/ Mar le y Class 160 Cooling T ower /.
2 / The Mar ley Dif f er ence / Y ou’ll enjoy single sour ce responsibility and reliability because we design and manufacture virtually all major cooling tower components. All Marley components are designed and selected to be part of an integrated system .
3 / Constr uction and Components / ■ Fill/Louvers/Drift Eliminators Marley high-performance lm ll is the heart of every Class 160 tower . A r epeating chevron patter n provides the wetted surface and air turbulence necessary for proper heat transfer , while minimizing resistance to airow so you’ll save on fan power .
4 Class 160 towers offer the benets of adjustable pitch propeller type fans. All fans used on Class 160 towers include hollow GRE (glass-reinfor ced epoxy) blades and epoxy-coated cast iron or galvanized steel hubs.
5 The primary structural elements of all Class 160 towers are the nominal 4 ″ x 4 ″ columns spaced on 4 ′ -0 ″ longitudinal centers. A system of nominal 4 ″ x 4 ″ tower diagonals carries loads in both tension and compression to heavy-duty hot dip galvanized steel anchor plates.
6 / Oper ating and Envir onmental Consider ations / Caution The cooling tower must be located at such distance and direction to avoid the possibility of contaminated tower discharge air being drawn into building fresh air intake ducts.
7 / T o wer Sc hematic / 1. Last number of model indicates number of cells. Change as appropriate for your selection. Primary engineering data is per cell. 2. Fan hp is usually less than shown here. 3. Height shown is from base of tower columns to fan deck.
8 / St eel Basin Support / 1. Use this bulletin for preliminary layouts only . All dimensions show column locations, not anchor bolt locations. Obtain current drawings from your Marley sales r epresentative befor e designing supports. 2. Other contractors or purchaser must design and er ect support- ing steel.
9 1. Use this bulletin for preliminary layouts only . Do not use for construction. Obtain current drawings fr om your Marley sales repr esentative. Concrete basin design and construction ar e by other contractors or purchaser . 2. Operating weight is total wet operating weight of tower only , excluding water in concrete basin.
10 / Inlet Piping Plan / G BASE OF T OWER COL. INLET C L B DIA. FLOW CONTROL V AL VE AND CROSSO VER PIPE R E W O 4 L E D O - - 0 ' L L E # R E P S N O I S N E M I $ ! " # $ % & ' .
11 ■ Cell Partition Options Every Class 160 tower includes plenum partitions and hot water distribution basin partitions between adjacent cells. Plenum partitions keep air from entering an operating cell through an adjacent idle fan—assuring consistent thermal performance.
/ A v ailable Options / Accessory Description and Remarks Accessory Description and Remarks Fan Cylinder Extension Optional ared fan cylinder extensions improve fan efciency to r educe your operating costs. Cell Partition Extra partitions between fan cells for specic operating considerations.
デバイスSPX Cooling Technologies 160の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
SPX Cooling Technologies 160をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSPX Cooling Technologies 160の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。SPX Cooling Technologies 160の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。SPX Cooling Technologies 160で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
SPX Cooling Technologies 160を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSPX Cooling Technologies 160の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、SPX Cooling Technologies 160に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSPX Cooling Technologies 160デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。