TraneメーカーCVHE-SVU01E-ENX39640712050の使用説明書/サービス説明書
ページ先へ移動 of 112
CVHE-SVU01E-EN X39640712050 Operation Maintenance W ater Cooled CenT raV ac ™ With CH530.
© 2005 American Standard All rights reserved CVHE-SVU01E-EN Warnings and Cautions Warnings and Cautions Notice that warnings and cautions appear at appropriate intervals throughout this manual.
3 Contents CVHE-SVU01E-EN Warnings and Cautions General Information Unit Control Panel (UCP) Operator Interface Chilled Water Setpoint Inter Processor Communication (IPC) Control System Components Con.
CVHE-SVU01E-EN 4 T ypical Product Description Block MODL CVHE DSEQ 2R NTON 320 VOL T 575 REF 123 HRTZ 60 TYPE SNGL CPKW 142 CPIM 222 TEST AIR EVTM IECU EVTH 28 EVSZ 032S EVBS 280 EVWC STD EVWP 2 EVWT .
5 CVHE-SVU01E-EN An example of a typical model number is: CVHF091NAL00ACU2758W7E8TB C0000000K01G14C10W1A03B1 Model Number Digit Identification C = (1 st digit) CenT raV ac ® Hermetic V = (2 nd digit).
CVHE-SVU01E-EN 6 General Information Commonly Used Acronyms For convenience, a number of acronyms are used throughout this manual. These acronyms are listed alphabetically below , along with the “tr.
7 CVHE-SVU01E-EN General Information Figure 1. General CVHE and CVHG unit components Overview CVHE, CVHG, CVHF Each CVHE, CVHG, or CVHF unit is composed of 5 basic components.
CVHE-SVU01E-EN 8 General Information Figure 1. General CVHE and CVHG unit components - continued.
9 CVHE-SVU01E-EN General Information Figure 2. Illustrates the general component layout of a typical CVHF chiller.
CVHE-SVU01E-EN 10 General Information Cooling Cycle CVHE, CVHG, CVHF When in the cooling mode, liquid refrigerant is distributed along the length of the evaporator and sprayed through small holes in a distributor (i.e., running the entire length of the shell) to uniformly coat each evaporator tube.
11 CVHE-SVU01E-EN Figure 3. CVHE, CVHG pressure enthalpy curve Figure 4. CVHE, CVHG 2-stage economizer General Information.
CVHE-SVU01E-EN 12 Figure 5. CVHF pressure enthalpy curve Figure 6. CVHF single stage economizer General Information.
13 CVHE-SVU01E-EN Overview Controls Operator Interface Information is tailored to operators, service technicians and owners When operating a chiller , there is specific information you need on a day-to-day basis — setpoints, limits, diagnostic information, and reports.
CVHE-SVU01E-EN 14 General Information Figure 8. CVHE, CVHF , and CVHG sequence of operation: power up to starting Figure 9. CVHE, CVHF , and CVHG sequence of operation: running.
15 CVHE-SVU01E-EN General Information Figure 11. CVHE, CVHF and CVHG sequence of operation: normal shutdown to stopped and run inhibit Figure 10. CVHE, CVHF , and CVHG sequence of operation: satisfied.
CVHE-SVU01E-EN 16 General Information Oil and Refrigeration Pump Compressor Lubrication System - A schematic diagram of the compressor lubrication system is illustrated in Figure 12.
17 CVHE-SVU01E-EN General Information Figure 12. Oil refrigerant pump.
CVHE-SVU01E-EN 18 General Information Base Loading Control Algorithm: This feature allows an external controller to directly modulate the capacity of the chiller . It is typically used in applications where virtually infinite sources of evaporator load and condenser capacity are available and it is desirable to control the loading of the chiller .
19 CVHE-SVU01E-EN General Information Figure 13. Base loading with external mA input and with external voltage input.
CVHE-SVU01E-EN 20 General Information Ice Machine Control The control panel provides a service level “Enable or Disable” menu entry for the Ice Building feature when the Ice Building option is installed.
21 CVHE-SVU01E-EN General Information Free Cooling Cycle Based on the principle that refrigerant migrates to the coldest area in the system, the free cooling option adapts the basic chiller to function as a simple heat exchanger . However , it does not provide control of the leaving chilled water temperature.
