Installation / Operation / Maintenance Instructions JFR Distribution Step Voltage Regulator 21-115532-001 PR4018-06 SUPERCEDES 21-115532-001 PR4018-05 October 08.
.
TABLE OF CONTEN TS Page INTRODUCTION Inspection for Dam age in Shipment ................... 2 Storage Prior To Installation ............................. 2 Physical Considerations ................................... 3 Line Terminals and Connection s .
.
INTRODUCTION Page 1 Type JFR single-phase step-voltage reg ulators are designed to give dependable service an d to make installation, operation and maintenance as simple as possib le.
INTRODUCTION Page 2 INSPECTION FOR STORAGE PRIOR TO DAMAGE IN SHIPMENT INSTALLATION Check each item with the shipping manifest immediat ely upon receipt of the regulator. Make a thorough visu al in- spection of the regulator. Check for evidence of damage attributable to mishandling in shipment.
INTRODUCTION Page 3 PHYSICAL CONSIDERATIONS • Handling. Type JFR regulators are designed to be lifted either by a forklift at the ba se or by use of li fting hooks on the side of each tan k. Each JFR regulator is provided with either 2 or 4 lifting hooks on the sid e of each tank.
INTRODUCTION INSTALLATION DIAGRAMS Connection of two single phase JFR regulators in open delta on a three phase, ungrounded line. Connection of one single phase JFR regulator on single phase line. Connection of three JFR regulators in closed delta on three phase, ungrounded system.
INTRODUCTION Page 5 PROTECTIVE MEASURES Bypass Arrester. All JFR regulators are equip ped with a properly si ze d arre ste r, connected ex ternally be tw een the 'S' and 'L' line terminals. T he arrester is provi ded to protect the series winding of the regulator from line surges.
CONNECTION DIAGRAMS STRAIGHT DESIGN (ANSI TYPE A) S L SL SOURCE LOAD Typical arrangement of windings and connections of Type “A” JFR regulators. Note: Straight design units may or may not be equiped with a balance winding. Refer to regulator nameplate.
CONNECTION DIAGRAMS Page 7 S L LOAD SOURCE SL INVERTED DESIGN (ANSI TYPE B) L S SL Wiring diagram of a typica l Type “B” regulator showing both internal and external connectio ns. Schematic diagram of a typical Type “B” JFR regulator utilizing single poten tial source for motor and control circuit.
Wiring diagram of a typica l reg ulator with series transformer showing both internal and external connectio ns. S L SL CONNECTION DIAGRAMS Page 8 S L SL LOAD SOURCE Schematic diagram of a typical regulator with series transformer with fan power U3-U5.
PLACING THE REGULATOR IN SERVICE Page 9 The following checks will be useful in assuring the regulator is ready for use. The list cannot be al l incl usive; careful at- tention on the part of a qualifi ed operator remains imp erative. BEFORE CONNECTING • Check oil level at oil sight windo w.
REMOVING THE REGULATOR FROM SERVICE Page 10 SWITCHING “OFF LINE ” • Improper by-pass op eration w ill result in explo si on and fire hazard. Will cause serious injury, death or equipment damage. • Do NOT remove from ser vice unless tap -changer is in neutral position A ND control panel is pro perly disabled.
MAINTENANCE Pa g e 11 GENERAL INSTRUCTIONS This manual does not repres ent an e xhaustive survey of maintenance steps necessar y to ensure saf e operation of the regulat or.
MAINTENANCE Page 12 PERIODIC INSPECTION A sample of oil from the regul ator should be subjected to dielectric breakdown test, per AST M D-877. If found be low 25kV, the oil should be changed or rec on ditioned.
SPECIAL FEATURES Page 13 POLARIZED DISCONNECT SWI TCH VARI -AMP TM POSITION INDICATOR (JACK PLUG) AND HINGED CONTROL PANEL The Ac c u/ S t at TM control panel is hin ged and may be re- moved completely from the regulator control box by removing the wing nuts on the polar ized jack plug and pull ing the jack from its fixed position .
