IMPOR T ANT READ ALL OF THE FOLLO WING W ARNINGS AND ST A TEMENTS BEFORE READING THE INST ALLA TION INSTR UCTIONS W ARNING LIQUEFIED PETROLEUM (L.P .) PROP ANE GAS-FIRED BOILERS Installation location ONL Y as permitted in paragraph entitled "LIQUEFIED PETROLEUM (L.
V I CTOR Y VSPH Models 2 NO TE: Height dimensions increase by 1 1 ⁄ 2 " and depth increases to 28 1 ⁄ 2 " when combustib le floor kit is used.
V I CTOR Y VSPH Models 3 LOCA TION AND IDENTIFICA TION OF P ARTS Figure 2. Location and identification of par ts Base Assemb ly.
V I CTOR Y VSPH Models 4 The installation must conf or m to the requirements of the authority having jurisdiction or , in the absence of such requirements, to the National Fuel Gas Code , ANSI Z223.1- latest edition. This installation must also conf or m to the additional require- ments in this Slant/Fin Instruction Book.
VENTING APPLICA TION V SPH Series are sealed combustion type boilers, the y maybe installed and vented either as a direct v ent boiler which all air f or combustion is obtained directly from outside or as a non- direct vent boiler which air f or combustion is tak en from inside the boiler room.
When joining the various components of the abo ve listed v ent systems , the manufacturers’ instructions should be closely f ollowed to insure proper sealing. Use sealant speci- fied by v ent system manufacturer f or sealing of pipe and fit- tings. See Figure 4 for proper application of v ent pipe sealing f or Saf-T vent system by Heat-F ab, Inc.
V I CTOR Y VSPH Models 7 Maximum allo wed flue and air intake equivalent length (Feet) fo r Heat-Fab Saf-T vent system (Inc luding EZ Seal) Boiler Model Number Piping 0- 5,000 Ft.
V I CTOR Y VSPH Models 8 V ENTING INST ALLA TION F ollow the v ent mater ial manuf acturer’ s instr uctions in con- junction with these instructions for v enting system installa- t ion.
V I CTOR Y VSPH Models 9 VICTOR Y VSPH MODELS NON - DIRECT VENT , SIDEW ALL VENTING All joints must be liquid and pressure tight. Use U/L listed single wall 3" dia. AL29-4C S.S .*. venting materials (See page 5). Definition of Snow Line: Knowledge of local conditions will re veal the maximum height that repeated snowf alls accumulate to .
V I CTOR Y VSPH Models 10 VICTOR Y VSPH MODELS- NON- DIRECT VENT , VENTING THROUGH A ROOF All joints must be liquid and pressure tight. Use U/L listed single wall 3" dia.
V I CTOR Y VSPH Models 11 VICTOR Y VSPH MODELS- NON - DIRECT VENT , UTILIZING AN EXISTING CHIMNEY AS A CHASE All joints must be liquid and pressure tight. Use U/L listed single wall 3" dia. AL29-4C* S.S . venting materials (See page 5). Figure 8.
V I CTOR Y VSPH Models 12 VICTOR Y VSPH MODELS - DIRECT VENT , SIDEW ALL VENTING All joints must be liquid and pressure tight. Use U/L listed single wall 3" dia. AL29-4C* S.S . venting materials (See page 5). Figure 9. Direct vent, side wall venting illustration; with straight horizontal vent.
V I CTOR Y VSPH Models 13 Figure 11. V ent/Air Intake T ermination 10. F rom inside, install inside termination plate using 4 screws . Make sure the 4" collar on the plate, penetrate- ed into the galvaniz ed pipe. 1 1. Assemble and seal straight screened termination to the slip joint connector .
V I CTOR Y VSPH Models 14 Figure 12. Direct vent, venting and air intake thr ough a roof. VICTOR Y VSPH MODELS DIRECT VENT , VENTING AND AIR INT AKE THROUGH A ROOF All joints in vent system m ust be liquid and pressure tight. Use U/L listed single wall 3” dia.
V I CTOR Y VSPH Models 15 VENTING AND AIR INT AKE SYSTEM REGULAR INSPECTION A . Inspect the system regularly for condensation, corrosion a nd/or ph ysical damage. A qualified professional should ser- vice the boiler annually and include such an inspection at that time.
