IMPOR T ANT READ ALL OF THE FOLLO WING W ARNINGS AND ST A TEMENTS BEFORE READING THE INST ALLA TION INSTR UCTIONS The installation must conf or m to the requirements of the authority having jurisdiction or , in the absence of such requirements, to the National Fuel Gas Code , ANSI Z223.
REAR VIEW SIDE VIEW FRONT VIEW TOP VIEW 95 / 8 25 WATER RETURN 1 1/4" NPT (MA LE) G AS PIPE 3/4" NPT 5 1/8 16 3/8 35 / 8 55 / 8 CONDENSATE DRAIN - 3/4" DIA 41 / 4 4" AIR INTAKE CON.
Jaguar Model J-390 3 BOILER CO NTROL FIELD WIRING TERMINALS (24V ) FIELD WIRING TERMINALS (120V ) GAS VALVE TRANFORMER 4" AIR INTAKE CONNECTION 4" VENT CONNECTION SPARK ELECTRODE (IGNITER) H.
Jaguar Model J-390 4 The installation must conf or m to the requirements of the authority having jurisdiction or , in the absence of such requirements, to the National Fuel Gas Code , ANSI Z223.1- latest edition. This installation must also conf or m to the additional require- m ents in this Slant/Fin Instruction Book.
CONT AMINA TION PREVENTION The combustion air supply must not be susceptib le to contami- nation sources, whether the comb ustion air comes from the interior or exterior of the building. Contaminated air can cause c orrosion or other damage to the heat e xchanger and compo- nents of the boiler , causing failure of these parts or unsafe operation.
Jaguar Model J-390 6 F or both direct and non-direct installation, the f ollowing must be considered: - Openings must ne ver be reduced or closed. If doors or win- dows are used f or air supply , they must be loc ked open. - Protect against closure of openings by snow and debris.
Jaguar Model J-390 7 T he vent connector on the boiler is designed to directly accom- modate either PVC/CPVC Schedule 40 pipe or the listed stain- less steel vent systems b y utilizing an adapter . The adapter has a built-in sealing ring, so no additional sealant is required.
Jaguar Model J-390 8 In this case, the maximum str aight pipe vent length that can be utilized with the 4 elbo ws would be: 100’ - (4’ x 10’) = 60’. Since the air intake pipe also is PVC and requires the use of 4 elbows , the maximum straight pipe air intake length that can be utilized is also 60 f eet.
Jaguar Model J-390 9 JAGUAR J-390 NON-DIRECT VENT , SIDEW ALL VENTING All joints must be liquid and pressure tight. Use 4” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 4" dia. AL29-4C S.S .*. venting materials (See page 7). AIR INTAKE ( DO NOT BL0CK ) A U/L LISTED FLASHING AND SEALING B OOT MUST BE USED ON C OMBUSTIBLE W ALLS.
Jaguar Model J-390 10 JAGUAR J-390 NON-DIRECT VENT , VENTING THROUGH A ROOF All joints must be liquid and pressure tight. Use 4” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 4" dia.
Jaguar Model J-390 11 JAGUAR J-390 NON - DIRECT VENT , UTILIZING AN EXISTING CHIMNEY AS A CHASE All joints must be liquid and pressure tight. Use 4” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 4" dia. AL29-4C S.S .*. venting materials (See page 7).
Jaguar Model J-390 12 JAGUAR J-390 - DIRECT VENT , SIDEW ALL VENTING All joints must be liquid and pressure tight. Use 4” dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 4" dia.
Jaguar Model J-390 13 Figure 12a. V ent/Air intake termination; utilizing PVC/CPVC pipe f or venting. Figure 12b. V ent/Air intake termination; utilizing stainless steel venting materials.
Jaguar Model J-390 14 V ENT/AIR INT AKE TERMINA TION FOR PVC/CPVC V ENTING INST ALLA TION This termination is designed specifically for 4” diameter PVC or CPVC Schedule 40 pipe to be used as the vent and air intak e piping material, only . It can be used on a combustible w all, provided that the w all passage is cut out as specified in step 5.
Jaguar Model J-390 15 B. DIRECT VENT - VENTING AND AIR INT AKE THROUGH A R OOF F igure 13 shows typical v er tical venting. The vent pipe must p ass through the ceiling, floor and the roof vertically through a 8” minimum diameter cutout. A fire stop is required for each ceiling and floor penetration.
Jaguar Model J-390 16 VENTING AND AIR INT AKE SYSTEM REGULAR INSPECTION A. Inspect the system regularly for condensation, corrosion, sagging and/or ph ysical damage. A qualified professional should ser vice the boiler annually and include such an i nspection at that time.
