D20 7 1A EN Operation & Installation Guide Fire Alarm Control Panel.
Bosch | 09 /04 | 7 4-0620 0-00 0-F 2 D20 7 1A | Operations & Installation Guide | Contents Contents 1 .0 Overview .......................................................................... 4 1 . 1 Communicator .....................................
3 Bosch | 09 /04 | 7 4-0620 0-00 0-F D20 7 1A | Operations & Installation Guide | F CC Notice FCC Notice The D2 0 7 1A Fire Alarm Control Panel (FA C P) generates, uses, and can radiate radio frequency energy . If this device is not installed according to the manufacturer’s instructions, it can cause interference to radio communications.
Bosch | 09 /04 | 7 4-0620 0-00 0-F 4 D20 7 1A | Operations & Installation Guide | 1 . 0 Overview The D2 0 7 1A Fire Alarm Control Panel (F AC P) is a three-zone digital alarm communicator transmitter (DACT) used in limited stand-alone applications or in off-premises monitoring of existing F ACPs in slave applications.
5 Bosch | 09 /04 | 7 4-0620 0-00 0-F 1 .5. 1 Mandatory Connections T o comply with the N F PA 72 Central Station Fire or N F P A 7 2 Remote Station Signaling S ervice, connect the D20 7 1A as described in T able 2 . The Class “ A ” and Class “B” circuits are mandatory connections for the slave and stand-alone applications.
Bosch | 09 /04 | 7 4-0620 0-00 0-F 6 D20 7 1A | Operations & Installation Guide | 1.6 Slave Communicator Applications T o use the D2 0 7 1A as a slave communicator that only provides signaling connections, connect the D207 1A to an existing U L Listed N F P A 7 2 F ACP .
7 Bosch | 09 /04 | 7 4-0620 0-00 0-F D20 7 1A | Operations & Installation Guide | 1 .0 Overview 1 .8.5 Phone Line T rouble LE D This yellow Phone Line T rouble LE D ( Item 5 in Figure 1 ) is visible through the top of the enclosure at the upper right corner ( Item 6 in Figure 1 ).
Bosch | 09 /04 | 7 4-0620 0-00 0-F 8 D20 7 1A | Operations & Installation Guide | 2. 0 Installation Some terminals are wired differently for the stand-alone ( Figure 2 ) and slave applications ( Figure 3 on page 9).
9 Bosch | 09 /04 | 7 4-0620 0-00 0-F D20 7 1A | Operations & Installation Guide | 2.0 Inst allation 1. Do not conne ct ear th gro und when conn ected t o a 24 VDC power suppl y. 2. Do not conne ct a bat tery when co nnected t o a 2 4 VDC power suppl y (maxi mum chargi ng curr ent o f 300 mA) .
Bosch | 09 /04 | 7 4-0620 0-00 0-F 10 D20 7 1A | Operations & Installation Guide | 2.1 Earth Ground Wiring Only use Terminal 3, not telephone or electrica l ground, f or earth g round connectio ns. 2. 1 . 1 1 2 V AC Mode T o prevent damage from electrostatic charges or other transient electrical surges, use 1 6 A WG ( 1 .
11 Bosch | 09 /04 | 7 4-0620 0-00 0-F • If the time specified in the retard time accumulates in one or more successive alarm activations, the D207 1A transmits an Alarm Zone 1 Report and activates the Alarm Relay .
Bosch | 09 /04 | 7 4-0620 0-00 0-F 12 D20 7 1A | Operations & Installation Guide | 2.3.3 Mode 3 Mode 3 ( Figur e 6 ) uses a 1 .8 k Ω E OL resistor at the end of the loops.
13 Bosch | 09 /04 | 7 4-0620 0-00 0-F 2.4.2 Wiring Connect only low voltage power sources and devices to T erminals 1 6, 1 7 , and 1 8. Do not use the D2 0 7 1A Standby Battery to provide a power output for the circuit. 2.5 Phone Line Trouble Relay U se T erminals 1 3, 1 4, and 1 5 for Phone Line T rouble Relay connections.
Bosch | 09 /04 | 7 4-0620 0-00 0-F 14 D20 7 1A | Operations & Installation Guide | Set the 1 2 V Mode to YE S . Refer t o Section 2. 7 . 1 Battery for battery installation instructions. N F P A 72 applications require 1 1 0 V AC or 1 20 V AC, 60 Hz commercial power for the transformer to be unswitched and from a reliable source.