CVHE-SVU01E-EN 22 General Information it is then compressed and discharged to the condenser . Most of the condensed refrigerant initially follows the path of least resistance by flowing into the storage tank.
23 CVHE-SVU01E-EN General Information Hot Gas Bypass The hot gas bypass (HGBP) control option is designed to minimize machine cycling by allowing the chiller to operate stably under minimum load conditions.
CVHE-SVU01E-EN 24 General Information Hot Water control Occasionally CTV chillers are selected to provide heating as a primary mission. With hot water temperature control, the chiller can be used as a heating source or cooling source. This feature provides greater application flexibility .
25 CVHE-SVU01E-EN General Information Heat Recovery Cycle ‘‘Heat recovery’’ is designed to salvage the heat that is normally rejected to the atmosphere through the cooling tower , and put it to beneficial use. For example, a high- rise office building may require simultaneous heating and cooling during the winter months.
CVHE-SVU01E-EN 26 Unit Control Panel (UCP) Control Panel Devices and Unit Mounted Devices Unit Control Panel (UCP) Safety and operating controls are housed in the unit control panel, the starter panel and the purge control panel. The UCP ‘s operator interface and main processor is called the DynaView ™ (DV) and is located on the UCP door .
27 CVHE-SVU01E-EN Unit Control Panel (UCP) T racer CH530 Chiller Controller Revolutionary control of the chiller , chilled water system, and your entire building with unprecedented accuracy , reliability , efficiency , and support for maintenance using the chiller’ s PC-based service tool.
CVHE-SVU01E-EN 28 Operator Interface Figure 17. DynaView ™ main processor The DynaView ™ (DV) Operator Interface contains the “Main Processor (MP)” and is mounted on the unit control panel fro.
29 CVHE-SVU01E-EN Operator Interface DynaView ™ (DV) is the operator interface of the T racer CH530 control system utilized on the CTV machine. The DynaView ™ enclosure is 9.75" wide, 8” high and 1.6” deep. The DynaView ™ display is approximately 4” wide by 3” high.
CVHE-SVU01E-EN 30 Operator Interface The Auto and Stop keys are used to put the unit into the auto or stop modes. Key selection is indicated by being darkened (reverse video). The Alarms button is to the right of the Stop key . The Alarms button appears only when alarm information is present.
31 CVHE-SVU01E-EN Operator Interface The machine-operating mode indicates the operational status of the chiller . A subscreen with additional mode summary information will be provided.
CVHE-SVU01E-EN 32 Operator Interface Reference T op Level Mode Sub Level Mode BAS Code SYSTEM RESET Boot & Application software part number , self-test, and configuration validity screens will be present.
33 CVHE-SVU01E-EN Operator Interface Reference T op Level Mode Sub Level Mode BAS Code W aiting T o Start Motor T emperature Inhibit: Motor T emperature / Inhibit T emperature 7 0 W aiting T o Start R.
CVHE-SVU01E-EN 34 Operator Interface Main Screen The main screen is provides “an overall view“ of the chiller performance in addition to the main and sub operating modes. The table below indicates other items found , when specified by options, that can be scrolled to via the up or down arrows.
35 CVHE-SVU01E-EN Operator Interface Diagnostic Screen The diagnostic screen is accessible by touching the Alarms enunciator . When an alarm is present, the alarm enunciator is present next to the Stop key . A flashing “alarm” indicates a machine shutdown and a non flashing “alarm” indicates an informational message.
CVHE-SVU01E-EN 36 Operator Interface The chilled water reset status area in the right most column will display one of the following messages: Return, Constant Return, Outdoor , None The left column te.
37 CVHE-SVU01E-EN Operator Interface The left column text “Front Panel”, “BAS”, “External”, and “Active Current Limit Setpoint” will always be present regardless of installation or enabling those optional items.
CVHE-SVU01E-EN 38 Operator Interface Reports Evaporator Report items Uni ts Evaporator Entering W ater T emperature °C or ° F Evaporator Leaving W ater T emperature °C o r °F Evaporator Saturated .
39 CVHE-SVU01E-EN Operator Interface Compressor Report Items Unit s Compressor Starts: ### Compressor Running T ime: Hour and minute Compressor Discharge T emperature; If installed °C or °F Oil T an.
