Slant/FinメーカーVHS-180の使用説明書/サービス説明書
ページ先へ移動 of 27
HO T W A TER MODELS VHS-30 THR OUGH VHS-180 GAS-FIRED CAST -IR ON BOILERS FOR NA TURAL AND L.P . PR OP ANE GASES IMPOR T ANT READ ALL OF THE FOLLO WING W ARNINGS AND ST A TEMENTS BEFORE READING THE INST ALLA TION INSTR UCTIONS W ARNING LIQUEFIED PETROLEUM (L.
V I CTOR Y II V HS Models NO TE: Height dimensions increase by 1 3 ⁄ 4 " and depth increases to 22 1 ⁄ 4 " when combustib le floor kit is used.
V I CTOR Y II V HS Models INST ALLA TION REQUIREMENTS The installation must conf or m to the requirements of the a uthority having jurisdiction or , in the absence of such requirements, to the National Fuel Gas Code , ANSI Z223.
V I CTOR Y II V HS Models BOILER ROOM AIR SUPPL Y AND VENTILA TION An ample supply of air is required f or combustion and v enti- l ation. When buildings are insulated, caulked and w eather- stripped, now or later on, direct openings to outside ma y be required and should be provided.
V I CTOR Y II V HS Models CA TEGOR Y II AND III VENTING 1. V ent Material A) The vent system f or horizontal or vertical venting (Categor y II and III ) must be UL listed single wall 3" diameter AL29-4C s stainless steel material.
V I CTOR Y II V HS Models Heat-Fab Saf-T V ent System Boiler Model No . Minimum Length, Ft. 0 to 5500 Ft. Altitudes 5500 to 7000 Ft. Altitudes 7000 to 10,000 Ft.
V I CTOR Y II V HS Models Figure 6 Figure 5 VICT OR Y II HORIZONT AL (SIDEW ALL) VENTING All joints must be liquid and pressure tight. Use U/L listed single wall 3" dia. AL29-4C* S.S . venting materials * Definition of Snow Line: Knowledge of local conditions will re veal the maximum height that repeated snowf alls accumulate to.
V I CTOR Y II V HS Models 8 Figure 7..
V I CTOR Y II V HS Models Figure 8. 9.
V I CTOR Y II V HS Models 10 CA TEGOR Y I VENTING (Natural Draft Chimney and T ype “B” V enting) 1. Installation Model VHS-90, VHS-120, VHS-150 and VHS-180 may be v ented into a natur al draft mas.
V I CTOR Y II V HS Models T able 1. Masonry Vitreous Tile-Lined Chimney (not metal lined) C himneys not e xposed to the outdoors below the roof line. (5" dia. vent adapter must be used) Natural Draft Chimney and T ype “B” V enting T ables A dditional National Fuel Gas Code Boiler Gas Appliance Reference T able No.
V I CTOR Y II V HS Models 12 Figure 9..
V I CTOR Y II V HS Models Figure 10. 13.
V I CTOR Y II V HS Models 14 VENTING SYSTEM REGULAR INSPECTION A. Inspect the system regularly f or condensation, corrosion and/or ph ysical damage. A qualified prof essional should ser- vice the boiler annually and include such an inspection at that time.
V I CTOR Y II V HS Models Figure 11a. Figure 11b. W A TER PIPING Alwa ys f ollow good piping practices . Obser ve minimum 1" clearance to comb ustibles around all uninsulated hot water pipes or when openings around pipes are not protected by non-combustib le materials.
V I CTOR Y II V HS Models 16.
V I CTOR Y II V HS Models Figure 14. Figure 15. Piping Arrangement 17.
V I CTOR Y II V HS Models 18 An automatic air vent is used to remo ve air from the sys- tem. It should be installed in the top of the boiler as shown i n Figure 15. If system pressure needs fur ther control, add an additional tank in parallel with original tank or install a larger capacity tank.
V I CTOR Y II V HS Models Instructions F ollow the lighting instructions in this manual. These instruc- t ions are also attached to the boiler . SAFETY INFORMA TION F or Y o ur Saf e ty Read Bef o re .
V I CTOR Y II V HS Models The gas metered in 3 minutes to obtain rated input f or e ach boiler model , using 1000 Btu/cu. ft. gas, is tab u- lated in gas rate table . B. Main Bur ners 1. Fire the boiler continuously for at least 15 min utes, to reach burner operating temperature.
V I CTOR Y II V HS Models 1. High Limit Control T est Set thermostat high enough for water temperature to reach high limit control setting of Aquastat. When this temperature is reached, the high limit s witch should open and the main gas valv e should close automatically .
V I CTOR Y II V HS Models 22 3. P erf or m “V enting System Regular Inspection” on P age 14. C . Piping Check the f ollowing: 1. W ater piping and accessories for leaks. Slightest l eaks should be corrected. 2. System to be full of water and pressure to remain stable at correct setting on gauge .
V I CTOR Y II V HS Models THERMOST A T CALLS FOR HEA T CIRCULA TOR ON IGNITION SP ARK ST AR TS AND PILO T V AL VE OPERA TOR OPENS THERMOST A T CALLS FOR HEA T ENDS CIRCULA TOR OFF .
V I CTOR Y II V HS Models BURNERS F AIL T O OPERA TE CA USE REMED Y 1. Gas supply valv e shut off 1. Open gas valve 2. No power , main electr ic s witch open 2. Close switch 3. No power , blown or def ective line fuse 3. Replace fuse 4. Pilot flame too low 4.
V I CTOR Y II V HS Models 25 DELA YED IGNITION CA USE REMED Y 1 . Pilot flame too low 1. Adjust pilot flame 2. Excessiv e primar y air 2. Adjust pr imary air shutter 3. Excessiv e burner input 3. Check and reduce to input shown on rating plate NO T ENOUGH HEA T CA USE REMED Y 1.
V I CTOR Y II V HS Models 26 A PPENDIX A V ent System Location and Condensation Drain Requirements 1 . The v enting system shall ter minate at least 3 feet abov e any forced air inlet located within 10 f eet.
SLANT/FIN CORPORA TION, Green vale, N.Y . 11548 • Phone: (516) 484-2600 F AX: (516) 484-5921 • Canada: Slant/Fin L TD/L TEE , Mississauga, Ontario www .
デバイスSlant/Fin VHS-180の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Slant/Fin VHS-180をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSlant/Fin VHS-180の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Slant/Fin VHS-180の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Slant/Fin VHS-180で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Slant/Fin VHS-180を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSlant/Fin VHS-180の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Slant/Fin VHS-180に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSlant/Fin VHS-180デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。