GENERAL YORK Model D1NA and D2NA units are cooling/heating air con - ditioners designed for outdoor installation. Only gas piping, elec - tric power and duct connections are required at the point of installation. The gas-fired heaters have hot surface to pilot ignition.
035-18265-001-A-0202 2 Unitary Products Group T ABLE OF CONTENTS TROUBLESHOOTING T roubleshooting Chart ..................................................... 15 T ABLES No. Description Page 1 Units Application Data ................................. 3 2 Natural Gas Application Data .
Not suitable for use with conventional venting systems. LIMIT ATIONS These units must be installed in accordance with the following national and local safety codes. 1. National Electrical Code ANSI/NFPS No. 70 or Canadian Electrical Code Part 1, C22.1 (latest editions).
Refer to Figure 5 for information concerning rear and bottom supply and return air duct openings. ROOF CURB On applications when a roof curb is used, the unit must be posi - tioned on the curb so the front of the unit is tight against the curb.
Scroll compressors operate in one direction only . If a three phase scroll compressor is experiencing: • Low amperage draw • Similar discharge and suction pressures • Increased noise level then the compressor is operating in reverse. T o correct this condition, switch any two (2) line voltage leads at the contactor .
3. Use wrought iron or steel pipe for all gas lines. Pipe dope should be applied sparingly to male threads only . CAUTION: If flexible stainless steel tubing is allowed by the authority having jurisdiction, wrought iron or steel pipe must be installed at the gas valve and extend a minimum of two (2) inches outside of the unit casing.
035-18265-001-A-0202 Unitary Products Group 7 FIG . 4 - CENTER OF GRA VITY 25 24 CENTER OF GRA VITY FRONT OF UNIT CORNER “C” CORNER “D” CORNER “A” CORNER “B” T ABLE 7 - UNIT WEIGHTS MODEL DNA UNIT SHIPPING WEIGHT (lbs.) UNIT OPERA TING WEIGHT (lbs.
035-18265-001-A-0202 8 Unitary Products Group FIG . 5 - DIMENSIONS AND CLEARANCES CLEARANCES (Minimum) Front 36" Back 0" Left Side (Filter Access) 24" Right Side 12" Below Unit 1 0.
HEA TING When the thermostat calls for “HEA T”, the thermostat terminal “W” is energized, energizing the combustion air blower . After airflow is established, the air proving switch closes, the hot surface ignitor is energized and the pilot valve opens ignit - ing the pilot flame.
2. Check for correct manifold gas pressures. See “Checking Gas Input”. 3. Check the supply gas pressure. It must be within the limits shown on rating nameplate. Supply pressure should be checked with all gas appliances in the building at full fire.
3. After maintenance of the pilot assembly , always measure the resistance across the ignitor . If the resistance is greater than 10 ohms, discard the ignitor and replace it with a new ignitor .
NORMAL MAINTENANCE WARNING: Prior to any of the following maintenance proce - dures, shut off all power to the unit, to avoid per - sonal injury . Periodic maintenance consists of changing or cleaning filters. Under some conditions, the main burners should be cleaned.
Checking Supply Air CFM T o check the supply air CFM after the initial balancing has been completed: 1.Remove the two ¼ inch dot plugs in the duct panel. 2.Insert at least 8 inches of ¼ inch tubing into each of these holes for sufficient penetration into the airflow on both sides of the indoor coil.
14 Unitary Products Group 035-18265-001-A-0202 T ABLE 1 1 - SUPERHEA T CHARGING T ABLE FOR MODEL D1NA024 OUTDOOR TEMPERATURE (F) SUPERHEA T A T COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM/TON INDOOR WB TEMPERATURE (F) 55 57 59 61 63 65 67 69 71 73 75 65 13.
Unitary Products Group 15 035-18265-001-A-0202 T ABLE 14 - SUPERHEA T CHARGING T ABLE FOR MODEL D1NA042 OUTDOOR TEMPERATURE (F) SUPERHEA T A T COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM/TON INDOOR WB TEMPERATURE (F) 55 57 59 61 63 65 67 69 71 73 75 65 18.
16 Unitary Products Group 035-18265-001-A-0202 TROUBLESHOOTING YES . T urn gas supply off . Set thermostat to SV9501 is powered (24 V AC nominal) Igniter warms up and glows red Pilot valves opens T urn gas on. Pilot burner lights? Check . Line voltage power .
Unitary Products Group 17 035-18265-001-A-0202 FIG . 9 - TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPL Y) FIG . 10 - TYPICAL WIRING DIAGRAM (208/230-3-60 POWER SUPPL Y) SEE DET AIL "A" (S.
18 Unitary Products Group 035-18265-001-A-0202 FIG . 1 1 - TYPICAL WIRING DIAGRAM (460-3-60 POWER SUPPL Y) FIG . 12 - TYPICAL WIRING DIAGRAM (575-3-60 POWER SUPPL Y) (See page 18) B (See page 18) B.
Unitary Products Group 19 035-18265-001-A-0202 (AL TERNA TE) (AL TERNA TE) TYPICAL WIRING DIAGRAM NOTES (See pages 16 and 17) TYPICAL WIRING DIAGRAM LEGEND (See pages 16 and 17) FIG .
20 Unitary Products Group 035-18265-001-A-0202 NOTES.
Unitary Products Group 5005 Y ork Drive, Noman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A. Copyright by Y ork International Corporation 2000 All Rights Reserved.
デバイスYork D1NA018の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
York D1NA018をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはYork D1NA018の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。York D1NA018の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。York D1NA018で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
York D1NA018を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はYork D1NA018の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、York D1NA018に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちYork D1NA018デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。