SharpメーカーAY-XP7FRの使用説明書/サービス説明書
ページ先へ移動 of 14
CHAPTER 1. SPECIFICA TION [1] SPECIFICA TI ON .............. ................ ...... ........ 1-1 [2] EXTERNAL DIMENSION .............. ......... ........ 1-4 [3] WIRING DIAGRM ............... ................. .. ........ 1-5 [4] ELECTRICAL P AR TS .
A YXP7FR 1 – 1 A YXP7FR Service Manual CHAPTER 1. SPECIFICA TION [1] SPECIFICA TION 1. A Y -XP7FR – AE-X7FR MODEL INDOOR UNIT OUTDOOR UNIT ITEMS A Y -XP7FR AE-X7FR Cooling capacity(Min. > Max.) kW 2.1 (0.9 - 2.5) Heating capacity(Min. > Max.
A YXP7FR 1 – 2 2. A Y -XP9FR – AE-X9FR MODEL INDOOR UNIT OUTDOOR UNIT ITEMS A Y -XP9FR AE-X9FR Cooling capacity(Min. > Max.) kW 2.64 (0.9 - 3.0) Heating capacity(Min. > Max.) kW 3.1 (0.9 - 4.8) Moisture removal(at cooling) Liters/h Electrical dat a Phase Single Rated frequency Hz 50 Rated voltage V 230 Rated current ✩ (Min - Max.
A YXP7FR 1 – 3 3. A Y -XP12FR – AE-X12FR NOTE: The condition of star” ✩ ” marked item are ‘ISO5151’ : 1994(E), contition T1. MODEL INDOOR UNIT OUTDOOR UNIT ITEMS A Y -XP12FR AE-X12F R Cooling capacity(Min. > Max.) kW 3.5 (0.9 - 3.8) Heating capacity(Min.
A YXP7FR 1 – 4 [2] EXTERNAL DIMENSION 1. Indoor unit 2. Out door unit 278 198 790 22.0 58 18.5 175 INVERTER AIR CONDITIONER 250 165 167.5 136 81 730 72 540 299 324 515 12 37.
A YXP7FR 1 – 5 [3] WIRING DIAGRM 1. Indooa unit 2. Out dooa unit 2.1. AE-X7FR / AE-X9FR 2.2. AE-X12 FR 420V 750μF 420V 750μF.
A YXP7FR 3 – 13 [8] TROUBLESHOOTING GUIDE 1. Self-Diagnosis Function and Display Mod e T o call out the content of the self-diagnosis memory , hold dow n the emergency operation button for more than 5 se conds when the indoor unit is not operating.
A YXP7FR 3 – 14 Indoor/ outdoor units in complete shutdown 2 times 2 -0 Cycle tempera- ture Compressor high- temperature error (1) Check the outdoor unit air outlet for blockage. (1) Ensure unobstructed air flow from the out- door unit air outlet. (2) Check if the power supply voltage is 90 V or higher at full power .
A YXP7FR 3 – 15 Indoor/ outdoor units in complete shutdown 6 times 6 -0 Outdoor unit DC DC overcurrent error ( 1) IPM continuity check (1) Replace the outdoor unit control PW B assembly . (2) Check the IPM and heat sink for secure installation. (2) Correct the ins talla- tion (tighten the screws).
A YXP7FR 3 – 16 Indoor/ outdoor units in complete shutdown 11 times 1 1 -0 Out door unit DC fan Outdoor unit DC fan rotation error (1) Check connector CN3 of the outdoor unit DC fan motor for secure installa- tion. (1) Correct the installa- tion. (2) Check the outdoor unit fan motor for proper rotation.
A YXP7FR 3 – 17 Indoor/ outdoor units in complete shutdown 19 -0 Indoor unit fan Indoor unit fan error (1) Check the indoor fan motor for proper rotating operation.(Check fan lock.) (1) Replace the indoor fan motor . (2) Check the lead wire of the indoor fan motor for open- circuit.
A YXP7FR 3 – 18 Malfunction indications due to erroneous wiring during air condi tioner installation Inter-unit wiring error mode Symptom 1 Indoor unit relay Malfunction diagnosis display T urns On momentarily , then turns Off. "18-1" 2 Indoor unit relay Malfunction diagnosis display Relays turns Off after about 30 minutes.
A YXP7FR 4 – 2 [4] PERFORMANCE CURVES NOTE 1) Indoor fan speed: Hi 2) V ertical adjustment louver "45 ° ”, Horizontal adjustment louver "front" 3) Indoor air temp. : Cooling 27 ° C, Heatin g 20 ° C 4) Power source : 230V , 50Hz 1.
A YXP7FR 4 – 3 3. A Y -XP12F R 3.1. At Cooling 3.2. At Heating 25 30 35 40 3.2 3.4 3.6 3.8 4.0 1200 900 1000 1100 Cooling capacity(kW) Outside air temp.(ºC) Input(W) -5 0 5 7 10 3.5 4.0 4.5 3.0 2.5 1000 1100 1200 900 800 Heating capacity(kW) Outside air temp.
デバイスSharp AY-XP7FRの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Sharp AY-XP7FRをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSharp AY-XP7FRの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Sharp AY-XP7FRの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Sharp AY-XP7FRで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Sharp AY-XP7FRを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSharp AY-XP7FRの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Sharp AY-XP7FRに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSharp AY-XP7FRデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。