4200 FA XT1 September 6, 2004 1 TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200 FA 50 kVA XT – Transformer / External Battery 208v Input / 208/1.
4200 FA XT1 September 6, 2004 2 (50 kVA XT) 1.0 SCOPE 1.1 System This specification describes a conti nuous duty, three-phase, on-line, solid- state uninterruptible power supply system, hereafter referred to as the UPS.
4200 FA XT1 September 6, 2004 3 H. Input / Output EMI / RFI Filters 2.3 System Operation The UPS shall operate as an on-line, fully automatic system in the following modes: A. NORMAL - Incoming AC power is boosted using a chopper circuit, and converted into DC power.
4200 FA XT1 September 6, 2004 4 protection against spikes, common/normal mode noise, load steps and frequency shifts (without battery back-up capability).
4200 FA XT1 September 6, 2004 5 +/- 3% (loss or return of input power) +/- 8% (bypass to inverter) 13) Transient Voltage Recovery 50ms maximum to within 2% of nominal 14) Overload Cap. (on inverter) 125% for 90 sec., 150% for 30 sec. 15) Overload Cap.
4200 FA XT1 September 6, 2004 6 4.0 FUNCTIONAL DESCRIPTION A. Converter / Charger / DC Chopper DESCRIPTION - The converter/charger s hall consist of a solid-state three phase rectifier, DC to DC converter (chopper), output filter, and transient suppresser network to regulate and maintain DC power to the inverter.
4200 FA XT1 September 6, 2004 7 2) INPUT ISOLATION TRANSFORMER - The inverter network shall incorporate a shielded isolation transfo rmer to provide complete isolation of the load from utility AC, as well as providing attenuation for high frequency noise common mode).
4200 FA XT1 September 6, 2004 8 See “System Diagnostics” for specific fault. 3) SYSTEM METERING - The UPS s hall be provided with a single read- out display which displays, upon request, the follo.
4200 FA XT1 September 6, 2004 9 B. Matching Battery Enclosure The battery cabinet shall consist of a freestanding, matching NEMA1 enclosure equipped with casters and leve ling feet. The maximum overall dimensions and weights shall be as follows: UPS Size Dimensions Weight Runtimes 50 kVA 30”L x 32”W x 59.
4200 FA XT1 September 6, 2004 10 D. Battery Test Function The UPS shall be provided with a “Battery Test” pushbutton to periodically check the condition of the batteries. Upon detection of a battery problem, the UPS shall notify the us er of this condition allowing the user to perform a detailed check of the battery string.
デバイスToshiba 4200FA XT1の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Toshiba 4200FA XT1をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはToshiba 4200FA XT1の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Toshiba 4200FA XT1の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Toshiba 4200FA XT1で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Toshiba 4200FA XT1を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はToshiba 4200FA XT1の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Toshiba 4200FA XT1に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちToshiba 4200FA XT1デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。