1. Important Safety W arnings 2 2. Control P anels 3 2.1 Front P anel 3 2.2 Battery Access Panel (Co ver Removed) 4 2.3 Rear Panel 5 3. Installation 6 3.1 UPS Location 6 3.2 Mounting Bracket Installation 6 3.3 Grounding Connection 6 3.4 UPS Input And Output Hard wire Connection 6 3.
2 SA VE THESE INSTR UCTIONS. This manual contains important instructions and warnings that should be follo wed during the installation and maintenance of all T ripp Lite SmartOnline 3-Phase 20kV A and 30kV A UPS Systems. UPS Location Warnings • Installyour UPS in acontrolled en vironment.
2. Control P anels 3 Note: F amiliarize yourself with the location and function of the features on your UPS system befor e installing and operating it. “ON” Button: 1. This buttonturns theUPS System's in verter ON. “OFF” Button: 2.
4 1 2 3 4 5 6 7 Individual models may vary slightly from diagram. 2.2 Battery Access P anel (Cover Removed) 2. Control P anels ( continued ) Internal Battery Packs: 1. Thesesupply backup runtime toconnected equipment. Eachpack consists oftwo strings (onepositiveand onenegativ e).
Individual models may vary slightly from diagram. 5 Manual Bypass Switch: 1. This dialis used toput the UPS in“BYP ASS” mode, whichmust be donebefore performing anymaintenance on theUPS withthe connected load supported.
6 Mov e your UPS over short distances using its wheels. Note: The wheels ar e not designed to pro vide long-term support for the UPS system after f inal installation.
7 WIRING CONNECTION Connectyour wiring to theinput and outputterminal blocks locatedon the rear panelof your UPS(see figurebelow). CA UTION! Qualified personnel should follo w all procedures prescribed by N.
8 Momentarilypress the “SELECT” buttononthe front panelto browsethrough differentpowerreadings onthe LCD Display . BYP ASS OUTPUT R: XXXV R: XXX.XV S: XXXV S: XXX.XV T: XXXV T: XXX.XV (Bypass&Output Vo ltage) OUTPUT LO AD R: XXX% XXX.
9 Condition LCD Display Message Overload Shutdown ONBYP ASS O VERLO AD 150% SHUTDO WN... VERSION: XXXXXXX UPS Output Short Circuit ONBYP ASS SHOR T CIRCUIT! SHUTDO WN... VERSION: XXXXXXX Overtemperature ONBYP ASS HIGHTEMP! SHUTDO WN... VERSION: XXXXXXX DCBUS Overv oltage ON BYP ASS DCBUS O.
3 V + - 10 Thisfemale DB9 port connectsyour UPS viaan RS-232 cableto a workstationor serverequipped withTrippLite software.Theport uses RS-232 communicationsto report UPS statusand powerconditions.
X 1 2 3 4 5 6 X 11 Thisoptional feature is onlyfor those applicationswhich require connectionto a facility'sEmergencyPowerOff(EPO) circuit.Whenthe UPS System isconnected to this circuit,it enables emergenc y shutdownof theoutput.
UPS System Batter y Back Co nnec to r White wir e Blue wire UPS System Batter y Back Co nnec to r Fu se Block Bracket Red wire (+ ) Black wire (–) 12 Qualifiedservice personnelshould familiarizethemselves withthe battery packwiring diagram prior toadding or replacingbatteries.
13 Placethe UPS System inBypass Mode orcompletely turn itoff, dependingon preference. (See section5.4, Operation of Manual Bypass Switch , or4.2, T urning the UPS Off .) 1 Remov e battery accesspanel, located on theFRONTof theUPS system.
14 Slide the battery string with the RED cable into an empty slot within the battery compartment as sho wn. Make sure that the string is oriented as shown in the diagram 7A . Note: If the auxiliary battery connector is in the way , remove its mounting screw and position the cable to allow adequate room to add the battery strings 7B .
240 15 D ANGER! B A TTER Y CARTRIDGE FUSES MUST BE INSERTED LAST DUE TO THE DANGER OF PO TENTIAL ARCING OF CONNECTORS. FUSE REPLA CEMENT The fuses protect against shor t circuit damage . If a heavy overload or shor t cir cuit is encountered, a fuse will blow .
16 Y our SmartOnline 3-Phase UPSSystem is cov ered by thelimited warranty describedbelow . Extended warranty(2-, 3- and4-year) and start-upservice programsare av ailable. Formore information, callTrippLiteCustomer Service at(773) 869-1234.
17 Model: SU20K3/3 Input Input Voltage 120/208V AC, 3ø, 4 Wire (plus ground), wye Input Frequency 60 Hz ± 3 Hz V oltage Correction Range 88-144/166-250V AC Input Cur rent (Per Phase, On-Line) 60A Inr ush Cur rent <300A Power Factor (Full Load) >0.
200901138 93-2624 18 Model: SU30K3/3 Input Input Voltage 120/208V AC, 3ø, 4 Wire (plus ground), wye Input Frequency 60 Hz ± 3 Hz V oltage Correction Range 88-144/166-250V AC Input Cur rent (Per Phase, On-Line) 90A Inr ush Cur rent <300A Power Factor (Full Load) >0.
デバイスTripp Lite 120/208Vの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Tripp Lite 120/208Vをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはTripp Lite 120/208Vの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Tripp Lite 120/208Vの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Tripp Lite 120/208Vで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Tripp Lite 120/208Vを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はTripp Lite 120/208Vの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Tripp Lite 120/208Vに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちTripp Lite 120/208Vデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。