/ Marley Class F4 00 Cooling T o wer / User Manual 93-12 88A.
2 Contents These instructions assist in obtaining efficient, long life from Marley counterflow cooling towers. Direct questions concerning cooling tower operation and maintenance to your Marley sales represen- tative. Always include your tower serial number when writing for information or ordering parts.
3 B efore Start-up Among other sources, outbreaks of L egionnaires’ disease have reportedly been traced to cooling tower s. Maintenance procedures that prevent amplifi cation and dissemination of L.
4 oil level placard must be adjusted so that its “full” mark is at the s ame eleva- tion as the “full” mark on the side of the Geareducer case. Check oil lines to be sure there are no leaks. See Geareducer User Manual for oil filling procedure and list of recommended lubricants.
5 TO WE R PE R F OR MAN CE –K eep the cooling tower clean and water distribu- tion uniform to obtain continued maximum cooling capacity. The capacity of a cooling tower to cool water to a given cold water tempera- ture varies with the wet-bulb temperature and the heat load applied to the cooling tower .
6 Caution operation will be enhanced if you read “Operating Cooling T owers in Freezing W eather” Marley T echnical Repor t #H-003. Ice forming characteristics on any given cooling tower will vary, depending on velocity and direction of wind, circulating water rate, and heat load.
7 tenance. See Cooling T ower Inspection Chec k List in this manual. Keep a continuous lubrication and maintenance record for each cooling tower . HOT W A TE R D I STR I B UTI ON SY STE M –Keep the circulating water and distribution system (piping and nozzles) clean and free of dirt, algae, and scale.
8 Water T reatment B LO WD OWN –Blowdown, or bleed-off, is the continuous removal of a portion of the water from the circulating system. Blowdown is used to prevent the dissolved solids from concentrating to the point where they will form scale.
9 copper are not recommended. Chlorine and chlorine cont aining compounds are effective algaecides and slimicides. If used, chlorine should be added as intermittent (or shock) treatment only as frequently as needed to control the slime and algae.
.
.
12 Spare Parts SPX Cooling T echnologies manufactures and maint ains a stock of replacement parts for all cooling tower mechanical equipment. Shipment of these parts are normally made within ten days after an order is received. If emergency service is necessary, contact the local Marley representative for assist ance.
13 Geareducer (shutdown for 3 months or more). 1. If the motors have space heaters, operate mec hanical equipment one hour each month. 2. If the motors do not have space heaters, operate mechanical equipment one hour each week. 3. At st artup, operate mechanical equipment one hour or until oil is warm, then shut the equipment down.
14 T roubleshooting Remedy 1. Check power at starter . Correct any bad connections between the control apparatus and the motor . 2. Check starter cont acts and control circuit. Reset overloads, close contacts, reset tripped switches or replace failed control switches.
15 Ladders, Stairways, W alkways, Handrails, Covers, Decks and Access Doors Davits, Derricks, and Hoists Inspect for General Condition Semi-annually Semi-annually Inspect and Repair for Safe Use Y ear.
16 Inspection and Maintenance Schedule General Recommendations —more frequent inspection and mainte- nance may be desirable D–Daily W–W eekly M–Monthly Q–Quarterly S–Semiannually Y –Y early R–as Required 1. Inspect for clogging M M W W 2.
17 Inspection and Maintenance Notes.
18 Date Inspected Inspected By Owner Location Owner’s T ower Designation T ower Manufacturer Model No. Serial No. Process Served by T ower Operation: Continuous q Intermittent q Seasonal q Design Co.
19 Mechanical Equipment Gear Drive Units Manufacturer Model Ratio Oil Level: Full q Add Immediately q Low , chec k again soon q Oil Condition: Good q Contains W ater q Contains Met al q Contains Sludg.
7 401 WEST 129 STRE ET | OVER LAN D P AR K, KAN SAS 66213 U N ITE D ST A TES | 913 664 7 4 00 | spxcooling@spx.com | spxcooling.com In the interest of technological progress, all products are subject to design and/or material c hange without notice. ©2009 S PX Cooling T echnologies, Inc.
デバイスSPX Cooling Technologies MARLEY CLASS F400の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
SPX Cooling Technologies MARLEY CLASS F400をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSPX Cooling Technologies MARLEY CLASS F400の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。SPX Cooling Technologies MARLEY CLASS F400の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。SPX Cooling Technologies MARLEY CLASS F400で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
SPX Cooling Technologies MARLEY CLASS F400を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSPX Cooling Technologies MARLEY CLASS F400の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、SPX Cooling Technologies MARLEY CLASS F400に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSPX Cooling Technologies MARLEY CLASS F400デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。