3Comメーカー59039-2の使用説明書/サービス説明書
ページ先へ移動 of 64
1 8 -DIN DIGITAL INDICATO R PRODUCT MANUA L 59039- 2.
CAUTION: REFER TO MANUA L THE INTERNATIONAL HAZARD SYMBOL IS INSCRIBED ADJACENT T O THE REAR CONNECTION TERMINALS. IT IS IMPORTANT TO READ TH E MANUAL BEFORE INSTALLING OR COMMISSIONING THE UNIT . PREFAC E This manual comprises two volumes : Volume I : This supports normal operation of the 1 8 -DI N Digital Indicator.
SM067- V 1 November, 200 0 ( i ) 5903 9 1 8 -DIN Digi tal In di ca to r Prod uct Man ual - Vol ume I 1 8 -DIN DIGITAL INDICATO R PRODUCT MANUA L VOLUME I OPERATING INSTRUCTION S In normal operation, t.
Con tent s 1 IN TRO DUC TIO N 1- 1 2 OP ERA TOR MOD E 2- 1 3 SET UP MOD E 3- 1 4 RS485 SE RIAL COM MU NI CA TION S 4-1 Ap pen di ce s A Al pha beti cal In de x A- 1 ( i i ) November, 200 0 SM067- V 1 .
SEC TION 1 INTRODUCTIO N The 1 8 -DIN Digital Indicator is an easy-to-operate microprocessor-based instrument , incorporating the latest in surface-mount and CMOS technology. The standard feature s include : * Large four- digit LED dis play (or der able as red or green) .
* 90 - 264V AC power sup ply . * De signed to com ply with EN50081 Part 2 (Emis sion) and EN5008 2 (Im mu nity) EMC speci fi ca tions . * Front panel seal ing to IP65 (NEMA 4) stan dard . * Pro gram ma ble digi tal fil ter . * Proc ess Vari able off set fa cil it y * Alarm type se lected from front panel.
SEC TION 2 OPERATOR MOD E 2. 1 INTRODUCTIO N The Operator Mode is the normal mode of the Indicator, once it has been set up an d configured as required. The front panel displays, indicators and keys are shown i n Figure 2 - 1 . 2.2 FOUR-DIGIT DISPLA Y In Operator Mode, this normally displays the process variable value.
(iii) Time elapsed in the Alarm 1 ac tive con di tion (units dis play shows ) . The dis play is in the for mat mm.ss [mm = min utes, ss = sec onds] or mmm.
2. 5 OVER-RANGE / UNDER-RANGE DISPLAY S If the process variable attains a value higher than the input scale maximum limi t (over-range) or lower than the input scale minimum limit (under-range), the uppe r display will show : for the over-range condition and: for the under-range condition .
for two seconds, indicating that the latched alarm has been reset. The latched Alarm 1 can be reset only if the original alarm condition has been cleared; this reset has n o effect whilst the alarm condition prevails .
SEC TION 3 SET UP MOD E 3. 1 ENTRY INTO SET UP MOD E To enter Set Up Mode, with the instrument initially in Operator Mode displaying th e process variable value, depress the Raise and Scroll keys simultaneously for three seconds.
3 - 2 November, 2000 OM067-3 Sec tion 3 1 8 -DIN Digi tal In di ca to r 5903 9 Set Up Mod e Prod uct Man ual - Vol ume I Table 3 - 1 Set Up Pa rame ter s Paramete r Alarm 1 Value 1 Alarm 1 Hysteresi s Alarm 2 Value 2 Alarm 2 Hysteresis 2 Alarm 3 Value 3 Alarm 3 Hysteresis 3 Process Variable Offse t Digital Filter Time Const .
3. 2 ALA R M 1 VALU E or If Alarm 1 is selected to be a Process High alarm, this defines the process variabl e value at or above which Alarm 1 will be active; the default value will be Input Range Maximum.
3. 6 ALARM 3 VALU E If Alarm 3 is selected to be a Process High alarm, this defines the process variabl e value at or above which Alarm 3 will be active; the default value will be Input Rang e Maximum.
3.1 1 LINEAR INPUT SCALE RANGE MAXIMU M This parameter, applicable only if a linear input is fitted, defines the scaled input value when the process variable input is at its maximum value. It is adjustable between –1999 and 9999 (with decimal point as defined by Linear Input Decimal Point Position).
3 - 6 November, 2000 OM067-3 Sec tion 3 1 8 -DIN Digi tal In di ca to r 5903 9 Set Up Mod e Prod uct Man ual - Vol ume I Figure 3 - 1 Alarm Op era tio n Process Low Alar m direct-actin g Process Low A.