V I CTOR Y VSPH Models 16 PI LO T B UR NER BU R NER MODEL UT-1107 MODEL UT-1107 P5 P5 P4 P4 P1 P1 P6 P6 P2 P2 P3 P3 INTEG RA TED BOILER CONTR OL INTEGR A TED BOILER CONTR OL P6 P6 THERMOST A T THERMOS.
V I CTOR Y VSPH Models 17 MUL TIZONING OF VSPH BOILER ZONE V AL VE SYSTEM USING V8043E/F ZONE V AL VES Figure 14. MUL TIZONING OF VSPH BOILER PUMP ZONING SYSTEM USING R845A RELA Y Figure 15. MUL TIZONING OF VSPH BOILER PUMP ZONING SYSTEM USING R882A/B RELA YS Figure 16.
V I CTOR Y VSPH Models 18 2. P ower Connection A. Remove electrical junction bo x cover . B. Hot connection lead is black. Neutral connection lead is white. Proper polarity is important f or VSPH boilers. Re versed polarity will cause system lockout and the po wer LED will flash continuously .
V I CTOR Y VSPH Models 19 5. Cold Water Fill P ressure reducing (fill) valv e and shut-off valv e should be installed. 6 . Relief V alve Discharge Piping Use same size or larger piping than v alve outlet. Must ter- minate 6" minimum from floor with a plain (no threads) end.
V I CTOR Y VSPH Models 20 I I. Initial Star t Saf e lighting and other perf ormance cr iteria were met when testing various gas manif old and control assemblies used on the Victor y VSP Ser ies Boilers under the ANSI Z21.13- latest edition. Instructions F ollow the lighting instructions in this manual.
V I CTOR Y VSPH Models 21 THERMOST A T CALLS FOR HEA T CIRCULA T OR ON INDUCER (BLO WER) ON VSPH BOILER SEQUENCE OF OPERA TION BOILER W A TER TEMPERA TURE IS B ELO W HIGH LIMIT SETTING? PRESSURE SWITC.
V I CTOR Y VSPH Models 22 a. Input for PR OP ANE is approximately at rating sho wn on ating plate when manif old pressure is 9- 1 ⁄ 2 " water column b . Input for NA TURAL GAS is approximately at rating whe n manifold pressure is 3-1/2" w ater column, but should be check ed on the gas meter : B tuh Input = Btu/cu.
V I CTOR Y VSPH Models 23 T o reset the lock out condition: T urn down ther mostat or turn power off at disconnect s witch for at least 45 seconds , then restore power or set thermostat at desired setting. A utomatic reset: After one hour (1/2 hour for flame f ailure), control will automatically retr y .
V I CTOR Y VSPH Models 24 CARE AND MAINTENANCE This section must be brought to the attention of the owner b y the installer so that the owner can mak e the necessar y arrangements with a qualified service agency for the periodic care and maintenance of the boiler .
V I CTOR Y VSPH Models 25 General T r oubleshooting Guide For Service Per sonnel TOP JACKET TOP JACKET F LU E CO LL ECTO R FLU E CO LL ECTO R I ND U CE R IND UC E R B RUSH BRU SH W ARNING: Only a trained, e xper ienced ser vice technician should perf or m troubleshooting.
V I CTOR Y VSPH Models 26 CA USE 8. Defectiv e pressure switch. POWER and PRES SWITCH LED’ s flashing 9. Defectiv e high limit control 10. Def ective inducer motor 11. Def ective gas v alve 12. Def ective boiler control module REMED Y 8. Check pressure s witch.
V I CTOR Y VSPH Models 27 D . BURNER SHORT CYCLES CA USE 1. Thermostat heat anticipator set too low . 2. Excessive pressure drop due to e xcess venting or air intak e system. 3 . Blockage or restriction in venting or air intak e system. 4. Def ective air flo w switch (out of adjustment).
SLANT/FIN CORPORA TION, Green vale, N.Y . 11548 • Phone: (516) 484-2600 F AX: (516) 484-5921 • Canada: Slant/Fin L TD/L TEE , Mississauga, Ontario www .
デバイスSlant/Fin VSPH-180の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Slant/Fin VSPH-180をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSlant/Fin VSPH-180の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Slant/Fin VSPH-180の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Slant/Fin VSPH-180で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Slant/Fin VSPH-180を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSlant/Fin VSPH-180の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Slant/Fin VSPH-180に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSlant/Fin VSPH-180デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。