E6581364 ② T OSVER T VF-AS1/PS1 Commercial Power Supply Backup and Commercial Power Supply/Inverter Switching Instruction Manual T echnical information described in this document is used to e xplain.
E6581364 1 - Contents - 1. Commercial Power Supply Ba ckup ..................................................................................... 2 1.1. S t andard connection diagram......................................................................
E6581364 2 1. Commercial Power Supply Backup When the inverter ’s protective function is activated, switching power to commercial power supply makes the motor run immediately . 1.1. S t andard connection diagram *1: The control power supply backup option (Mod el: CPS002Z) is needed.
E6581364 3 1.1.1. Switching circuit connection diagram, T i me chart, Parameter settings T itle Function Adjustment range Setting value Output signal selection of commercia l power/inverter switching 0 to 3 1 (Automatic switching in case of trip) *3 Inverter side switching w ait ing time 0.
E6581364 4 1.2. S t andard connection diagram (S tar-delt a switching st art) This is the circuit to switch the motor to commercial power supply S tar Delt a (star-delta) connection startup when the inverter ’ s protective function is activated.
E6581364 5 1.2.1. Switching circuit connection diagram, T i me chart, Parameter settings ON Setting frequency S p eed detection time Inverte r trip occurs Frequency after speed is detected P24-OUT1(RY.
E6581364 6 Ti tl e Function Adjustment range Setting value Output signal selection of com mercial power/inverter switching 0 to 3 1 (Automatic switchi ng when tripped) *3 Inverter side switching w ait ing time 0.1 to 10.
E6581364 7 2. Commercial Power Supply/Inverter Switching The motor runs on commercial power supply under rated operating conditions and when the motor runs in energy saving mode with its input power frequency lowered, this circuit switches the motor to the inverter power without stopping the motor .
E6581364 8 2.1.1. Switching circuit connection diagram, T i me chart, Parameter settings T itle Function Adjustment range Setting value Output signal selection of com mercial power/inv.
E6581364 9 2.2. Precautions 1. Make sure to interlock the magne tic cont actor (MC3) on the inverter output side with th e commercial power supply magnetic contactor (MC1). 2. Magnetic contactor (MC2) can be omitted for normal operation but this is needed to isolate the inverter circuit in case a short-circuit fault occurs inside the inverter .
デバイスToshiba VF-AS1の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Toshiba VF-AS1をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはToshiba VF-AS1の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Toshiba VF-AS1の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Toshiba VF-AS1で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Toshiba VF-AS1を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はToshiba VF-AS1の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Toshiba VF-AS1に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちToshiba VF-AS1デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。