SEC TION 4 RS485 SERIAL COMMUNICATION S This three-wire RS485-compatible serial communications option is the means by which communication may occur between the instrument and a master device (e.g. a computer or terminal) . 4. 1 PHYSICAL REQUIREMENT S There are two communications protocols available with this option : (a) AS CII (b) MOD BU S 4.
(a) A Start of Message characte r (b) One or two address characters (uniquely defining the slave ) (c) A parameter/data character string (d) An End of Message characte r Messages from the master devic.
OM067- 4 November, 2000 4 - 3 5903 9 1 8 -DIN Digi tal In di ca to r Sec tion 4 Product Man ual - Vol ume I RS485 Se rial Com mu ni ca tion s Table 4 - 1 {DATA} Ele ment - Sign and Deci mal Point Po si tion +abc d +abc.d +ab.cd +a.bcd –abc d –abc.
4.2. 1 Type 1 Mes sag e L {N} ? ? * This message is used by the master device to determine whether the addressed slave is active. The reply from the slave instrument, if it is active, i s L {N} ? A * An inactive instrument will give no reply .
L {N} {P} {DATA} I * (where I = Hex 49) indicating that the instrument is ready to implement the command. If the parameter specified is invalid or is not modifiable or if the desired value is outside the permitted range for that parameter, the instrument replies with a negative acknowledgement in the form: L {N} {P} {DATA} N * 4.
NOTE: This parameter value should be selected with care. An y adjustment to this parameter is, in effect, an adjustment to th e instrument’s calibration. Injudicious application of values to thi s parameter could lead to the displayed PV value having no meaningfu l relationship to the actual PV value .
the Input Scale Minimum and the decimal point position will always be the same as that for the input . NOTE: If this parameter is set to a value greater than the Recorde r Output Maximum Value, the sense of the Recorder Output is reversed .
4.3.1 6 In stru ment Com mand s {P} = Z Only Type 3 or Type 4 messages are allowed with this parameter. In the Type 3 message, the {DATA} field must be one of four five-digit numbers. The reply from th e instrument also contains the {DATA} field with the same content.
4. 4 MODBUS PROTOCO L With the RS485 Serial Communication option fitted and configured, communication between a master device and slave instruments via protocol conforming to th e MODBUS industry standard is available.
4.4. 2 Word Pa rame ter s 4 - 1 0 November, 200 0 OM067-4 Sec tion 4 1 8 -DIN Digi tal In di ca to r 5903 9 RS485 Se rial Com mu ni ca tion s Product Man ual - Vol ume I Paramete r Process Variable (P.
Al pha beti cal In de x A AL 1 Indicato r Functio n 2-2 AL2 Indicato r Functio n 2-2 AL3 Indicato r Functio n 2-2 Alarm Hysteresi s Alarm 1 3-3 Alarm 1 (adjusting - comms. ) 4-7 Alarm 2 3-3 Alarm 2 (adjusting - comms. ) 4-7 Alarm 3 3-4 Alarm 3 (adjusting - comms.
Communications Message Forma t 4- 1 D Display Strategy (Operator Mode) 3- 5 E Error Response s 4- 8 H Hardware Definition Cod e Viewing in Operator Mod e 2-4 Hardware Optio n Viewing in Operator Mod e 2-4 I Input Filter Time Constan t 3-4 Adjusting (comms.
Scan Tables Comman d 4-8 Sensor Break Indicatio n Operator Mod e 2-3 Set Up Mode Automatic exit fro m 3- 5 Entry int o 3- 1 Exit fro m 3- 5 Set Up Parameters All At defaul t Indication o f 3-1 T Time Elapsed Operator Mode displa y 2-2 Resetting (from front panel ) 2- 2 Resetting (via comms.
A - 4 November, 2000 OM067- A Ap pen dix A 1 8 -DIN Digi tal In di ca to r 5903 9 Al pha beti cal In de x Prod uct Man ual - Vol ume I.
SM067- V 2 November, 2000 ( i ) 5903 9 1 8 -DIN Digi tal In di ca to r Prod uct Man ual - Vol ume I I 1 8 -DIN DIGITAL INDICATO R PRODUCT MANUA L VOLUME I I INSTALLATION AN D CONFIGURATION INSTRUCTION S The procedures described in this volume must b e undertaken by technically competent servicing personnel .
Con tent s 1 IN STAL LA TIO N 1- 1 2 IN TER NAL LINKS AND SWITCHE S 2- 1 3 CON FIGU RA TION MOD E 3- 1 Ap pen di ces A PROD UCT SPECI FI CA TIO N A- 1 B AL PHA BETI CAL IN DE X B- 1 ( i i ) November, .
