SuperiorメーカーDT-400CMPの使用説明書/サービス説明書
ページ先へ移動 of 28
1 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. INST ALLA TION INSTRUCTIONS VENTED GAS FIREPLACE HEATERS - DIRECT VENT MODELS P/N 700,020M REV. M 11/2004 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors or liquids in the vicin- ity of this or any other appliance.
2 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 1 Installation must conform to local codes. In the absence of local codes, installation must com- ply with the current National Fuel Gas Code, ANSI Z223.1. (In Canada, the current CAN-1 B149 installation code.
3 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. h t i w s l e d o M t l o v i l l i M e v l a V s a G d e t a l u d o M - y l l a u n a M s a G e n a p o r P d n a l a r u t a N s r e b m u N l e d o M) H / U T B ( e t a r t u p n I 0 0 4 - T D 0 0 4 - R D 0 0 5 , 7 1 o t 0 0 5 , 3 1 .
4 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 2 Figure 3 APPLIANCE AND VENT CLEARANCES The appliance is approved with zero clearance to combustible materials on all sides (as de- tailed in.
5 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. h c t i P f o o R H ) t e e f ( 2 1 / 6 o t t a l F0 . 1 2 1 / 7 o t 2 1 / 6 r e v O5 2 . 1 2 1 / 8 o t 2 1 / 7 r e v O5 . 1 2 1 / 9 o t 2 1 / 8 r e v O0 . 2 2 1 / 0 1 o t 2 1 / 9 r e v O5 . 2 2 1 / 1 1 o t 2 1 / 0 1 r e v O5 2 .
6 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 8 EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS * n o i t a l l a t s n I n a i d a n a C* * n o i t a l l a t s n I S U , h c r o p , a d n a r e v , e d a r g e v o b a e c n a r a e l C = A .
7 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. *34 ⁵⁄₁₆ (872) Back wall of chase/enclosure (including any finishing materials) a 8 ³⁄₁₆ (208) b Note- Venting requirements for rear vent applications in corner installations - - the round termination (SV4.
8 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 21 ¹⁄₂ (546) 13 (330) ¹⁄₂ (13) 1 ⁵⁄₈ (42) 8 ¹¹⁄₃₂ (212) 3 (76) T op View NOTE - Eyebrow hood shown as positioned in louvered front model.
9 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. T R A H C H T G N E L N O I T C E S T N E V l a n i m o N h t g n e L n o i t c e S ) s e h c n i ( 62 14 26 38 4 T O T A L Q T Y n o i t c e S t e N.
10 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 10 ¹⁄₂ ” Min. (267 mm) 10 ¹⁄₂ ” Min. (267 mm) First Vent Component Align the dimple (four places) with the opening of the locking incline channel on appliance collar . T wist vent component clockwise to engage and seal.
11 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Framing Dimensions for Roof Pitch C D 0/12 10 ¹⁄₂ in. 10 ¹⁄₂ in. (267 mm) (267 mm) 6/12 10 ¹⁄₂ in. 12 in. (267 mm) (305 mm) 12/12 10 ¹⁄₂ in. 17 ³⁄₄ in. (267 mm) (451 mm) SV4.
12 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 24 - Rear Vent - ONE 90 DEGREE ELBOW Figure 23 - Top Vent - STRAIGHT Figure 25 - Top Vent - TWO 90 DEGREE ELBOWS VERTICAL VENT FIGURES/TABLES Note: Secure Vent (rigid vent pipe) is shown in the figures; Secure Flex (flexible vent pipe) may also be used.
13 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 26 - Rear Vent - THREE ELBOWS Figure 27 - Top Vent - THREE ELBOWS VERTICAL VENT FIGURES/TABLES (continued) E E L B A T VM M U M I N I HH + 1 m u m i x a M t e e f) m (t e e f) m ( 1) 5 0 3 . 0 (5 ) 2 5 .
14 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Vertical Rise SV4.5E90 Elbow Horizontal / Inclined Run SV4.5HTSSL T ermination Shown *Ceiling Firestop/Spacer (SV4.5BF) SV4.5L6/12/24/36/48 Vent Sections Support Bracket Spacing Every 5 ft (1.52 m) See Figure 17 on page 10 for vertical vent section support.
15 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. *Firestop/Spacer (SV4.5HF) shown on the exterior side of the wall. It may also be installed on the interior side.
16 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. SFHRK Snorkel Cap – The snorkel cap is de- signed to be fitted into a basement window box. The SFHRK cap is for use with flex vent The vertical distance between the inlet and outlet of the cap is 28 in.
17 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 37 - Top Vent - ONE 90 DEGREE ELBOW - ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE Figure 38 - Rear Vent - TWO 90 DEGREE ELBOWS Figure 36 - Top.
18 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Refer to Table 3 on page 16 for an aid in venting component selection for a particular range of exterior wall thicknesses when using the square (SV4.5HTS), small square (SV4.5HTSS) or the round (SV4.
19 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. D. Install Firestop/Spacers at ceilings and walls - When Secure Flex penetrates a wall or ceiling, a firestop/spacer is required: use the SF4.5 BF firestop/spacer for ceilings and the SF4.5 HF firestop/spacer for walls.
20 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 1. If any of the original wire as supplied must be replaced, 1. it must be replaced with T ype AWM 105 ° C – 18 GA.
21 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. FBK-250 Blower Kit (See Figure 46 ) An electrical outlet box is provided for the instal- lation of the FBK-250 forced air blower kit. Electrical power must be provided to this box to operate these blowers.
22 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 52 Electronic Appliance Checkout To light the burner, turn ‘ ON ’ the optional remote wall switch and turn the gas control switch to the “ ON ” position. Ensure the ignitor lights the pilot.
23 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Adjustment Rod Up (Fully Open Position) Air Shutter Burner T ube Adjusting Set Screw Adjustment Rod Down (minimum air opening position) Combustible .
24 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. * All compressed flex vents can be expanded up to two times. d e t s i L x e l F e r u c e S s t n e n o p m o C ™ .
25 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. * All compressed flex vents can be expanded up to two times. INSTALLATION ACCESSORIES (Continued) d e t s i L x e l F e r u c e S s t n e n o p m o C ™ . t a C . o N . o N l e d o Mn o i t p i r c s e D .
26 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. SIT Millivolt Gas Valve Pressure Regulator Remove These Components Figure 59 Step 4. Millivolt Appliances - SIT Systems a. See Figure 59 and the instructions provided with the kit. Using a Torx T20, remove and discard the three pressure regulator mounting screws.
27 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Pilot for SIT Millivolt Gas Valve Orifice Strip T ab Pilot Hood Position After Loosening Hex Fitting 1/4 T urn Push T ab to Set Gas T ype Usage Note - Orifice Strip T ab May Be Randomly Located On Any Side Of The Hex Fitting Hood Alignment Hood 7/16 in.
28 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Step 8. Reassemble all removed components by reversing the procedures outlined in the preceding steps.
デバイスSuperior DT-400CMPの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Superior DT-400CMPをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSuperior DT-400CMPの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Superior DT-400CMPの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Superior DT-400CMPで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Superior DT-400CMPを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSuperior DT-400CMPの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Superior DT-400CMPに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSuperior DT-400CMPデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。