SPECIAL FEATURES VA RI-A MP TM RANGE AND CURRENT RATINGS AVAILABLE ±10% ±8 3/4% ±7 1/2% ±6 1/4% ±5% 10-02.5-050.0 200 220 240 270 320 10-02.5-075.0 300 330 360 405 480 10-02.5-100.0 400 440 480 540 640 10-02.5-167.0 668 668 668 668 668 10-02.5-250.
SPECIAL FEATURES Page 15 FORCED AIR COOLING Certain regulators may be equip ped for forc ed-air cooling and include fans mounted on the radiators. T he fans are usually automatically controlled by means of the ch ange in oil temperature (see Connection Diagr am).
PARTS LIST Page 16 MAJOR COMPONENTS PARTS LIST Instructions For Ordering Part When ordering parts give the quant ity of parts required, the regulator seria l number, parts list item number, complete description, and method of shipping. State whether for emergency repair, maintena nce, spare part, etc.
PARTS LIST TYPE TLG DIAL SWITCH Item 01-11 Description 5320 Panel 5317A Reversing M ain Shaft 5321 Main Stationa ry Contacts 5322 Reversing St ationary Cont act R 5323 Reversing St ationary Cont act L.
PARTS LIST Page 18 TYPE TLG QUICK BREAK MECHANISM Item 01-11 Description 5201G Mounting Frame Assembly 5202 Motor 5207 Drive S p ring Ass embly 5212 La tch Assembly 5213 La tch Spring (no t shown) 5214 La tch Pin (not shown) *5216A Reversing Switch Drive Arm - P henolic *5216B Reversing Switch Drive Arm - P henolic *5216C Rev.
PARTS LIST TYPE TLF DIAL SWITCH FIGURE 20A Item 01-11 D escription 5351 Panel 5352 Stationar y C ontact 5353 Neutral St ationary Cont act 5354 Stationar y C ontact - LH 5355 Stationar y C ontact - RH .
PARTS LIST Page 20 TYPE TLF QUICK BREAK MECHANISM Figure 21A Item 01-11 Description 5266 Interlock Disc and Drive Sprocket Ass embly 5267 Quick Break Mechanism Shaft 5275 Actuating Arm Assembly 5276 S.
PARTS LIST Page 21 BYPASS ARRESTERS Item 01-11 Description Volts 5423 Bypass Arrester Asse mbly 3 kV MOV 2,500, 5,000, 7,620 5425 Mounting Bracket Assembly 5423 B ypass Arrester Assembly, 3 kV MOV 12,.
PARTS LIST Page 22 Figure 23A BUSHINGS Item 01-11 Description kVA Volts 5400P Bushing Assembly for 15 kV 50 5000 38.1 thru 76.2 7620 69 thru 138 13,800 5400R Bushing Assembly for 15 kV 50 2500 100 5000 114.3 t hru 16 7 7620 5400S Bushing Assembly for 15 kV 75 2500 414 13,800 5401P Bushing Porcelain for 15 kV 50 5000 38.
PARTS LIST Page 23 BUSHINGS z Item 01-11 Description kVA Volts 5400T Bushing Assembly 15 kV 100 thru 167 2500 167 500 250 thru 509 7620 5400U Bushing Assembly, 15 kV 207-276 13,800 5400V Bushing Assembly, 23 kV 72 thru 144 14,400 100 thru 200 19,920 5400W Bushing Assembly 15 kV 333 thru 416.
Siemens Energy, Inc. P.O. Box 6289 Jackson, MS 39288-6289 Phone: 601- 939-0550 Fax: 601-93 9-3606 ACCU/STA T, DATA/PAK, NEUT RALITE a nd VA RI - AMP are trademarks of Siemens Energy, Inc.
デバイスSiemens 21-115532-001の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Siemens 21-115532-001をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSiemens 21-115532-001の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Siemens 21-115532-001の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Siemens 21-115532-001で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Siemens 21-115532-001を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSiemens 21-115532-001の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Siemens 21-115532-001に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSiemens 21-115532-001デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。