CVHE-SVU01E-EN 40 ASHRAE Chiller Log Units 1 . Current T ime and Date Monitor HH:MM xm 2 . Operating Mode 3 . Active Chilled Water Setpoint: °C or °F 4 . Active Current Limit Setpoint: % RLA 5 . Refrigerant T ype: 6 . Refrigerant Monitor: If installed PP M 7 .
41 CVHE-SVU01E-EN Operator Interface Setting T ab screens provides a user the ability to adjust settings justified to support daily tasks. The layout provides a list of sub-menus, organized by typical subsystem. Settings screen for standard CTV : Chilled Water Setpoint: T o change chilled water setpoint first select the settings tab screen.
CVHE-SVU01E-EN 42 Operator Interface Chiller Description Un its notes 1 . Front Panel Control T ype (Chilled Water , Hot W ater), Chilled W ater default 2 . Front Panel Chilled Water Setpoint T emperature 1 3 . Front Panel Hot Water Setpoint T emperature 1 4 .
43 CVHE-SVU01E-EN Operator Interface Display Settings Description Un its notes 1. Date Format (“mmm dd, yyy”, “dd-mmm-yyyy”), “mmm dd, yyy” 2. Date 4 3 . T ime Format (12-hour , 24-hour), 12-hour 4 . T ime of Day 4 5 . Keypad and Display Lockout (Enable, Disable), Disable 5 6 .
CVHE-SVU01E-EN 44 Operator Interface Each Settings Sub screen consists of a setpoints list and the current value. The operator selects a setpoint to change by touching either the description or setpoint value. Doing this causes the screen to switch to the Analog Settings Subscreen shown below .
45 CVHE-SVU01E-EN Operator Interface Settings with buttons only [screen has no cancel or enter key] do accept the new selection immediately . Mode Override for Enumerated Settings is shown below: Note: Radio 1 and Radio 2 refer to “touch sensitive buttons.
CVHE-SVU01E-EN 46 Operator Interface The mode override analog setting subscreen is similar but offers an Auto or Manual radio button and value setting. An Auto or Manual selection is necessary set to the mode to override. An Enter and Cancel Key will allow the user to Enter or Cancel the entry .
47 CVHE-SVU01E-EN Operator Interface The time setpoint screen with a 12-hour format is shown below: The user must select Hour , or Minute and then use the up or down arrows to adjust. Adjusting hours will also adjust am and pm. Note: The 24-hour format setpoint screen is similar with the am and pm not shown.
CVHE-SVU01E-EN 48 Operator Interface The DynaView ™ Display T ouch Screen Lock screen is shown below . This screen is used if the Display and T ouch Screen Lock feature is Enabled. 30 minutes after the last key stroke this screen will be displayed and the Display and T ouch Screen will be locked out until “159enter” is entered.
49 CVHE-SVU01E-EN Interprocessor Communication Inter Processor Communications IPC3 When using T racer CH530, you will not be required to know all the details about the structure of the IPC3 bus. However this page gives detailed information about the system for those of you that are really interested in how it works.
CVHE-SVU01E-EN 50 Control System Components Control Panel Internally mounted devices For visual identification Internal Control Panel mounted devices are identified by their respective schematic designation number . Control panel items are marked on the inner back panel in the control panel.
51 CVHE-SVU01E-EN Control System Components.
CVHE-SVU01E-EN 52 Control System Components Control Panel Devices Standard Devices Controls Field Connection Description Package Purpose Point T erminals 1A1 Power Supply Standard # 1 C onverts 24 vac.
53 CVHE-SVU01E-EN Head Relief Request Output When the chiller is running in Condenser Limit Mode or in Surge Mode, the head relief request relay (1 minute default) on the 1A9–J2-6 to J2-4 will be energized and can be used to control or signal for a reduction in the entering condenser water temperature.
CVHE-SVU01E-EN 54 Control System Components EXOP Extended Operation Option The following modules (1A17, 1A18, and 1A19) are provide when this control package is specified.
55 CVHE-SVU01E-EN Control System Components FRCL (Free Cooling Option) 1A11 Optional Quad FRCL Relay #1 Free Cooling Relay 1, J2- 4 NO to J2-6 common Relay Output Status 1A20 Optional Dual L V FRCL Si.
