Toshibaメーカー1700の使用説明書/サービス説明書
ページ先へ移動 of 39
1700 Series Uninterruptible Power Systems 2/2.4 k V A Rackmount UPS c User Manual.
TOSHIBA 2.
TOSHIBA 3 IMP OR TA NT NO TIC E The ins tructio ns conta ined in th is m anual are not int ended t o cover all of the deta ils or variat ions in equi pm ent, nor to pr ovide f or ever y poss ible contingenc y to be met in co nnection with inst allat ion, o peration, or ma intenance.
TOSHIBA 4 TABLE OF CONTENTS SECTI ON PA GE Disclaimer ................................................................................................ 3 Table of Content s................................................................................
TOSHIBA 5 GENERAL SAFETY INSTRUCTIONS War nings in t his m anual appear in t wo diff erent wa ys: 1) Danger warning s - The danger w arning symbol is an ex clamation mar k enclosed i n a trian gle that precedes the larg e bold letter s spel ling the word "DAN GER".
TOSHIBA 6 IMPORT ANT SA FETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This m anual contains im por tant instr uctions for the 1 700 Ser ies T oshiba Rackm ount UPS. T hese instr uctions shou ld be f ollo wed dur ing the ins tal lation and maintenanc e of the UPS and its b atteries .
TOSHIBA 7 INSTRUCTIONS IMPORT ANTES CONCERN A NT L A SÉCURITÉ CONSERVER CES INSTRUCTIONS. Cette not ice contient d es instr uct ions im portant es concer nant la séc urit. ATTENTION Une batter ie peut pr ésenter un ris que de choc électr iqu e, de brû lure par transf ert d’énerg ie.
TOSHIBA 8 Inspection/Inst allation Inspection of the New UPS Equipment Upon rec eipt of the UPS, a c areful ins pec tion fo r shipp ing dam age should be m ade. A fter Unpacking: 1) Chec k the un it for lo ose, br ok en, bent or oth er wise dam aged parts.
TOSHIBA 9 2) T he input po wer sour ce vo ltage and f requenc y mus t be withi n the allo wable r ange as s pec ified in ap pendix A. Voltag es and frequenc ies outs ide of the perm issible to lerance range m a y cause in ternal pro tection dev ices to act ivate.
TOSHIBA 10 Battery Module UPS Connections Standard Module Connections The ill ustration o n the f ollo wing pa ge shows the prop er assem bly of the two m odules t hat m ak e up the standar d unit. If add itiona l batter y modules are bein g ins talled with the stand ard unit see page 19.
TOSHIBA 11 Operating the UPS Display Panel Layout ON LINE (gr een lam p) Lights gre en when the U PS’s i nverter is supplying power to the load. AC INPUT (green lam p) Lights gre en when nor mal AC input pow er is being su pplied to the UPS u nit. W ARNING/FAULT (red lamp) Lights red when t he UPS u nit is experiencin g an abn ormal conditio n.
TOSHIBA 12 Starting on DC Power If no AC power so urce is avail able, or if the AC inp ut po wer is outside of the al lowable r an ge for vo ltage or fr equency, the UP S can be starte d from battery po wer.
TOSHIBA 13 Notes The unit w ill r eturn t o normal o perat ion mode when AC power is restor e d . Battery backup is not availab le. Alarm Sta te Alarm is off. Ala rm will sound for 1 second at 10 second interva ls. Alarm is off. LED State On Line ....
TOSHIBA 14 Notes Parallel operat ion oc curs whe n input power is present, but inadequat e to fully power t he connect ed load. The bat teries are used to s upplem ent the AC input power. The UPS w ill return to nor mal op eration when full i nput power retur ns.
TOSHIBA 15 Battery Backup Time The ex act am ount of bac kup tim e provide d wil l vary de pendin g on the UPS m odel be ing us ed, number of batteri es, cond ition of the batteries an d other factor s. Ho wever, t he char t belo w gives the times that can b e expec ted f rom the s tandard un its with batteries in good cond ition.
TOSHIBA 16 placed on the UP S incr eases the fan sp eed wi ll incr ease. T he temper ature of the envir onm ent the UPS is opera ting i n can a lso cause the fan spee d to inc reas e.
TOSHIBA 17 will autom atical ly exit t he progr amm ing mode an d retur n to bypass operatio n.) W hat f ollows is a ste p b y step guid e to navigati ng in t he progr amm ing mode, f ollo wed b y a detail ed descripti on of each optio n. A. Load Shed.
TOSHIBA 18 A.2 Onc e the opt ion is s et to th e desire d le vel, pres s an d hold the Func tion Contr ol but ton. T his will sa ve the n ew loa d shed lev el setti ng. The U PS will in dica te that t he va lue has been stor ed by bl inking t he LEDs .
TOSHIBA 19 Fixed Frequency Mode The 1700 Series Rackm ount UPS has th e optio n of oper ating i n a fixed f requenc y mode. N orm all y the UPS operat es in the f requenc y auto-detec t m ode.
TOSHIBA 20 Communication Inter face Dry Contacts The rem ote contacts interf ace is a s tandard f eatur e. It i s provide d through s olid st ate rela ys with c ontacts through a DB9 m ale connector locat ed on the b ack of the UPS ( refer to th e Comm unication O ption Us er Manu al for a m ore detai led desc riptio n of this opt ion) .
