SiemensメーカーCM300/3の使用説明書/サービス説明書
ページ先へ移動 of 40
STÖBER CombiDrive ® SIEMENS Micromaster integrated Installation and Commissiong instructions It ist essential to read and comply with these instructions prior to installation and commissioning! 01/2.
Contents Safety prec autions ................................................................................................ ..1 1. OVERVIE W ..................................................................................................... ..2 2.
© STÖBER pl c 199 8 05.02.01 Safety Precautions Before installin g and putt ing this equip ment into o peration, please read t hese safety precautions and warnings carefully and all the warning signs attach ed to the equipment. Make sure that the w arning signs are kept in a legible condition and replace missing or damaged signs.
English 2. Installation © STÖBER pl c 199 8 05.02.01 2 1. OVERVIEW The CombiDrive ® is an integr ated motor/inverter for variable speed applications. The inverter is micr opr oces s or -c ontr olled and uses s tate of the ar t IGBT tec hnology for r eliability and flexibility .
2. Installation Engli sh © STÖBER pl c 1997 3 05.02.01 2. INSTALLATI ON WARNING To guarantee the safe oper ation of the equipment it must be installed and commissioned b y qualified personnel only. Take particular note of the gener al and regional installation and safety regulations regarding work on high voltage ins tallations (e.
English 2. Installation © STÖBER pl c 199 8 05.02.01 4 2.2 Mechanical Installation Figures 1 and 2 show dimens ional information for all CombiDrive ® variants. Note: ‘ Case size ’ refers to the type of inv erter box mounted on the motor. ‘ Motor frame ’ refer s to the motor frame size only .
2. Installation Engli sh © STÖBER pl c 1997 5 05.02.01 CombiDrive ® – Dimension (Only dimens ions of the motor, total dimensions of the gear motor see MGS-catalog, Impr .-No. 440 637) qx = Max. dimension; G iven either through the invert er or through the fan cowl.
English 2. Installation © STÖBER pl c 199 8 05.02.01 6 2.3 Electrical Installation Remove the four M5 cr oss-head sc rews on the inverter's cover to acc ess the electric al terminals (see Figure 3 and Figure 4) . Notes: (1) Refer to the elec trical data table for cable siz es (see sec tion 6) .
2. Installation Engli sh © STÖBER pl c 1997 7 05.02.01 2.3.1 Mai ns Cabl e Connections Ensure that the power sourc e supplies the corr ect voltage and is designed for the necessary current. Ensure that the appropriate circ uit-breakers with the specified curr ent rating ar e connected between the power supply and CombiDrive ® (see s ection 6) .
English 2. Installation © STÖBER pl c 199 8 05.02.01 8 1 2 3 1 2 3 1 . 8 mm m a x . OR Figure 4b: Connecting Control Wir es to PL800 Figure 2: Cable Connections with Dr ip Loop.
2. Installation Engli sh © STÖBER pl c 1997 9 05.02.01 2.3.3 Block Di agram 3 ~ M CPU A/ D SI GR ZK WR AD Ana l ogue t o D i gi t al C onver t er CPU M i cropr oces sor GR Rec t i f i e r M Mo t o r.
English 3. Operating Inform ation © STÖBER pl c 199 8 05.02.01 10 3. OPERAT ING INFOR MAT ION WARNING The equipment must not be sw itched on until after its cov er has been fitted and the cove r screws have been tightened to the correct torque.
3. Operating Inform ation English © STÖBE R plc 1997 11 05.02.01 (2) Using a combination of the internal potentiometer and a r un/stop switch: (a) Connect a run/stop sw itch between DIN1 (pin 5) and P15+ ( pin 8) on PL800 (see F igure 4a) if forward rotation is required.
English 3. Operating Inform ation © STÖBER pl c 199 8 05.02.01 12 3.6 If the Motor Does Not Start Up Check the LEDs on the s ide of the inverter: LED State CombiDrive ® Statu s Green Yellow ON ON M.
3. Operating Inform ation English © STÖBE R plc 1997 13 05.02.01 3.8 Closed Loop Contr ol Closed loop control is only possible when an OPm2 or a serial link is connec ted to the CombiDrive ® . 3.8.1 General Descri pt i on The CombiDrive ® provides a Proportional/Integral (PI) c ontrol function for c losed loop contr ol (see F igure 7) .
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 14 4. CLEAR TEXT DISPLAY MODULE & SYSTEM PARAMETERS 4.1 Clear Text Di splay Module (OPm2) This section only applies for users who intend using the optional Clear Text Display module (OPm2) to control the opera tion of the CombiDrive ® .
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 15 05.02.01 4.2 System Parameters The parameters listed here can only be accessed via th e OPm2 or a serial link to the Comb iDrive ® .
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 16 Parame ter Function Range [Default] Description / Notes P003 • • • • Ramp down time (seconds) 0 - 650.00 [25.00] This is the time taken for the motor to decelerate from maximum frequency (P013) to standstill.
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 17 05.02.01 Parame ter Function Range [Default] Description / Notes P007 Keypad control 0 - 1 [0] 0 = The RUN, REVERSE and JOG buttons are disabled. Control is via digital inputs (see parameters P051 - P053) .
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 18 Parame ter Function Range [Default] Description / Notes P018 • • • • Automatic restart after fault 0 - 1 [0] Automatic restart after fault: 0 = Disabled 1 = The inverter will attempt to restart up to 5 times after a fault.