SEC TION 1 INSTALLATIO N 1. 1 UNPACKING PROCEDUR E 1 . Remove the instrument from its packing. The instrument is supplied with a panel gasket and push-fit fixing strap. Retain the packing for future use , should it be necessary to transport the instrument to a different site or to return it to the supplier for repair/testing .
To panel-mount the instrument : 1 . Insert the rear of the housing through the cut-out (from the front of the mounting panel) and hold the instrument lightly in position against the panel . Ensure that the panel gasket is not distorted and that the instrument i s positioned squarely against the mounting panel.
SM067- 1 November, 200 0 1 - 3 5903 9 1 8 -DIN Digi tal In di ca to r Sec tion 1 Prod uct Man ual - Vol ume I I In stal la tion Figure 1 - 3 Panel- Mountin g Front pane l Housing Tongues on fixing str.
1. 3 CONNECTIONS AND WIRIN G The rear terminal connections are illustrated in Figure 1-4 . 1 - 4 November, 200 0 SM067-1 Sec tion 1 1 8 -DIN Digi tal In di ca tor 5903 9 In stal la tio n Prod uct Man .
1.3.1 Mains (Line) In pu t The instrument will operate on 96 - 264V AC 50/60Hz mains (line) supply. The powe r consumption is approximately 4 VA . CAUTION : This equipment is designed for installation in an enclosur e which provides adequate protection against electric shock.
1 - 6 November, 200 0 SM067-1 Sec tion 1 1 8 -DIN Digi tal In di ca to r 5903 9 In stal la tio n Prod uct Man ual - Vol ume I I Table 1 - 1 Ther mo cou ple Ca ble Col our Code s.
1.3. 3 Ther mo cou ple In pu t The correct type of thermocouple extension leadwire/compensating cable must be used for the entire distance between the instrument and the thermocouple, ensuring tha t correct polarity is observed throughout. Joints in the cable should be avoided, i f possible.
1.3. 9 RS485 Se rial Com mu ni ca tions (Op tion ) The connections for the three-wire RS485 serial communications option (if fitted) are on Terminals 16, 17 and 18, as shown in Figure 1-4.
SEC TION 2 INTERNAL LINKS AND SWITCHE S 2. 1 REMOVING THE INSTRUMENT FROM ITS HOUSIN G To withdraw the instrument from its housing, simply grip the side edges of the fron t panel (there is a finger grip on each edge) and pull the instrument forwards.
2 - 2 November, 200 0 SM067-2 Sec tion 2 1 8 -DIN Digi tal In di ca to r 5903 9 In ter nal Links and Switche s Prod uct Man ual - Vol ume I I Figure 2 - 2 Re mov ing the Out put 2/Out put 3 Op tion PC.
2. 2 REMOVING/REPLACING THE OUTPUT 2/ OUTPUT 3 OPTION PCB s With the instrument removed from its housing : 1 . Gently push the rear ends of the CPU PCB and Power Supply PCB apar t slightly, until the .
2. 4 INSTALLING THE ENGINEERING UNIT LABE L The instrument is equipped with a label carrier (see Figure 2-4) to which a self-adhesive engineering unit label may be attached if required .
NOTE: Spare label carriers (Part No. 18633) and engineering labe l sheets (Part No. 84107) are available . SM067- 2 November, 200 0 2 - 5 5903 9 1 8 -DIN Digi tal In di ca to r Sec tion 2 Prod uct Man.
2.5 REPLACING THE INSTRUMENT IN ITS HOUSIN G To replace the instrument, simply align the CPU PCB and Power Supply PCB with thei r guides and connectors in the housing and slowly but firmly push the instrument int o position . CAUTION : Ensure that the instrument is correctly orientated.
2.7 OUTPUT 2 TYPE/OUTPUT 3 TYP E The type of output for Output 2 and Output 3 is determined by the Option PCB fitted i n the appropriate position (see Figure 2-1) and, in the case of the DC Output 2 Optio n PCB being fitted, the setting of Link Jumpers LJ8 and LJ9 on that Option PCB (se e Figure 2-7 and Table 2-2).
SEC TION 3 CONFIGURATION MODE 3. 1 ENTRY INTO CONFIGURATION MOD E To enter Configuration Mode : 1 . Ensure that the instrument is powered-down . 2 . Power-up the instrument and, within ten minutes of power-up, hold dow n the Raise and Scroll keys simultaneously for six seconds.