CVHE-SVU01E-EN 56 Control System Components CDRP Refrigerant Pressure Output Option 1A15: Refrigerant Pressure Output can be configured at commissioning to correspond to either A) the absolute condenser pressure, or B) the differential pressure of the evaporator to condenser pressures.
57 CVHE-SVU01E-EN Control System Components B) Refrigerant Differential Pressure Indication Output: A 2 to 10 VDC analog output is provided instead of the previous condenser pressure output signal. This signal corresponds to a predetermined minimum and maximum pressure settings setup at commissioning of this feature.
CVHE-SVU01E-EN 58 Control System Components GBAS (Generic Building Automation System) 1A15 Optional Dual GBAS Signal #1 Percent RLA Compressor Output J2-1 Output #1, J2-3 Ground Analog Input/ o r outp.
59 CVHE-SVU01E-EN Control System Components External Chilled Water Setpoint (ECWS) The External Chilled Water Setpoint allows the chilled water setpoint to be changed from a remote location. The External Chilled Water Setpoint is found on 1A16 J2-5 to J2-6 (Ground).
CVHE-SVU01E-EN 60 Control System Components 1A8, 1A9, 1A11, 1A12 Quad Relay Output Status: Relay #1 J2-1 NO, J2-2 NC, J2- common Relay #2 J2-4 NO, J2-5 NC, J2-6 common Relay #3 J2-7 NO, J2-8 NC, J2-9 common Relay #4 J2-10 NO, J2-11 NC, J2-12 common Relay Outputs: at 120 V AC: 7.
61 CVHE-SVU01E-EN Control System Components 1A15, 1A16, 1A17, 1A21 Dual Analog Input/output Module; Analog Output: The Analog Output is a voltage only signal. 2-10 Vdc at 22mA J2: 14 - 26 A WG with a maximum of two 14 A WG J2-1 Output #1 to J2-3 (Ground), J2-4 Output #2 to J2-6 (Ground).
CVHE-SVU01E-EN 62 Control System Components Unit mounted devices V ane Actuator Control The Stepper Module within the stepper vane actuator (4M2) (and 4M4 extended capacity) pulses a DC voltage to the windings of the Stepper Motor Actuator(s) to control inlet guide vane position.
63 CVHE-SVU01E-EN Electrical Sequence This section will acquaint the operator with the control logic governing CVHE, CVHF and CVHG chillers equipped with T racer CH530 UCP based control systems.
CVHE-SVU01E-EN 64 When less than 2.5 seconds remain before compressor start, a starter test is conducted to verify contactor states prior to starting the compressor . The following test or start sequence is conducted for ‘‘Wye-Delta’’ starters: Also refer to Figure 24.
65 CVHE-SVU01E-EN Now that the compressor motor (4M1) is running in the ‘‘Delta’’ configuration, the inlet guide vanes will modulate, opening and closing to the chiller load variation by operation of the stepper vane motor actuator (4M2) to satisfy chilled water setpoint.
CVHE-SVU01E-EN 66 Interval Minimum Maximum Units Actual Design A. (T est for transition complete input open) 160 to 240 milliseconds B. (Just delay time) 20 milliseconds C. (Close 1M (2K1) Contactor and test for no current.) (Starter integrity test) 500 m illiseconds D.
67 CVHE-SVU01E-EN Current passing through fuse 1F2 reaches 2 normally open parallel sets of contacts: those of refrigerant and oil pump relay (1A7-J2-5 to 1), and the start contactor 2K1-aux. Connecter at module 1A7-J2-2 to 4. Note: While the (1A7-J2-5 to 1) relay automatically is closed by the main processor 1A22 as a part of the start sequence.
CVHE-SVU01E-EN 68 Momentary Power Loss (MPL) Protection. Improved power measurement and protection algorithms allow the unit to accommodate more power anomalies than ever . If the chiller must shut down, faster restarts get the machine up and running as soon as possible.
69 CVHE-SVU01E-EN Current Overload Protection Motor currents are continuously monitored for over current protection and locked rotor protection. This protects the Chiller itself from damage due to current overload during starting and running modes but is allowed to reach full load amps.
CVHE-SVU01E-EN 70 Current Limit Protection Current Limit Protections exist to avoid motor current overload and damage to the compressor motor during starting and running. Compressor motor current is continuously monitored and current is controlled via a limit function that to prevent running into over current diagnostic trips.