Jaguar Model J-390 17 A t 30 ft. length of pipe, match required capacity from table on t his page (choose higher capacity , in this case is 590 cu. ft. per hour). Required pipe size is 1 1 ⁄ 4 ". I mproper gas pipe sizing will result in flame outages, insuffi- cient heat and other installation difficulties.
Jaguar Model J-390 18 WIRE LEGEND: 1 CAUTION: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 12 3 4 56 78 HN H N HN 1 2 3 4 5 6 12 3 1 2 3 4 W W BL R B L DISPLAY BK BK G BK BK G W G ROUN D R Y PR PK BR BK PR BK W 1 2 3 4 5 6 7 BK R Y W 1 W W W BK BK BK W W W Y LABEL A LL WIRE S PRIOR TO DI SCONNECT ION WHEN SERVI CIN G CONT ROLS.
Jaguar Model J-390 19 ARGUS VISIO N CON TRO L NOT USED NOT USED T2 J12 J13 SPARK IGNITO R SPARK CABLE GROUND FUSE J9 J6 J2 J5 BOILER CONT ROL Figure 15b.
Jaguar Model J-390 20 GND NEUTRAL HOT L2 L1 120V/6 0H Z 120V 10V 120V 24V DISPLAY WATER HIGH LIMIT "CALL FOR HEAT" 24V ROOM THERMOSTAT DHW THERMOSTAT (IF USED) OR SENSOR LOW WATER CUT OFF (I.
Jaguar Model J-390 21 1 END SWITCH TH-TR MO T OR 2 T T T T T T T T T T T T T T T T T 3 4 5 6 SP ACE HEA TING SYSTEM CIRCU LA T OR END SWITCH TH-TR MO T OR ZON E 2 THERMOS TAT V8043E/F END SWITCH TH-TR.
Jaguar Model J-390 22 Figure 16b. Multizoning of Bobcat Jaguar; pump zoning system using R845A rela y . 12345678 FIELD WIRING TERMINALS ON BOILER 1 2 T T 3 4 5 6 T T T T LI L2 DISCONNECT SWITCH 1 R84 5A RELA Y ZONE 3 CIRC. ZON E 3 R84 5A RELA Y ZONE 2 CIRC.
Jaguar Model J-390 23 Figure 16c. Multizoning of Jaguar boiler; pump zoning system using R882A/B rela ys. LI L2 1 DISCONNECT SWI TCH 120V/24V TRANSFORMER FI ELD WIRING TERMINALS ON BOILER CI RC. Z ONE 3 Z ONE 3 THERMOS TAT 1 POWER SUPPL Y , PROVIDE DISCONNECT MEANS AND OVER LOA D PROTECTION AS REQUIRED.
Jaguar Model J-390 24 W A TER PIPING 1. Connection of system to boiler: P rimar y/secondar y piping of the system is recommended, to e nsure the proper flow through the boiler .
Jaguar Model J-390 25 FOR PROTOTYP E ONLY PIPING ORIENTATION FO R REFERENCE ONLY. Plublicatio n No. : J-40 WATER OUTLET PIPING TO REST OF THE S YSTEM PROBE TYPE LOW WATER CUTOFF (IF REQUIRED) PRES SUR.
Jaguar Model J-390 26 T ab le 2. Jaguar boiler recommended pump models for domestic hot water tank piping. Flow Rate (gpm) T emp Rise (˚F) Boiler Head Loss (Feet w .c.) Domestic Water T ank Piping Head Loss ** (Feet w .c.) A vailable Head Capability f or V arious Model Circulator s to Overcome DHW T ank Head Loss (Feet w .
Jaguar Model J-390 27 I SOLAT ION VAL VE B OILER L O OP P URGE/ VAL VE D RAI N T HE BOIL ER) CIRCUL ATOR (SUPPL IED WITH I SOLATI ON V ALVE FLOW CHE CK VALVE F igure20.
Jaguar Model J-390 28 ISOLATIO N VALVE B OI LER LO OP P URG E/ VALVE DRAIN THE BOILER) CI RCULAT OR ( SUPPLIED WITH IS OL AT IO N VALVE FLO W CHE CK VALVE Figure20.
Jaguar Model J-390 29 C HILLER W ATER VALVE VALVE UNIT STRAINER INL ET (RE TURN) BOILE R WATER CIRCUL ATO R BOILER LOO P VALV E I SOLATI ON 1 2" AP ART D ON O TE X C E E D DRAI N VAL VE P URGE / .
Jaguar Model J-390 30 OPERA TING INSTRUCTIONS I. FILLING AND VENTING W A TER SYSTEMS A . Fill the system with water . V ent or purge of air . B. Fire the boiler as soon as possible (see f ollowing warning and instructions) and bring water temperature in the system.
