D500-08-00 1 I56-5 12-0 7R DH500 Intelligent Air Duct Smoke Detector Housing INST ALLA TION AND MAINTENANCE INSTRUCTIONS 3825 Ohio A venue , St. Charles, Illinois 60 174 1-800-SENSOR2, F AX: 63 0-377-6495 www .
D500-08-00 2 I56-5 12-0 7R NO TE: The inlet sampling tube must be or dered sepa- rately . It must be the corr ect length for the width of the duct where it will be installed. See T able 1 to determine the inlet tube r equired for differ ent duct widths.
D500-08-00 3 I56-5 12-0 7R T able 1. Sampling (Inlet) Tubes T ube Outside Duct Width ST -1.5 1 to 2 ft. (0.3 to 0.6 m) ST -3 2 to 4 ft. (0.6 to 1.2 m) ST -5 4 to 8 ft.
D500-08-00 4 I56-5 12-0 7R W A RN ING In no case should mor e than 2 air inlet holes be cut off the tube . There must be a minimum of 1 0 holes in the tube exposed to the air stream. B. Installation for Ducts Mor e Than 8 Feet W ide NO TE: T o install inlet tubes in ducts more than 8 feet wide , work must be performed inside the air duct.
D500-08-00 5 I56-5 12-0 7R NO TE: This pr ocedure should only be used in an emergen- cy , and it is not intended as a permanent substitute for or dering the correct length tubes. Step 5. Field Wiring Wiring Installation Guidelines All wiring must be installed in compliance with the Canadian Electrical Code and the local codes having juris- diction.
D500-08-00 6 I56-5 12-0 7R (+) (-) RA400 REMOTE ALARM LED OPTION 1 PER UNIT 8mA CURRENT DRAW RA400Z (+) RA400Z or (-) RTS451/ RTS451KEY EXTERNAL (-) POWER (+) SUPPLY * RTS451/RTS451KEY REMOTE TEST STA.
TWIST COUNTERCLOCKWISE TO REMOVE DUCT HOUSING TWIST CLOCKWISE TO INST ALL DETECTOR HEAD MOLDED RIB TEST MAGNET P AINTED SIDE TO WARD HOUSING DUCT DETECTOR HOUSING DETECTOR HEAD 2. T o determine that smok e is capable of entering the sens- ing chamber , a visual ex amination should be conducted to note any obscurations ar ound the sensing chamber .
D500-08-00 8 I56-5 12-0 7R Step 8. Install the Cover Install the cov er using the four scr ew s . Be certain filter s are installed as specified in Step 6. Make sur e that the co ver fits into the base gr oov e and that all gask ets ar e in their pr oper positions.
D500-08-00 9 I56-5 12-0 7R Both T ypes Of Units 16. R einstall the detector housing. 17. R estore pow er to the sy stem. 18. Put detector into alarm using appropriate method described in STEP 7.
D500-08-00 1 0 I56-5 12-0 7R.
D500-08-00 1 1 I56-5 12-0 7R Three-Y ear Limited W arranty Sy stem Sensor warr ants its enclosed smok e detector to be free from defects in materials and w orkmanship under normal use and service for a period of three year s fr om date of manufacture .
D500-08-00 12 I56-5 12-0 7R © 200 3 System Sensor DETECTOR TEST LOG Detector Identification Infor mation Manufacturer and Serial Date Detector Model:______________________ Number: ___________________.
デバイスSystem Sensor Intelligent Air Duct Smoke Detector Housingの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
System Sensor Intelligent Air Duct Smoke Detector Housingをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSystem Sensor Intelligent Air Duct Smoke Detector Housingの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。System Sensor Intelligent Air Duct Smoke Detector Housingの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。System Sensor Intelligent Air Duct Smoke Detector Housingで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
System Sensor Intelligent Air Duct Smoke Detector Housingを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSystem Sensor Intelligent Air Duct Smoke Detector Housingの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、System Sensor Intelligent Air Duct Smoke Detector Housingに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSystem Sensor Intelligent Air Duct Smoke Detector Housingデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。