User Manual - USA TPS3 12 & TPS3 15 Surge Prot ective De vice.
• Only qualified licensed electricians should install or ser vice SPDs • Hazardous voltages e xist within SPDs • SPDs should never be installed or serviced when energized • Use appropriat e s.
T able of Contents F AILURE T O FOLLO W THESE INSTRUCTIONS COULD RESUL T IN DEA TH OR SERIOUS INJURY .............................. 2 Do Not Hi-Po t T est SPDs ...........................................................................................
Introduction Thank you for choosing Siemens TPS3 Surge Pro tective Device (SPD). This is a high quality , high energy surge suppres sor designed to prot ect sensitive equipment fr om damaging transient overvoltages. Proper installation is important to maximize per formance.
2008 NEC Ar t 285 & UL 1449-3 SPD T ypes: T ypes 1, 2, 3, & 4 Based on Location within electrical distribution system (also coincides with ANSI/IEEE C62.
TPS SERIES DESCRIPTION TPS3 12 Externally mount ed SPD, single module in enclosure, standard modes of pr ot ection TPS3 L12 Externally mount ed SPD, single module in enclosure, 10 modes of pr otection.
Parallel Connection This is a Parallel connected SPD – not series connected. As outlined previousl y , an SPD ‘drains of f ’ excessiv e voltage fr om an electrical system. Because of parallel connection, installation of the SPD reasonably near the eq uipment to be pro tect ed is satisfactory.
T able 2: Weight & Dimensions TPS3 12 H/W/D (in./mm.) Weight Standar d Enclosure 12" x12" x 7.5" (305x305x191) 22 lbs (10 kg) Standar d Enclosure, 400 – 500kA with Opt. Disc. Switch 16" x 14" x 6" (496x356x152) 32 lbs (14.
T erminals T erminals will accept 14 - 2 A WG conductor and are provided for line (phase), neutral (if used), and equipment safety ground connections. 8 A WG is the minimum recommended wire size because UL testing and evaluation was performed using 8 A WG.
Optional Flush Mount Installation Considerations The TPS3 12 and TPS3 15 are appro ximately 6” deep. The unit will not mount flush unless there is at least 6” of depth clearance. The TPS3 12 and TPS3 15 are not designed to mount flush on a typical 2 x 4 stud wall.
PRE-PL AN INST ALL A TION TO ACC OMPLISH THE FOLLO WING: • Meet all National and Local codes (NEC® Ar ticle 285 addresses SPDs) • Mount SPD as close to panel or equipment as possible to keep leads short • Ensure leads are as shor t and straight as possible, including neutral and ground.
Figure 4: Electrical Dra wings Figur e 1 SPLIT 2 Hots, 1 Neu, 1 Grnd Hot (BLK) Hot (BLK) Neutral (WHT ) V V } } Ground (GRN ) Figur e 2 WYE 3 Hots, 1 Neu, 1 Grnd } Phase A (BLK) Phase B (BLK) Neutral .
Phase A, B & C: Green LED indicators—one per phase. Green is good. Extinguished green LED indicates loss of prot ection. Every suppres sion element in this SPD is monitor ed. N-G suppres sion element monitoring is logic-connected t o Phase A. Ser vice LED (red): LED illuminates in the event of problems.
Dr y Contact Option T wo sets of Form C dr y contacts are included with the Dr y Cont act option. Dry Contacts change state during inoper ative conditions, including loss of power . Any status change can be monitored elsewhere via Dr y Contacts. A T erminal Block includes two sets of Normally Open (N.
Display Replacement The display is field replaceable. Deenergize SPD, confirm with appropriat e measurement equipment and dischar ge internal capacitance to ground. Mark locations and carefully disconnect diagnostic cables, contacts, connecting conduct ors, etc.
Siemens Industr y , Inc. Building T echnologies Division 5400 T riangle Parkway Norcr oss, GA 30092 888-333-3545 info.us@siemens.com 6.17.11.jb #8172.
デバイスSiemens TPS3 12の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Siemens TPS3 12をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSiemens TPS3 12の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Siemens TPS3 12の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Siemens TPS3 12で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Siemens TPS3 12を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSiemens TPS3 12の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Siemens TPS3 12に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSiemens TPS3 12デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。