Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard. Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/or property damage.
2 INST ALLA TION REMOVE OLD THERMOSTAT 1. Shut off electricity at the main fuse box until installation is complete. Ensure that electrical power is disconnected. 2. Remove the front cover of the old thermostat. With wires still attached, remove wall plate from the wall.
3 RH Y 24 V AC 120 V AC Hot Neutral THERMOST A T SYSTEM G W Figure 5. T ypical wiring diagram for heat/cool, 5-wire, two-transf ormer systems HEA TING TRANSFORME R (Class II Current Limited) Heating S.
4 Press HOLD to change to the next menu item or press TIME to go backwards to the previous item in the menu. To exit the menu and return to the program operation, press RUN. If no keys are pressed within fifteen minutes, the thermostat will revert to normal operation.
5 5) Select Compressor Lockout LOC OFF or ON - Selecting LOC ON will cause the thermostat to wait 5 minutes before turning on the compressor if the heating and cooling system loses power. It will also wait 5 minutes minimum between cooling cycles. This is intended to help protect the compres- sor from short cycling.
6 PROGRAMMING YOUR THERMOSTAT This section will help you plan your thermostat ’ s program to meet your needs. For maximum comfort and efficiency, keep the following guidelines in mind when planning your program.
7 5. Press PRGM once. The currently programmed start time and setpoint temperature for the Monday's 2nd heating program period will appear. 6. Repeat steps 3 and 4 to select the start time and heating temperature for Monday's 2nd heating program period.
Symptom Possible Cause Corrective Action N o Heat/No Cool/No Fan 1. Blown fuse or tripped circuit breaker . Replace fuse or reset breaker . (common problems) 2. Furnace power switch to OFF . T urn switch to ON. 3. Furnace blower compartment door or Replace door panel in proper position to engage panel loose or not properly installed.
デバイスWhite Rodgers 1F87-251の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
White Rodgers 1F87-251をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはWhite Rodgers 1F87-251の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。White Rodgers 1F87-251の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。White Rodgers 1F87-251で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
White Rodgers 1F87-251を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はWhite Rodgers 1F87-251の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、White Rodgers 1F87-251に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちWhite Rodgers 1F87-251デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。