RWB 6104 BAFG R02 Page 1 Beckett Beckett AF/AFG Oil Burner Manual T ype ‘M’ Air T ube Combination (AFG Models only) T ype ‘L1’ Head T ype ‘V1’ Head Potential for Fire, Smoke and Asphyxiati.
Page 2 RWB 6104 BAFG R02 T able of Contents Hazard De fi nitions and Owner ’ s Information ........................................................................................ 3 Information T o Be Used Only By Quali fi ed Service T echnicians General Information .
RWB 6104 BAFG R02 Page 3 T o the Owner: Thank you for purchasing a Beckett burner for use with your heating appliance. Please pay at- tention to the Safety W arnings contained within this instruction manual.
Page 4 RWB 6104 BAFG R02 T able 1 – Burner Speci fi cations Capacity ( Note 1 ) ‘F’ Head (AF & AFG) Firing rate range: .............. 0.40 – 3.00 GPH Input: ....................... 56,000 – 420,000 Btu ‘L1’ Head (AFG Only) Firing rate range: .
RWB 6104 BAFG R02 Page 5 SK9475 Notice Special Requirements For recommended installation practice in Canada, refer to the latest version of CSA Standard B139 & B140. Concealed damage — If you discover damage to the burner or controls during unpacking, notify the carrier at once and fi le the appropriate claim.
Page 6 RWB 6104 BAFG R02 T able 4. AFG Reduced Firing Rates (with LFRB) Burner head type Low Firing Rate Baf fl e installed F0 up to 0.65 gph F3 or L1 up to 0.85 gph F4 or F6 up to 0.90 gph V1 up to 1.00 gph Prepar e the Bur ner Low Firing Rate Baf fl e The AFG Low Firing Rate Baf fl e (LFRB) reduces the air fl ow and pressure.
RWB 6104 BAFG R02 Page 7 Attach air tube (if not already installed) If using a fl ange and gasket, slide them onto the air tube. Then attach the air tube to the burner chassis using the four sheet metal screws provided. Refer to Figure 3 for details.
Page 8 RWB 6104 BAFG R02 Check/Adjust ‘Z’ Dimension - ‘F’ heads 1. The important ‘Z’ dimension is the distance from the face of the nozzle to the fl at face of the head (or heat shield, if applicable). This dis- tance for F heads is 1- ⅛ ” (1- ⅜ ” if the air tube has a heat shield).
RWB 6104 BAFG R02 Page 9 Check/Adjust ‘Z’ Dimension - L1 & L2 Heads Check/Adjust ‘Z’ Dimension - V1 Heads V1 Adjusting Plate Setting AFG with V1 Head Burner Firing Rates 0 0.75-1.00 1 1.00-1.50 2 1.50-1.75 3 1.75-2.00 4 2.00-2.25 5 2.25-2.
Page 10 RWB 6104 BAFG R02 The burner may be equipped with a single-stage fuel unit for these installations. Connect the fuel supply to the burner with a single supply line if you want a one-pipe system (making sure the bypass plug is NOT installed in the fuel unit.
RWB 6104 BAFG R02 Page 1 1 Never use T e fl on tape on fuel oil fi ttings. T ape fragments can lodge in fuel line components and fuel unit, damaging the equipment and pre- venting proper operation. Use oil-resistant pipe sealant compounds. y y y Damage to the pump could cause impaired burn- er operation, oil leakage and appliance soot-up.
Page 12 RWB 6104 BAFG R02 7. RECYCLE. If the fl ame is lost while the burner is fi ring, the control shuts down the burner , enters a 60 second recycle delay , and then repeats the above ignition sequence. If fl ame is lost three times in a row , the control locks out to prevent cycling with repetitious fl ame loss due to poor combustion.
RWB 6104 BAFG R02 Page 13 Star t up bur ner/set combustion For R7184 primary controls, see T echnician’s Quick Reference Guide, part number 61351 for special pump priming sequence. Prepare for combustion tests by drilling a ¼” sam- pling hole in the fl ue pipe between the appliance and the barometric draft regulator .
Page 14 RWB 6104 BAFG R02 P erfor m re gular maintenance Check all wiring for secure connections or insula- tion breaks. Check the pump pressure and cutoff function. Check primary control safety lockout timing. Check ignition system for proper operation.
RWB 6104 BAFG R02 Page 15 For best performance specify genuine Beckett replacement parts Professional Maintenance SK9462 # Part No. Description 1 Burner Housing Assembly 2 Specify Air Band - Specify #.
Page 16 RWB 6104 BAFG R02 Limited WARRANTY For Residential, Commercial and Specialty Burners The R. W. BECKETT CORPORATION (“Beckett”) warrants to persons who purchase its Beckett burners from Bec.
デバイスBeckett AFGの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Beckett AFGをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBeckett AFGの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Beckett AFGの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Beckett AFGで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Beckett AFGを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBeckett AFGの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Beckett AFGに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBeckett AFGデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。