SIMA TIC NET S7-CPs for Industrial Ethernet Manual Part B3L CP 343-1 Lean 6GK7 343 − 1CX10 − 0XE0 as of hardware version 2, as of firmware version V2.
Notes on the Product B3L − 2 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Notes on the Product Product Names This description contains information on the following product S CP 343 − 1 Lean Order number 6GK7 343 − 1CX10 − 0XE0 as of hardware version 2 and firmware version V2.
Contents B3L − 3 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Contents Contents − Part A Ethernet CPs − General information see general part . . . . . . . . . . . . . . . . . . . Note Please remember that Part A of the device manual also belongs to the description of the CP .
Contents B3L − 4 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 6.4.2 Initialization and Configuration B3L − 28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.5 Example of Configuration and Programming B3L − 30 .
1 Properties / Services B3L − 5 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 1 Properties / Services Application The CP 343 − 1 Lean communications processor is designed for operation in a SIMA TIC S7-300 programmable logic controller .
1 Properties / Services B3L − 6 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 S T ime-of-day synchronization over Industrial Ethernet using the following configurable modes: − SIMA TIC mode The CP receives MMS time frames and synchronizes its local time and the time of the CPU (accuracy approx.
1 Properties / Services B3L − 7 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Configuration It is possible to download the configuration data to the CP over MPI or LAN/Industrial Ethernet.
2 Requirements for Use B3L − 8 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 2 Requirements for Use General Operation The CP can be operated in the fol.
2 Requirements for Use B3L − 9 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 T able 2-1 Use of the CP with S7 − 300 CPU Order Number CPU 314 IFM 6ES7.
2 Requirements for Use B3L − 10 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 T able 2-2 Use of the CP in C7 Control Systems C7 Order Number C7 − 613.
3 Installation and Commissioning B3L − 11 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 3 Installation and Commissioning 3.1 Procedure / Steps Step Explanation / Meaning 1. Install the CP on the S7 standard rail.
3 Installation and Commissioning B3L − 12 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Slider for setting the chassis ground contact Attachment to Ind.
3 Installation and Commissioning B3L − 13 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Note The hinged front panel must be kept closed during operation. The module must be installed so that its upper and lower ventilation slits are not covered, allowing adequate ventilation.
4 Displays B3L − 14 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 4 Displays The display on the front panel consists of 8 LEDs that indicate the operating mode and the communication status.
4 Displays B3L − 15 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 LEDs for displaying the mode The different combinations of the LEDs on the front pane.
4 Displays B3L − 16 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 LEDs for displaying the CP communication status In addition to the LEDs that signal the CP state, the following LEDs provide information about the status of the CP interface to Industrial Ethernet.
5 Performance Data B3L − 17 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 5 Performance Data 5.1 Number of Poss ible Connections over Ethernet T able 5.
5 Performance Data B3L − 18 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 5.3 Characteristics of the SEND/RECEIVE Interface T able 5-3 Characteristic E.
5 Performance Data B3L − 19 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 5.4 Characteristic Data for PROFINET IO CP as PROFINET IO device The CP suppo.
6 Configuring and Programming the CP as a PROFINET IO Device B3L − 20 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 6 Configuring and Programming the C.
6 Configuring and Programming the CP as a PROFINET IO Device B3L − 21 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 6.
6 Configuring and Programming the CP as a PROFINET IO Device B3L − 22 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 6.3 Configuration Configuring the CP as a PROFINET IO device involves the two following activities in STEP 7: 1.
6 Configuring and Programming the CP as a PROFINET IO Device B3L − 23 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 2. Check and, if necessary , correct the IP address in the “Properties Ethernet” dialog.
6 Configuring and Programming the CP as a PROFINET IO Device B3L − 24 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 6.3.2 Assigning the PROFINET IO Device to a PROFINET IO Controller PROFINET IO Controller This section describes the configuration of PROFINET IO controllers with STEP 7.
6 Configuring and Programming the CP as a PROFINET IO Device B3L − 25 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Result: Y ou will see the connector symbol for the PROFINET IO system beside the PROFINET IO controller .
6 Configuring and Programming the CP as a PROFINET IO Device B3L − 26 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Step 3: Configuring the properties of the CP as PROFINET IO device Continue configuration in HW Config as follows: 1.
6 Configuring and Programming the CP as a PROFINET IO Device B3L − 27 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 No further parameter assignment of the modules is necessary . Note By selecting suitable network components and setting the network properties (Section 9.
6 Configuring and Programming the CP as a PROFINET IO Device B3L − 28 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Data consistency The length information in the block call must be identical to the total length of the input or output data configured for this PROFINET IO device.