15 Bosch | 09 /04 | 7 4-0620 0-00 0-F Restoral Z N 9 Exceptions : If a battery is not connected to the D207 1A when AC power is connected, the control panel sends a RE STORAL ZN 9 Report to the receiver . A RE ST O RAL ZN 9 is also sent after the programmer disconnects from the D207 1A .
Bosch | 09 /04 | 7 4-0620 0-00 0-F 16 D20 7 1A | Operations & Installation Guide | Refer to Section 6.0 T roubleshooting on page 24 for help in determining the cause of telephone line problems.
17 Bosch | 09 /04 | 7 4-0620 0-00 0-F 2.9. 1 Screw Mounting 1 . Select the mounting location in the enclosure. 2. P osition the D2 0 7 1A in the desired location. 3. U se a pencil to mark the mounting tab holes. 4. Drill holes ( 1 /8 in. [ 3. 1 8 mm ]) for the screws provided.
Bosch | 09 /04 | 7 4-0620 0-00 0-F 18 D20 7 1A | Operations & Installation Guide | 3. 0 Programming The in format ion in this se ction is not int ended to be a subs titute fo r the D5200 Pr ogrammer Operat ion Manual (P/N: 74-06176-000 ). Become famil iar with t he D5200 Programme r Operation Manual before programm ing any Bosc h product.
19 Bosch | 09 /04 | 7 4-0620 0-00 0-F D20 7 1A | Operations & Inst allation Guide | 3.0 Programming 3.2 Function Keys T able 7 identifies the six function keys that simplify using the programmer . 3.3 Data Keys U se the white keys on the keyboard for data entry .
Bosch | 09 /04 | 7 4-0620 0-00 0-F 20 D20 7 1A | Operations & Installation Guide | 3.8 Program Modules Unlike larger Bosch products, the D20 7 1 Product Handler does not group program items in program modules. When you enter the 2 0 7 1 program, you are in the Program Item Level.
21 Bosch | 09 /04 | 7 4-0620 0-00 0-F PriPh# Default: Blank Select ions: 0 to 9, B to F, or Blank U se to select the primary receiver telephone number .
Bosch | 09 /04 | 7 4-0620 0-00 0-F 22 D20 7 1A | Operations & Installation Guide | Reset Time Default: 0 Selections: 0 to 90 U se to program the reset timer for the Class “ A ” Alarm Initiating Circuit (Zone 1 ). Enter the number of seconds you want for the reset time.
23 Bosch | 09 /04 | 7 4-0620 0-00 0-F 5 . 0 Receiver Reports D20 7 1A | Operations & Installation Guide | 5.0 Receiver Reports Title Description ALARM ZN 1 Closure or short between the two loops of t he Class “A” Alar m Initiating Circ uit.
Bosch | 09 /04 | 7 4-0620 0-00 0-F 24 D20 7 1A | Operations & Installation Guide | 6 .0 T roubleshoot ing T o help prevent problems, read the preceding sections of this guide and confirm the control panel is correctly installed and programmed.
25 Bosch | 09 /04 | 7 4-0620 0-00 0-F 6.3 Trouble Zone E Refer T able 1 0 on page 23 for the causes of the TROU B LE Z N E Report. If TROU B LE Z N E Reports regularly accompany other reports: • After two attempts to reach the receiver , a D2 0 7 1A switches to the alternate phone line for the third attempt.
Bosch | 09 /04 | 7 4-0620 0-00 0-F 26 D20 7 1A | Operations & Installation Guide | 6.5 Zones Problems 6.6 Trouble Zone 9 A TRO U BLE Z N 9 Report tells you there is a problem with the battery when the D2 0 7 1A is in 1 2 V AC Mode. It also indicates there is a problem with the power supply in the 2 4 VD C M ode.
27 Bosch | 09 /04 | 7 4-0620 0-00 0-F D20 7 1A | Operations & Installation Guide | 7 .0 Specifications 7 .0 Specifications Power In put 12 VAC, 20 VA with 12 VDC batt ery 24 VDC Spe cification 12 VAC Mode 24 VA C Mode Idle Current 29.5 mA 30.0 mA Ba ttery Chargin g 51.
Bosch 1 30 Perinton Parkway Fairport, NY 1 4450-9 1 99 U SA Customer Service: (800) 289-0096 T echnical Support: ( 888) 8 86-6 1 89 © 2004 Bosch 7 4-0 6200-000- F.
デバイスBosch Appliances D2071Aの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bosch Appliances D2071Aをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBosch Appliances D2071Aの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bosch Appliances D2071Aの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bosch Appliances D2071Aで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bosch Appliances D2071Aを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBosch Appliances D2071Aの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bosch Appliances D2071Aに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBosch Appliances D2071Aデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。