocol shall be used with Solution-Pac 2 for remote monitoring or gracef ul shutdown for most popular file servers. The JBus protocol is used with third party Building Management Systems (BMS) to monitor detailed three-phase information.
160/320/520kVA depending on model selected. Secondary UPS isolation breakers (2 to 6) are standard – must be determined pre-orderd. In cludes: PM800 Meter for SBC System Level Metering. E. 42” Distribution Cabinet: Distribution Cabinets are an avail able option to the System Bypass Cabinets not individual UPS module.
END OF SECTION APC – MGE Galaxy 5000 Specification (60Hz) 14 Effective: June 1, 2008 REV X0 JJG Parallel Module.
SPECIFICATION KEY 2.2 A–1 OUTPUT POWER RATINGS 40 kVA/ 36 kW 50 kVA/ 45 kW 60 kVA/ 54 kW 80 kVA/ 72 kW 100 kVA/ 90kW 130 kVA /117kW 2.
2.2 D-2 BATTERY DC CURRENT 40 KVA 50 KVA 60 KVA 80 KVA 100 KVA 130 KVA ADC At Max End Voltage 109 137 164 219 273 355 3.1 C WEIGHTS AND DIMENSIONS Dimensions (Inches)/ WEIGHT (Lbs.) KVA UPS 40 to 80kVA UPS 100 to 130kVA TOP Entry Battery Height 75.0 75.
3.2D SYSTEM BYPASS CABINET (SBC) - Parallel 28” SBC Cabinet 42” SBC Cabinet kVA 160/320 160/320/520 Metering No Yes (PM800) Input / output Volts 480V 480V Max UPS Modules Up to Two Up to Six Height 75.0” 75.0” Width 28.0” 42.0” Depth 33.4” 33.
デバイスSchneider Electric 5000の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Schneider Electric 5000をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSchneider Electric 5000の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Schneider Electric 5000の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Schneider Electric 5000で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Schneider Electric 5000を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSchneider Electric 5000の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Schneider Electric 5000に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSchneider Electric 5000デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。