6 Configuring and Programming the CP as a PROFINET IO Device B3L − 29 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Reasons for reinitialization The PR.
6 Configuring and Programming the CP as a PROFINET IO Device B3L − 30 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 6.5 Example of Configuration and Programming The configured input/output modules must be accessed in the user program of the PROFINET IO device using FCs.
6 Configuring and Programming the CP as a PROFINET IO Device B3L − 31 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 T ransfer the process inputs (DB10).
6 Configuring and Programming the CP as a PROFINET IO Device B3L − 32 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 T ransfer the O addresses to the pr.
7 Web Diagnostics B3L − 33 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7 Web Diagnostics With W eb diagnostics, the CP provides you with the option o.
7 Web Diagnostics B3L − 34 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 3. Select the display language you require from the “Language” drop-down list box at the top right. The following languages are available: S English S Deutsch S Français S Español S Italiano 4.
7 Web Diagnostics B3L − 35 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7.2.1 Start Page This page displays general device data and the status of the connected CP . Parameter Function General Station name Configured name of the station in which the CP is installed.
7 Web Diagnostics B3L − 36 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7.2.2 Identification Here, you can see a variety of information on the CP for identification and maintenance. Parameter Function Identification Plant designation 1) Plant designation of the CP if this was configured.
7 Web Diagnostics B3L − 37 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7.2.3 Rack Configuration The slots of the station and general data along with the status of the devices is displayed here.
7 Web Diagnostics B3L − 38 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Parameter Function V ersion Firmware version of the module LED Status LED disp.
7 Web Diagnostics B3L − 39 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7.2.4 Diagnostic Buffer This table lists all the events in the chronological order in which they were received. The latest entry is at the start and the oldest entry at the end of the table.
7 Web Diagnostics B3L − 40 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7.2.5 Industrial Ethernet “Parameters” T ab This page shows you the various parameters of the MAC address, the IP address and the LAN attachments.
7 Web Diagnostics B3L − 41 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 “Statistics” T ab This page displays information on sent and received frames since the last module restart.
7 Web Diagnostics B3L − 42 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 7.2.6 PROFINET IO This page provides you with information on the most important parameters of the PROFINET IO configuration.
7 Web Diagnostics B3L − 43 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Parameter Function Status Status of the device: S OK (problem-free operation) .
8 Compatibility with Predecessor Products B3L − 44 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 8 Compatibility with Predecessor Products 8.1 Extended Functionality New: Enhanced functions compared with module 6GK7 343 − 1CX10 − 0XE0 with firmware version V1.
8 Compatibility with Predecessor Products B3L − 45 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Module Replacement When replacing an older module with.
9 Further Notes on Operation B3L − 46 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 9 Further Notes on Operation 9.
9 Further Notes on Operation B3L − 47 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Behavior after Memory Reset The CPU in the S7 station does not recognize that the CP memory was reset. The CP therefore changes to the “stopped with error” state (see Chapter 4).
9 Further Notes on Operation B3L − 48 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Automatic Setting or Individual Network Settings As default, the CP is configured for automatic detection (autosensing).
9 Further Notes on Operation B3L − 49 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 S Recommendation: Change “individual network settings” only over MPI.
9 Further Notes on Operation B3L − 50 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Access Permissions using Community Name The CP uses the following c.
9 Further Notes on Operation B3L − 51 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 S The connections on which a job on the communication bus with a data length > 240 bytes is being processed are aborted temporarily .
9 Further Notes on Operation B3L − 52 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 9.8 Restart after Detection of a Duplicate IP Address in the Network T o save you time-consuming troubleshooting in the network, the CP detects double addressing in the network.
10 How to Load New Firmware B3L − 53 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 10 How to Load New Firmware Requirements Y ou download new firmware to a SIMA TIC NET CP using the firmware loader shipped with STEP 7 / NCM S7.
1 1 T echnical Specifications B3L − 54 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 1 1 T echnical Specifications Transmission rate 10 Mbps and 100 Mbps Interfaces Connection to Ethernet 2 x RJ − 45 jack Power supply DC +24 V (permitted range: +20.
1 1 T echnical Specifications B3L − 55 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Notice The approvals printed on the purchased device apply .
1 1 T echnical Specifications B3L − 56 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04.
デバイスSiemens CP 343-1の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Siemens CP 343-1をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSiemens CP 343-1の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Siemens CP 343-1の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Siemens CP 343-1で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Siemens CP 343-1を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSiemens CP 343-1の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Siemens CP 343-1に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSiemens CP 343-1デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。