TOSHIBA 21 Description and Resol ut ion The batteries have l ess than 30% power remai ning. T he warning will contin ue until eith er the batteries becom e comp letely exhausted or AC inp ut power is restored. An output curre nt limi t warnin g is typical ly a s ign of misapplic ation.
TOSHIBA 22 Description and Resol ut ion This warni ng can be c aused b y the same co ndition s list ed f or ambient over heat . Another possible c ause wou ld be a problem with th e batter y modu le, which could prev ent the unit from providin g back up pow er.
TOSHIBA 23 Description and Resol ut ion The input frequency is outside specified l imits. If the unit was online when the warning occurred it wil l tra nsfer to b a tter y ba ckup. After the backup t he output will shutdown. If the unit was in bypass the output will be turned off.
TOSHIBA 24 Description and Resol ut ion Battery pack is not connected or needs replacement as soon as possibl e. After replacing the batter ies th e b atter y time r must be reset (see “The Function Control Button”, page 17).
TOSHIBA 25 Description and Resol ut ion These faults indicate an internal pr oblem w ith the UPS. Contact yo ur Toshiba U PS service repre sentative at 1- 877-867-8773 (outside the U.S. call 713-466- 0277) . Alarm Sta te Ala rm will sound for 1/2- second, a t 1/2- second interva ls.
TOSHIBA 26 Description and Resol ut ion These faults indicate an internal pr oblem w ith the UPS. Contact yo ur Toshiba U PS service repre sentative at 1- 877-867-8773 (outside the U.S. call 713-466- 0277) . Alarm Sta te Ala rm will sound for 1/2- second, a t 1/2- second interva ls.
TOSHIBA 27 Storage of UPS Equipment. General Guidel ines If the UPS equ ipment is t o be stored; th e follow ing guid eline s should be used. Avoid: 1) Storage in sites sub jec t to ex treme change s in tempera t ure o r high humidity.
TOSHIBA 28 Preventiv e and Scheduled Maintenance/Parts Replacement Preventi ve M ainten ance Tos hiba's 1700 S eries of rack mount UPS s ystems have been designed to prov ide years of trouble- free o perat ion re quiring a minim um of preventive m ainten ance.
TOSHIBA 29 Appendi x A: Specification s Model Number UF1A1A020C6RK UF1A1A024C6RK Capacity 2000VA (1.40KW) 2400VA (1.68KW) Input volt age 1 Single phase 120VAC, +20% to -50% Input frequency 30 to 70 Hz Input c apacity 2000VA 2400VA Input Input power factor Approximatel y unity (0.
TOSHIBA 30 A ppendix B: Fan Speed Control The f ans in the 17 00 Ser ies wil l operat e at an y of four diff erent speeds depending on the envir onment a nd s ystem conditions . In th e firs t stage the fans ar e of f. As the l oad an d or the tem peratur e in crease the f ans will subse quentl y go to l ow, m edium or high s peed as requ ired.
TOSHIBA 31 Appendix C: Syste m Overlo ad Rating The 1700 Series Rackm ount UPS is capa ble of suppo rting sh ort dur ation overloa ds. W hen oper ating in the On Line m ode o utput ov erload ing of 125% of the r ated o utput c urrent c an be su pported f or 1 m inute, and 150% for 30 seconds .
TOSHIBA 32 Appendix D: Parallel Operation The 1700 Series Rackm ount UPS off ers a s tandard featur e that allows the unit to operate with ver y low input vol tag e witho ut de- rati ng the output po wer. If th e inpu t voltage drops b elow a cer tain po int the unit will switch to parall el m ode.
TOSHIBA 33 A ppendix E: Bypass Undervoltage / Overvoltage W hen the 1700 Ser ies Rac km ount UPS is in b ypass m ode the undervo ltage a nd over volta ge lim its are r estricted t o +/ -10% of the rated input vol tage. If the in put v oltage is outs ide of this vol tage windo w the UPS output will be turned off .
TOSHIBA 34 A ppendix G: Weights and Dimensions Module Modu le W eight Shipping W eight Model No. Pounds Ki logram s Pounds Kilogram s UF1A1A0 20C6RK UF1A1A0 24C6RK U F 1 - B R - 0 8 7.
TOSHIBA 35 TOSHIBA INTERNATIONAL CORPORATION LIMITED WARRANTY POLICY (48 contiguous U.S. States, Canada, Mexico) (UNINTERRUPTIBL E POWER SUPPLIES -UP S) TOSHIBA INTERNATIONAL CORPORATION (“TIC”) w.
TOSHIBA 36 PROCEDURE User must contact TIC via e-mail ups s ervice@tic.t oshiba.com , or phone 1-877-867-8773 (outside the U.S. call 713-466-0277), no later than 90 days after User’s discovery of occurrenc e or defect in UPS, UPS part, and/or BATTERY but in no event after the expiration of the respective warranty period .
TOSHIBA 37 Notes:.
TOSHIBA 38 Notes:.
T OSHIBA INTERN A TIONAL CORPORA TION INDUSTRIAL DIVISION 1 3 1 3 1 W est Little Y or k Road, Houst on, T e xas 77041 T el 7 1 3/466-0277 Fax 7 1 3/466-8 7 73 US 800/23 1-1 41 2 Canada 800/872-2 1 92 www .
デバイスToshiba 1700の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Toshiba 1700をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはToshiba 1700の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Toshiba 1700の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Toshiba 1700で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Toshiba 1700を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はToshiba 1700の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Toshiba 1700に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちToshiba 1700デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。