P art Number 550-141-807/0298 LGB Gas–fir ed boiler Contents Flame Guardian WMBC -1A RM7895C Controller Electronic Pilot System IRI Control Supplement I . Installation ..................... 2 II . Gas piping ...................... 5 III. Wiring ....
P art Number 550-141-807/0298 2 LGB (Series 2) — Control Supplement I Installation 1 . For use with LGB-6 through 12 boilers. 2 . L O CAL INSPECT OR MUST CER TIFY B OILER FOR IRI COMPLIANCE. 3 . Assemble pilot burner and flame sensor to main burners with pilot brackets.
P art Number 550-141-807/0298 3 Flame Guardian WMBC-1A Electronic Pilot System – IRI Figure 2 Q179 pilot burner assembly Figure 3 Main flame sensor assembly I Installation – continued LGB-A56 Loca.
P art Number 550-141-807/0298 4 LGB (Series 2) — Control Supplement 16 13 15 17 18 18 14 12 11 10 9 7 6 5 4 3 2 1 Boiler Jacket V ent to Outside Atmosphere Drip Leg Service V alve 9 Second motorized.
P art Number 550-141-807/0298 5 Flame Guardian WMBC-1A Electronic Pilot System – IRI 1 . Size gas piping considering: a. Diameter and length of gas supply piping. b. Number of fittings. c . Maximum gas consumption (including any possible future expansion).
P art Number 550-141-807/0298 6 LGB (Series 2) — Control Supplement P art Number 550-141-807/0298 7 Flame Guardian WMBC-1A Electronic Pilot System – IRI Figure 5 — WMBC-1A panel wiring schematic.
P art Number 550-141-807/0298 8 LGB (Series 2) — Control Supplement Figure 6 — WMBC-1A panel wiring diagram – factory wiring.
P art Number 550-141-807/0298 9 Flame Guardian WMBC-1A Electronic Pilot System – IRI Figure 7 — WMBC-1A field wiring diagram.
P art Number 550-141-807/0298 10 LGB (Series 2) — Control Supplement IV Start -up Low Fire Adjustment 1 . Disable high fire by disconnecting the blue wire in the two-stage gas valve. 2 . Connect manometer to gas manifold (manometer must be capable of measuring 0” to 14” W .
P art Number 550-141-807/0298 11 Flame Guardian WMBC-1A Electronic Pilot System – IRI V Sequence of operation 1 . Operating control begins startup sequence: a. Limit control contacts are closed. b. Purge timer is energized. 2 . Flame safeguard control pilot circuit energizes after 2.
P art Number 550-141-807/0298 12 LGB (Series 2) — Control Supplement W eil-McLain 500 Blaine Street Michigan City , IN 46360-2388 http://www .weil-mclain.com VI P arts list – T able 3 Description Size Vendor/Part Number Weil-McLain Part Number Primary Control Honey well RM789 5C1012 510-35 0-431 Prepurg e Timing Card 2 .
デバイスWeil-McLain WMBC-1Aの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Weil-McLain WMBC-1Aをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはWeil-McLain WMBC-1Aの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Weil-McLain WMBC-1Aの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Weil-McLain WMBC-1Aで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Weil-McLain WMBC-1Aを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はWeil-McLain WMBC-1Aの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Weil-McLain WMBC-1Aに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちWeil-McLain WMBC-1Aデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。