SM067- 3 November, 2000 3 - 2 5903 9 1 8 -DIN Digi tal In di ca to r Sec tion 3 Prod uct Man ual - Vol ume I I Con figu ra tion Mode Table 3 - 1 Con figu ra tion Mode Pa rame ter s Paramete r Hardware.
3 - 3 November, 200 0 SM067-3 Sec tion 3 1 8 -DIN Digi tal In di ca to r 5903 9 Con figu ra tion Mod e Prod uct Man ual - Vol ume I I Table 3-1 (Cont.) Configuration Mode Parameter s Paramete r Output.
SM067-3 November, 200 0 3 - 4 5903 9 1 8 -DIN Digi tal In di ca to r Sec tion 3 Prod uct Man ual - Vol ume I I Con figu ra tion Mode Table 3-1 (Cont.) Configuration Mode Parameter s Paramete r Output 3 Use (cont.
3. 2 HARDWARE DEFINITION COD E This parameter is used to represent the hardware fitted (input type, Output 1 type , Output 2 type and Output 3 type); this must be compatible with the hardware actuall y fitted.
3.3. 1 RS485 Se rial Com mu ni ca tions Op tio n For this option, the protocol used is defined by the Communications Protoco l parameter - see Subsection 3.
3.8 COMMUNICATIONS ADDRES S This is the unique address assigned to the instrument; it is used by the master device to communicate with the instrument . 3. 9 COMMUNICATIONS PROTOCO L There are two communications protocols available: ASCII (fixed, even parity) an d MODBUS (selectable odd parity, even parity or no parity).
AP PEN DIX A PRODUCT SPECIFICATIO N UNIVERSAL INPU T Genera l Maxi mum per In stru ment : On e In put Sam ple Rate : Four sam ples/sec on d Digi tal In put Fil ter : Time con stant se lecta ble from front panel - 0.0 (i.e. OFF), 0.5 to 100.0 sec onds in 0.
Cali bra tion : Com plies with BS4937, NBS125 and IEC584 . Sen sor Break Pro tec tion : Break de tected within two sec onds. Alarms op er ate as if the pro cess vari able has gone over- range .
Sen sor Break Pro tec tion: Ap pli ca ble to 4 - 20mA, 1 - 5V and 2 - 10V ranges only. Break de tected within two sec onds. Alarms op er ate as if th e pro cess vari able has gone under- range.
OUTPUT 2 (Option ) General Types Avail able : Re lay and DC . Relay Con tact Type : Sin gle pole dou ble throw (SPDT). Rat ing: 2A re sis tive at 120/240V AC . Life time : >500,000 op era tions at rate d volt age/cur rent . Iso la tion : In her ent .
Transmitter Power Suppl y Out put : 20 - 28V DC (24V DC nomi nal) . Mini mum Load Im ped ance : 910 Ω (22mA @ 20V DC) . ALARM CONTRO L Maxi mum Num ber of Alarms : Thre e Max.
Se ries Mode Re jec tion : >500% of span (at 50/60Hz) cause s neg li gi ble ef fect . DC Linear Input s Meas ure ment Ac cu racy : ± 0.05% of span ± 1LSD . Thermocouple Input s Meas ure ment Ac cu racy : ± 0.25% of span ± 1LSD. NOTE : Re duced per form ance with Type “B ” Ther mo cou ple be tween 100 - 60 0 o C (212 - 1112 o F) .
Lead Re sis tance: 50 Ω per lead maxi mum bal ance d (Pt100 ) Performance Under Operating Conditions Tem pera ture Sta bil ity : 0.01% of span/ o C change in am bi en t tem pera ture . Cold Junc tion Com pen sa tion (ther mo cou ple Only) : Bet ter than ± 1 o C .
Al pha beti cal In de x A AC/DC (24V) Suppl y Fuse ratin g 1- 5 Terminal connection s 1- 5 Voltage range s 1- 5 Alarm Type Selection o f 3- 6 C CJC Disabled Displa y Thermocouple inputs only 3-7 Cold .
M Mains (Line) Input Fuse rating 1- 5 Terminal connection s 1- 5 Voltage range 1- 5 O Output 2 DC Option PC B Link jumper s 2-7 Output 2 Option PC B Removal/replacement 2- 3 Output 2 Type Selection o .
B - 3 November, 2000 SM067- B Ap pen dix B 1 8 -DIN Digi tal In di ca to r 5903 9 Al pha beti cal In de x Prod uct Man ual - Vol ume I I.
デバイス3Com 59039-2の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
3Com 59039-2をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこには3Com 59039-2の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。3Com 59039-2の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。3Com 59039-2で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
3Com 59039-2を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又は3Com 59039-2の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、3Com 59039-2に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわち3Com 59039-2デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。