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 19 05.02.01 Parame ter Function Range [Default] Description / Notes P027 • • • • Skip frequency 2 (Hz) 0 - 120.00 [0.00] See P014. P028 • • • • Skip frequency 3 (Hz) 0 - 120.
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 20 Parame ter Function Range [Default] Description / Notes P051 Selection control function, DIN1 0 - 19 (terminal 5), fixed frequency 3 [1] or binary fixed frequency bit 0.
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 21 05.02.01 Parame ter Function Range [Default] Description / Notes P061 Selection relay output RL1 0 - 13 [6] Value Relay function Active 4 0 No function assigned (relay not active) Low 1 Inverter is running High 2 Inverter frequency 0.
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 22 Parame ter Function Range [Default] Description / Notes P065 Current threshold for relay (A) 0 - 99.
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 23 05.02.01 Parame ter Function Range [Default] Description / Notes P078 • • • • Continuous boost (% ) 0 - 250 [100] Operates continuously over the whole frequency range.
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 24 Parame ter Function Range [Default] Description / Notes P093 • • • • Serial link timeout (seconds) 0 - 240 [0] This is the maximum permissible period between two incoming data telegrams.
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 25 05.02.01 Parame ter Function Range [Default] Description / Notes P123 Enable/disable JOG button 0 - 1 [1] 0 = JOG button disabled. 1 = JOG button enabled (only possible if P007 = 1).
English 4. Clear Text Di splay Module & System Parameters © STÖBER pl c 199 8 05.02.01 26 Parame ter Function Range [Default] Description / Notes P203 • • • • I gain (% ) 0.00 - 99.99 [0.00] Integral gain. 0.01% corresponds to the longest integral response time.
4. Clear Text Di splay Module & System Parameters English © STÖBE R plc 1997 27 05.02.01 Parame ter Function Range [Default] Description / Notes P910 • • • • Local/Remote mode 0 - 4 [0] .
English 5. Fault Codes © STÖBER pl c 199 8 05.02.01 28 5. FAULT CODES Fault codes ar e only available when an OPm2 is c onnected to the CombiDrive ® . In the event of a failure, the CombiDrive ® switc hes off and a fault code appears on the LCD scr een.
6. Specifications English © STÖBE R plc 1997 29 05.02.01 6. SPECIFICATIONS CSA-single-phase devi ce Model PM25/1 PM37/1 P M55/1 PM75/1 Mo t or f ra m e s iz e: 4 po le 71K 71L 80K 80L Motor output rat ing: 0.
English 6. Specifications © STÖBER pl c 199 8 05.02.01 30 Input frequency: 47 Hz to 63 Hz Power factor : λ ≥ 0.7 Output frequency range: 0 Hz to 50 Hz (0 Hz to 120 Hz using OPm2 or ser ial link) Resolution: 0.
6. Specifications English © STÖBE R plc 1997 31 05.02.01 Options / Accessories Clear Text Dis play (OPm2) 6SE3290-0XX87-8BF0 Interface cable for OPm2 (length = 1 m) 6SE9090-0XX87-8SK0 Interface cable for OPm2 (length = 3 m, shielded + gland) 6SE9996-0XA30 PROFIBUS Module (CB155) 6SE9996-0XA20 Pulse Resistor Braking Unit (incl.
English 7. Supplementary Infor mation © STÖBER pl c 199 8 05.02.01 32 7. SUPPLEMENTARY INFORMATION 7.1 Application Example Setup procedure for a simple appl i cation Application requirements: Normal operating frequency set within range 15 - 50 Hz via potentiometer.
7. Supplementary Infor mation English © STÖBE R plc 1997 33 05.02.01 7.3 Electro-Magn etic Compatib ility (EMC) Class 2: Fil t ered Industrial ( Cl ass A) This level of per formance will allow the m.
English 7. Supplementary Infor mation © STÖBER pl c 199 8 05.02.01 34 7.5 User's Parameter Settings Record your own parameter settings in the table below: Parameter Your setting Default P000 - P001 0 P002 10.0 P003 25.0 P004 0.0 P005 50.00 P006 1 P007 0 P009 0 P011 0 P012 0.
8. Accessoires © STÖBER plc 1997 35 02.07.0 3 8.1 Control box (Steuerbox) for CombiDrive ® integrated / connection diagram Function Farben Number Designation Dir. of rotation / r.p.m, green 1 P10+ Dir. of rotation / r.p.m, grey 1 P10+ Dir. of rotation pink 5 DIN1 Dir.
8. Accessoires © STÖBER pl c 199 8 05.02.01 36 8.2 Clear text Di splay Module (Opm2) in IP55 housi ng see chap. 4.1. This section only applies for users who intend using the optional Clear Text Display module (OPm2) to control the opera tion of the CombiDrive ® .
.
Presented by: STÖBER ANTRIEBSTECHNIK GmbH + Co. KG GERMANY Kieselbronner Strasse 12 · 75177 Pforzheim Postfach 910103 · 75091 Pforzheim Fon +49 (0) 7231 582-0, Fax +49 (0) 7231 582-1000 Internet: http://www.stoeber.de / e-Mail: mail@stoeber.de © 2001 STÖBER ANTRIEBSTECHNI K GmbH + Co.
デバイスSiemens CM300/3の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Siemens CM300/3をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSiemens CM300/3の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Siemens CM300/3の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Siemens CM300/3で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Siemens CM300/3を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSiemens CM300/3の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Siemens CM300/3に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSiemens CM300/3デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。