71 CVHE-SVU01E-EN Differential to Start or Stop The Differential to Start setpoint is adjustable from 1 to 10°F (0.55 to 5.55°C) and the Differential to Stop setpoint adjustable from 1 to 10°F (0.55 to 5.55°C). Both setpoints are with respect to the Active Chilled Water Setpoint.
CVHE-SVU01E-EN 72 Evaporator Limit Evaporator refrigerant temperature is continuously monitored to provide a limit function that prevents low refrigerant temperature trips which allows the chiller to continue to run at a reduced load instead of tripping off at the Low Evaporator Refrigerant T emperature Cutout Setpoint (LRTC).
73 CVHE-SVU01E-EN Low Refrigerant T emperature Cutout The purpose of the low evaporator refrigerant temperature protection is to prevent water in the evaporator from freezing. When the Low Evaporator Refrigerant T emperature Cutout (LRTC) trip point is violated, a latching diagnostic indicating the condition is displayed.
CVHE-SVU01E-EN 74 Figure 27. Cutout strategy Machine Protection and Adaptive Control Limit Loading: The potential to limit loading increases as the saturated evaporator temperature approaches the evaporator limit setpoint.
75 CVHE-SVU01E-EN Condenser Limit Condenser pressure is continuously monitored to provide a limit function that prevents High Pressure Cutout (HPC) trips.
CVHE-SVU01E-EN 76 Restart Inhibit. This function provides short cycle protection for the motor , and indirectly also short cycling protection for the starter since the starter is designed to operate the motor under all the conditions of motor performance.
77 CVHE-SVU01E-EN High V acuum Lockout The oil sump pressure is below the lockout setpoint. Starting of compressor is inhibited as a result. Low Oil T emperature Star t Inhibit The oil temperature is at or below the low oil temperature start inhibit setpoint (143°F/61.
CVHE-SVU01E-EN 78 Oil T emperature Control The oil heater is used to maintain the oil temperature within +/- 2.5°F (1.4°C) of the oil temperature control setpoint.
79 CVHE-SVU01E-EN Controls Chilled Water Reset (CWR) Chilled water reset is designed for those applications where the design chilled water temperature is not required at partload. In these cases, the leaving chilled water temperature setpoint can be reset upward using the CWR features.
CVHE-SVU01E-EN 80 T able 3. V alues for start reset types The values for “RESET TYPE” are: Reset Outdoor Return Const Return T ype: Disable Air Reset Reset Reset The values for “RESET RA TIO” .
81 CVHE-SVU01E-EN Reset Ratio: The Reset Ratio is displayed as a percentage. T o use it in the above equation it must be converted to it’ s decimal form. Reset Ratio percent /100 = Reset Ratio decimal Example of converting Reset Ratio: If the Reset Ratio displayed on the CLD is 50 percent then use (50/100)= .
CVHE-SVU01E-EN 82 Figure 29. Reset function for return CWR Note: This graph assumes Maximum Reset is set to 20 degrees. Figure 30. Reset function for return CWR Machine Protection and Adaptive Control.
83 CVHE-SVU01E-EN Example of Calculating Return Reset: If: Reset Ratio = 50% Start Reset = 25 TWE = 65 TWL = 45 Maximum Reset = 8 How many Degrees of Reset will there be? Degrees of Reset = Reset Ratio*(Start Reset - (TWE-TWL)) Degrees of Reset = .5*(25-(65-45)) Degrees of Reset = 2.
CVHE-SVU01E-EN 84 Figure 31. Return CWR Figure 32. Constant CWR Machine Protection and Adaptive Control.
85 CVHE-SVU01E-EN Unit Start-Up Procedures Daily Unit Start-Up 1. V erify the chilled water pump and condenser water pump starter are in “ON” or “AUTO”. 2. V erify the cooling tower is in “ON” or “AUTO”. 3. Check the oil tank oil level; the level must be visible in or above the lower sight glass.
CVHE-SVU01E-EN 86 When the cooling requirement is satisfied, the UCP originates a “Shutting down” signal. The inlet guide vanes are driven closed for 50 seconds, and the unit enters a 3- minute post-lube period.
