Bosch AppliancesメーカーFPD-7024の使用説明書/サービス説明書
ページ先へ移動 of 122
Fire Alarm Control Panels FPD-7024 en Installation and Operation Manual.
.
Table of contents 1 Notices 6 1.1 FCC Compliance Notice 6 1.2 FCC Phone Connection to Users 6 1.3 Industry Canada Notice 7 1.4 Trademarks 7 2 Overview 8 2.1 System overview 8 2.2 Components 9 2.2.1 On-board conventional points 9 2.2.2 Off-board addressable points (with D7039 Multiplex Expansion Module) 9 2.
6.2 Basic System Use 38 6.2.1 Function keys 38 6.2.2 Selecting menu items 38 6.2.3 After a Main Menu item is selected 38 6.2.4 Returning to an earlier screen 38 6.2.5 Entering data 38 6.2.6 Drill 38 6.2.7 Disable 38 6.2.8 History 39 6.2.9 Remote Programming 40 6.
8.4.2 Point function 70 8.4.3 Point copy 72 8.5 PROG OUTPUTS 73 8.5.1 Programming NACs 73 8.5.2 Programming relays 76 8.6 PROG ACCOUNTS 77 8.6.1 Phone Numbers/IP Addresses 78 8.6.2 Phone Control 82 8.6.3 Report Steering 83 8.6.4 Ring Count 84 8.6.5 Communication Tries 85 8.
Notices FCC Compliance Notice This equipment was tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
Industry Canada Notice The Industry Canada label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational, and safety requirements. Industry Canada does not guarantee the equipment will operate to the user’s satisfaction.
Overview System overview The FPD‑7024 Fire Alarm Control Panel is a fully integrated hard-wire fire alarm system. It can support four input points (expandable to 255 using D7039 Multiplex Expansion Module and the FPC‑7034 Four-Point Expander) and 16 individual users (expandable to 100 with the D7039).
4 Zone input terminal strip 10 NAC terminal strip 5 Option bus terminal strip 11 Auxiliary power terminal strip 6 FPC-7034 point expander connector pins Components On-board conventional points All on-board points and points implemented with the FPC-7034 work with two- or four-wire detectors.
– Each point is individually supervised for proper connection to the common bus (when over ten points are troubled, up to ten troubles are shown per bus and the balance of the troubles is indicated by a common bus failure message). – Response time can be set to fast, or programmed from 1 to 89 seconds.
D7030X zones covered shown on D7030X shown on D7032 (if attached) comments 4 49 to 64 49 to 56 57 to 64 Combination with fourth lowest option bus address (such as Address 4) 5 1 to 16 1 to 8 9 to 16 F.
Communicator The communicator can report to two phone numbers or IP addresses with full single, double, and back-up reporting. Communicates in SIA, Modem IIIa 2 , Contact ID, BFSK, and 3/1 and 4/2 Tone burst formats (available communication formats depend on phone or IP connection).
Figure 2.2: Supplemental Reporting 1 Jumper from R1 to R2 3 House phone 2 Jumper from T1 to T2 4 TELCO line Users The system allows up to 16 individual users, or up to 100 users when the D7039 is installed.
Device Quantity Standby existing/device Total standby Alarm existing/ device Total alarm FMR‑7036 Annunciator Keypad 80 mA 100 mA D7030X Eight‑Point LED Annunciator 1 27 mA 132 mA D7030X‑S2 Eigh.
Device Quantity Standby existing/device Total standby Alarm existing/ device Total alarm D7053 MUX I/ O Module Fire 0.70 mA 0.70 mA Smoke Detectors Bells, Horns, and so on Other Sensors Other Grand To.
Required batteries for existing load Use the following procedure to determine the battery requirements for your system: – Estimate the size of the battery required to support the standby load using .
– Select the next larger standard battery for the system. If the results show a requirement for a battery over 40 Ah, reduce the existing load or add an external regulated fire protective signaling power supply.
Device Function D7039 Multiplex Expansion Module Provides either 2 two-wire (Class B, Style 4) multiplex buses or 1 four-wire (Class A, Style 6) multiplex bus. In Class A mode, up to 120 addressable points can be added. In Class B Mode, up to 247 addressable points can be added.
Table 2.8: Compatible devices Install D7042 modules only at addresses: 9 17 25 33 41 49 57 65 73 81 89 97 105 113 121 129 137 145 153 161 169 177 185 193 201 209 217 225 233 241 Do not install D7052 a.
Fire Safety Danger! No fire detection device or system is 100% foolproof. This fire alarm system can provide early warning of a developing fire. Such a system, however, does not ensure protection against property damage or loss of life resulting from a fire.
Figure 3.1: Smoke detector locations in residential settings 1 Bedroom 5 Basement 2 Hall 6 Recreation room 3 Living room 7 Kitchen 4 Dining room * Smoke detector Having and practicing an escape plan A fire warning can be wasted unless the personnel planned in advance for a rapid and safe exit from the building.
Installation Installation guide for UL Listed systems FPD‑7024 UL Listings The FPD‑7024 is UL Listed for the following: – Commercial Fire Alarm (UL Standard UL864) – Type Service: Auxiliary, L.
