Ins talla ti on/ Op er a t ion Maint enan c e V ar i T r ane ™ Pne umati c Con tr ols V A V -S V X0 2 B-EN March 2002.
V A V -SVX02B-EN Thermost at Selec tion and Location In general, both one- and two-pipe thermost ats have a gain of 2.5 psi per degree F ahrenheit, unless special thermosta ts are used that provide a different g ain.
3 V A V -SVX02B-EN Thermostat Specif icat ions TP970 S eries Pneumatic T -stats Maximum Safe Air Pressure: 25psi (172 kPa) Maximum S afe Air T emperature: 150°F (66°C) Throttling Range: 2–1 0°F (1–5°C) Gain: 2.5 psi/ °F Adjustable Ope ra t ion Pneumatic thermost ats modulate out put air pressure in respons e to room air temperature.
V A V -SVX02B-EN Inst alla tion and Oper a t ion The reversing relay is a proportional, non-bleeding device for use in pneu- matic control systems where a propor - tional signal from a controlling device must be reversed (see Figure 5). The most common use of the reversing relay is to c hange the action of a pneumatic thermostat.
5 V A V -SVX02B-EN Re v er sing Rela y Calibrat ion By using the “bias” adjustment on the relay , t he factory-set 8.0 – 9.0 “cross- over” can be c hanged. T o recalibrate, the relay should be connected as illustrated in F igure 8. F igure 8 – Rec a libra ting Reve rsing Re lay If the new desired “cross-over” pressure is 1 1 .
V A V -SVX02B-EN Model 30 1 1 The model 30 1 1 Pneumatic V olume Regulator (PVR) is capable of operating with normally-open or normally-closed air valves and can operate with either direct-acting (DA) or reverse-acting (RA) thermostats. F igure 9 – Accepta ble Installa tion Positions Ins ta lla tion 1 .
7 V A V -SVX02B-EN Use the following procedure to set-up the PVR: 1 . Select damper action (NO or NC). Loosen damper selection switc h screw and align to either the NO or NC pointer with damper pointer and tighten screw. 2 . Now determine the type of thermostat that will be used.
V A V -SVX02B-EN Calibration P r oced ur es Calibr a ti on P roc e dure (Steps 1– 4 apply to all ther mos t a t m odels) 1 . Be sure the PVR is installed correctly and that all connections are hooked up to the proper ports. See Figure 9 for unit appl ication.
V A V -SVX02B-EN 9 Spe cifica tions (30 1 1) Differential Pressure Range: 0 to 1 .0 in. wg Minimum Set point Range: 0 to 1 .0" H 2 O Maximum Set point Range: minimum to 1 .0 in. w g Operating Static Range: 0.25 – 6.0 in. wg Sp e cif ic ations (30 1 1) Normal Supply Air Pressure: 20.
V A V -SVX02B-EN 10 Model 350 1 The model 350 1 Pneumatic V olume Regulator (PVR) is capable of operating with normally-open or normally-closed air valves and can operate with either direct-acting (DA) or reverse-acting (RA) thermostats. Adjusting the Reset Span (350 1) The reset span is factory-set at 5 psi.
V A V -SVX02B-EN 11 Calibration P r ocedures Calibr ation Pr oce dure (Steps 1– 4 apply to all ther mostat models) 1 . Be sure the PVR is installed correctly and that all connections are hooked up to the proper ports. 2 . Remove the caps on the tees, whic h are connected to the lines to the flow sensor .
V A V -SVX02B-EN 12 Spec if ica t ions (350 1) Differential Pressure Range: 0 to 1 .0 in. wg Minimum Setpoint Range: 0 to 1 .0" H 2 O Maximum Setpoint Range: minimum to 1 .0 in. w g Maximum Setpoint Range: 6.0 in. wg Normal Supply Air Pressure: 20.
V A V -SVX02B-EN 13 MCP -3631—Rotary Pneumatic D amper Ac tuat or Desc ription: Rotary actuators mounts to a standard ½" diameter shaf t by a loc king collar and bushing.
V A V -SVX02B-EN 14 Constant V ol ume Dual-Duct Calibration (30 1 1) This calibration procedure is used when a constant volume of air must be maintained through a unit. On a dual- duct unit, a constant-volume disc harge sensor is used to measure the air leaving the unit.
V A V -SVX02B-EN 15 Thermostat Range: 3 – 8 psi Heating V alve = 5 psi range Thermostat Range: 8 –13 psi Cooling V alve = 5 psi range Approximately 1 0 0 0 cfm di vided by 5 psi = 200 cfm/1b* *Due.
T rane An American Standard Company www.trane.com For more information contact your local district office or e-mail us at comfort@trane.com Liter ature Order Number V AV - S V X02B - EN Fil e Number S.
デバイスTrane VAV-SVX02B-ENの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Trane VAV-SVX02B-ENをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはTrane VAV-SVX02B-ENの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Trane VAV-SVX02B-ENの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Trane VAV-SVX02B-ENで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Trane VAV-SVX02B-ENを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はTrane VAV-SVX02B-ENの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Trane VAV-SVX02B-ENに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちTrane VAV-SVX02B-ENデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。