/ Mar le y Class F40 0 Cooling T ower / User Manual 93-1288A.
2 Contents These instructions assist in obtaining efficient, long life from Marley counterflow cooling towers. Direct questions concerning cooling tower operation and maintenance to your Marley sales representative. Al- ways include your tower serial number when writing for information or ordering parts.
3 Before Start-up Among other sources, outbreaks of Legionnaires’ disease have re- portedly been traced to cooling towers. Maintenance procedures that prevent amplification and dissemination of Leg.
4 The oil level placard must be adjusted so that its “full” mark is at the same elevation as the “full” mark on the side of the Gear educer case. Check oil lines to be sure there are no leaks. See Geareducer User Manual for oil filling procedur e and list of recommended lubricants.
5 TOWER PERFORMANCE –Keep the cooling tower clean and water dis- tribution uniform to obtain continued maximum cooling capacity . The capacity of a cooling tower to cool water to a given cold water tem- perature varies with the wet-bulb temperature and the heat load applied to the cooling tower .
6 Caution cold weather operation will be enhanced if you read “Operating Cooling T owers in Freezing W eather” Marley T echnical Report #H-003 . Ice forming characteristics on any given cooling tower will vary , depending on velocity and direction of wind, circulating water rate, and heat load.
7 least tower maintenance. See Cooling T ower Inspection Check List in this manual. Keep a continuous lubrication and maintenance r ecord for each cooling tower . HOT W A TER DISTRIBUTION SYSTEM –Keep the circulating water and distribution system (piping and nozzles) clean and free of dirt, algae, and scale.
8 W ater T reatment BLOWDOWN –Blowdown, or bleed-of f, is the continuous r emoval of a portion of the water from the circulating system. Blowdown is used to prevent the dissolved solids from concentrating to the point where they will form scale.
9 compounds which contain copper are not recommended. Chlorine and chlorine containing compounds are effective algaecides and slimicides. If used, chlorine should be added as intermittent (or shock) treatment only as fr equently as needed to control the slime and algae.
.
class F400.
12 Spare Parts SPX Cooling T echnologies manufactur es and maintains a stock of re- placement parts for all cooling tower mechanical equipment. Shipment of these parts ar e normally made within ten days after an order is received. If emer gency service is necessary , contact the local Marley representative for assistance.
13 Geareducer (shutdown for 3 months or mor e). 1. If the motors have space heaters, operate mechanical equipment one hour each month. 2. If the motors do not have space heaters, operate mechanical equipment one hour each week. 3. At startup, operate mechanical equipment one hour or until oil is warm, then shut the equipment down.
14 T r oubleshooting Remedy 1. Check power at starter . Correct any bad connections be- tween the control apparatus and the motor . 2. Check starter contacts and control circuit. Reset overloads, close contacts, reset tripped switches or r eplace failed con- trol switches.
15 Ladders, Stairways, Walkways, Handrails, Covers, Decks and Access Doors Davits, Derricks, and Hoists Inspect for General Condition Semi-annually Semi-annually Inspect and Repair for Safe U.
16 Inspection and Maintenance Schedule General Recommendations —more frequent inspection and mainte- nance may be desirable D–Daily W–W eekly M–Monthly Q–Quarterly S–Semiannually Y–Y early R–as Required 1. Inspect for clogging M M W W 2.
17 Inspection and Maintenance Notes.
18 Date Inspected Inspected By Owner Location Owner’ s T ower Designation T ower Manufacturer Model No. Serial No. Process Served by T ower Operation: Continuous Intermittent Seasonal Design Conditi.
19 Mechanical Equipment Gear Drive Units Manufacturer Model Ratio Oil Level: Full Add Immediately Low , check again soon Oil Condition: Good Contains W ater Contains Metal Contains Sludge Oil Used—t.
7 401 WEST 129 STRE ET | O VE R LAN D P AR K, KANSAS 66213 U N ITE D ST A TES | 913 664 7 4 00 | spxcooling@spx.com | spxcooling.com In the interest of technological progress, all products are subject to design and/or material c hange without notice. ©2009 S PX Cooling T echnologies, Inc.
デバイスSPX Cooling Technologies F400の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
SPX Cooling Technologies F400をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSPX Cooling Technologies F400の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。SPX Cooling Technologies F400の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。SPX Cooling Technologies F400で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
SPX Cooling Technologies F400を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSPX Cooling Technologies F400の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、SPX Cooling Technologies F400に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSPX Cooling Technologies F400デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。