Jaguar Model J-390 31 "TEMPERA TURE" D ISPLAY (3 DIG ITS) "UP" PUS H BUTTO N "DOWN" PUSH B UTTON "ENTER" P USH BUTTO N "SELE CT" PUSH BUTTO N "BURNER S TATUS " STEADY DOT = BURNER ON BLINKING DOT = BU RNER OFF "MODE" DISP LAY "RESET" PU SH BU TTON Figure 22.
Jaguar Model J-390 32 M ODE DISPLA Y DESCRIPTION & TEMPERA TURE DISPLA Y Space heating supply water temperature could be changed b y pressing “Up/Down” button. Settable from 90˚F to 185˚F (steps of 1 F). The default v alue is 176˚F . Press “Enter” b utton to store.
Jaguar Model J-390 33 MODE DISPLA Y DESCRIPTION Changing space heating post pump time. Settable from 10 to 900 seconds. (steps of 10 seconds). The default v alue is 30 seconds. Changing DHW post pump time. Settable from 1 to 255 seconds. (steps of 1 seconds).
Jaguar Model J-390 34 70 70 60 -20 - 10 -30 0 10 20 30 40 50 Outdoor Te mp. (° F) Wat er Supply Targ et Temp . (° F) 185 ° F 140 150 130 190 180 170 160 120 110 100 80 90 2 00 S l o p e = 4 . 0 S l o p e = 3 . 0 S l o p e = 0 . 1 ( m i n . ) S l o p e = 2 .
Jaguar Model J-390 35 III. INITIAL ST ART Saf e lighting and other perf ormance cr iteria were met when testing various gas manif old and control assemblies used on the Jaguar J-390 boiler under the ANSI Z21.13 - latest edition. Instructions F ollow the lighting instructions in this manual.
Jaguar Model J-390 36 THERMOST A T CALLS FOR HEA T CIRCULA T OR(S) ON 5 SECOND PRE-PURGE PERIOD J A GU AR MODEL J-390 SEQ UENCE OF OPERA TION BLO WER SPEED CONFIRMED? GAS V AL VE OPENS GAS V AL VE REMAINS OPEN. CONTR OL CONTINUOUSL Y MONIT ORS THERMOST A T , HIGH LIMIT , W A TER SENSORS, BLO WER SPEED , FLAME SIGNAL, AND L WCO (IF USED).
Jaguar Model J-390 37 IV . CHECK COMBUSTION AND FUEL INPUT RA TE A. Star t and run the burner at the high fir ing rate, b y using the “System T est” mode in the “Vie w and changing system setting” menu. Refer to T able 5 on page 33. 1. Measure the CO , and CO 2 of the flue gas.
Jaguar Model J-390 38 V . SAFETY CHECK A. Check f or gas leaks: Using soap solution, check f or gas leaks from meter to gas valv e including all pipes and fittings and gas valv e connections. Use liquid soap solution for all gas testing. DO NO T use open flame.
Jaguar Model J-390 39 B. BLOCKING ERRORS: Indicated by an “E” in the mode displa y . Operation is automatically restored, once the condition retur ns to nor mal or is fix ed. The temperature displa y shows the error code. Pressing the “Reset” b utton is not required.
Jaguar Model J-390 40 ERROR CODE INDICA TION REMED Y 30 Excess Flue T emperature Check flue gas temper ature, at the maximum firing rate and high water temper ature. If the flue gas temperature reaches 212˚F , check the fuel input rate and comb ustion.
Jaguar Model J-390 41 CARE AND MAINTENANCE This section must be brought to the attention of the owner b y the installer so that the owner can mak e the necessar y arrange- ments with a qualified ser vice agency f or the periodic care and maintenance of the boiler .
Jaguar Model J-390 42 GENERAL TR OUBLESHOO TING GUIDE FOR SER VICE PERSONNEL W ARNING: Only a trained, e xper ienced ser vice technician should perform troubleshooting. T ur n off all electr ical power to the boiler bef ore ser vicing. A. BURNER F AILS T O OPERA TE - NO HEA T CA USE REMED Y 1.
Jaguar Model J-390 43 NO TES.
SLANT/FIN CORPORA TION, Green vale, N.Y . 11548 • Phone: (516) 484-2600 F AX: (516) 484-5921 • Canada: Slant/Fin L TD/L TEE , Mississauga, Ontar io www .
デバイスSlant/Fin J-390の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Slant/Fin J-390をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSlant/Fin J-390の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Slant/Fin J-390の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Slant/Fin J-390で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Slant/Fin J-390を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSlant/Fin J-390の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Slant/Fin J-390に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSlant/Fin J-390デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。