87 CVHE-SVU01E-EN Unit Shutdown Procedures Daily Unit Shutdown Note: Refer to Start-Run Shutdown sequence in General Information Overview Sequence of Operation. 1. Press STOP . 2. After compressor and water pumps shutdown turn Pump Contactors to OFF or open pump disconnects.
CVHE-SVU01E-EN 88 Overview This section describes the basic chiller preventive maintenance procedures, and recommends the intervals at which these procedures should be performed. Use of a periodic maintenance program is important to ensure the best possible performance and efficiency from a CenT raV ac ® chiller .
89 CVHE-SVU01E-EN W ARNING Hazardous V oltage w/ Capacitors! Disconnect all electric power , including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized.
CVHE-SVU01E-EN 90 [ ] Complete all recommended quarterly maintenance procedures. [ ] Lubricate the vane control linkage bearings, ball joints, and pivot points; as needed a few drops of light machine oil (SAE-20) is sufficient. [ ] Lubricate vane operator tang o-rings as described in the maintenance section.
91 CVHE-SVU01E-EN Oil Maintenance Compressor Oil Change on CVHE, CVHF , CVHG Recommendations are to subscribe to an annual oil analysis program rather than automatically change the oil as part of scheduled maintenance. Change the oil only if indicated by the oil analysis.
CVHE-SVU01E-EN 92 Oil Maintenance Replacing Oil Filter Replace oil filter: (1) annually , (2) at each oil change, (3) or if erratic oil pressure is experienced during chiller operation. Oil Filter Replacement Use the following procedure to service the oil filter .
93 CVHE-SVU01E-EN Maintenance Other Maintenance Requirements Compressors using new seal technology will not use O-rings. The O-ring has been replaced by Loctite 515 applied at a minimum film thickness of .010 applied across the width of the flange. The current jack bolt holes remain for disassembly .
CVHE-SVU01E-EN 94 Maintenance Figure 33. Rotary valve in drain position Front View with Refrigerant Pump DO NOT LEA VE GREASE FITTINGS INST ALLED. If grease fittings have been used for this procedure then they MUST BE REMOVED before returning the unit to service.
95 CVHE-SVU01E-EN Maintenance Refrigerant Charge W ARNING Contains Refrigerant! System contains oil and refrigerant and may be under positive pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type.
CVHE-SVU01E-EN 96 Maintenance Recovery and Recycle Connections T o facilitate refrigerant removal and replacement, newer-design CVHE, CVHF and CVHG units are provided with a 3/4-inch vapor fitting with shutoff valve on the chiller suction and with a 3/4-inch liquid connection with shutoff valve at the bottom of the evaporator shell.
97 CVHE-SVU01E-EN Maintenance Condenser tube fouling is indicated when the approach temperature (the difference between the condensing refrigerant temperature and the leaving condenser water temperature) is higher than predicted.
CVHE-SVU01E-EN 98 Maintenance Purge System Because some sections of the chiller’ s refrigeration system operate at less-than-atmospheric pressure, the possibility exists that air and moisture may leak into the system.
99 CVHE-SVU01E-EN Maintenance W ARNING Hazardous V oltage w/ Capacitors! Disconnect all electric power , including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized.
CVHE-SVU01E-EN 100.
101 CVHE-SVU01E-EN.
CVHE-SVU01E-EN 102.
103 CVHE-SVU01E-EN.
CVHE-SVU01E-EN 104.
105 CVHE-SVU01E-EN.
CVHE-SVU01E-EN 106.
107 CVHE-SVU01E-EN.
CVHE-SVU01E-EN 108.
109 CVHE-SVU01E-EN.
CVHE-SVU01E-EN 110.
111 CVHE-SVU01E-EN.
T rane A business of American Standard Companies www.trane.com For more information contact your local district office or e-mail us at comfort@trane.com T rane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
デバイスTrane CVHE-SVU01E-ENX39640712050の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Trane CVHE-SVU01E-ENX39640712050をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはTrane CVHE-SVU01E-ENX39640712050の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Trane CVHE-SVU01E-ENX39640712050の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Trane CVHE-SVU01E-ENX39640712050で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Trane CVHE-SVU01E-ENX39640712050を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はTrane CVHE-SVU01E-ENX39640712050の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Trane CVHE-SVU01E-ENX39640712050に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちTrane CVHE-SVU01E-ENX39640712050デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。