Timer Programming – Program Auto Silence Time for not less than five minutes, or to “0” to disable auto-silence operation. Point Programming – For fire points: open = trouble, latching. Alarm Output Programming – Program notification appliance circuits to activate from the appropriate input points.
Figure 4.1: Wiring the D132B smoke power reversing module 1 Power limited and supervised 7 12/24 VDC 2 Optional alarm latch 8 24 V reversing detectors 3 Loop 9 2.
Figure 4.2: Wiring the D185 1 D185 module 5 Fire control panel 2 To monitoring station bk black 3 D275 bu blue 4 2.2 kΩ EOL ye yellow The module can signal alarm, trouble, and supervisory conditions. The Wiring the D185 figure , 24 shows the module being used to signal alarm and trouble conditions only.
5. Install and tighten the remaining two screws in the bottom mounting holes. 6. Knock out the desired wire entrances on the enclosure. For mounting hole locations, see the following figure: Figure 4.
! Warning! Before the circuit board is installed, connect the supplied ground wires between the door and the enclosure and from the transformer to the enclosure using the supplied nuts. Both grounds connect to the stud in the enclosure to the left of the circuit board.
If the [*/BACK] key is not pressed during the power-up time-out period, the control panel resumes operation using the last confirmed status of the affected expander and displays an installation error condition.
Connection FACP terminal connection Danger! Incorrect connections may result in damage to the unit and personal injury. ! Warning! Before servicing this equipment, remove all power including the transformer, battery and phone lines. i Notice! Shared cable is not recommended for option bus, telephone or NAC wiring.
i Notice! All wiring except battery terminal and primary AC power is power-limited. Primary AC and bat- tery wires must be separated from other wires by at least ¼ in. (64 mm) and tied to prevent movement. Figure 5.3: Transformer RD red BN brown supervised: YE yellow WH white BK black Figure 5.
Unsupervised: Switched unsupervised: 1 Relay 1 4 Earth ground 2 Relay 2 5 Smoke detector 3 Relay 3 Input Points 1-4: (supervised) Points are intended for connection of normally-open/normally-closed alarm contacts. They may also be used for compatible two-wire smoke detectors.
DX4020, B420 models, ITS-DX4020-G Figure 5.6: Keypad Connection (supervised, Class B, Style 4, 500 mA maximum) Figure 5.7: Backup Batteries 1 Class B, Style Y supervised: 2 Class A, Style Z BAT Battery 3 Backup batteries BK black EOL End of line RD red i Notice! Unswitched unsupervised Auxiliary Power: 24 V, 1.
Danger! Explosion and burn hazard! Do not short terminals! Notification appliance circuit: NAC 1+ NAC 1- +24 V while in alarm; ground while in standby. Ground while in alarm; supervisory voltage while in standby. Notification appliance circuit: NAC 2+ NAC 2- +24 V while in alarm; ground while in standby.
Figure 5.8: Transformer Connections Primary: YE yellow WH white BK black Option bus wiring requirements Use 18 AWG (1.2 mm) or larger wire to connect option bus devices to the FACP. The total length of wire connected to the option bus terminals must not exceed 4 000 ft (1 219 m), regardless of the wire gauge wire used.
Add together the alarm existing current draw by all the devices on the wiring run to determine the maximum allowed distance between the option bus terminals on the control panel and the last device on the wire run (the device farthest from the control panel).
System Operation Modes of Operation There are four modes of system operation for the FPD‑7024: normal, alarm, supervisory, and trouble. Normal When the system operates normally, it shows SYSTEM NORMAL on the top line of the display, the Power LED lights steadily, and no other LEDs are lit.
Trouble When a trouble condition occurs (such as cut wiring for a point or AC power fails), the sounder beeps every 10 seconds. The Trouble LED lights and the LCD shows the trouble condition. When you back out of the detailed screen when the [4/<] key is pressed the group is entered and shows TROUBLE (XXX).
Basic System Use Function keys A keypad that does not require a PIN number shows (under normal conditions) SYSTEM NORMAL on the top line, and existing date and time on the bottom line. On a keypad that does require a PIN number, enter the PIN number first.
History i Notice! If a system without a D7039 Multiplex Expansion Module loses all power (AC and standby bat- tery), all history events are cleared. The HISTORY option is a chronological list of system events that occurred. Press the [History] key to HISTORY select from the Main Menu (SYSTEM NORMAL display).
For additional history log ID information, see the Modem IIIa 2 reporting table , 105 . Remote Programming Call for remote programming Phone Numbers 1 and 3 must be programmed, along with Account Code 1. The control panel calls Phone Number 3 and attempts to connect for downloading.
Figure 6.1: Built-in Keypad 1 Green Power LED - is on when the AC power is present, and flashes when the unit is operating from battery power. 9 [#/Enter] key - to accept data when in the programming mode. 2 Yellow Trouble LED - lights when the system detects a problem with wiring or internal circuitry.
4 Yellow Silenced LED - lights when the user manually silences an alarm condition (fire or water flow), turns off when the condition that was silenced is corrected. 12 [Silence] key - mutes the bell or sirens for an alarm condition, if the system is so configured.
Figure 6.2: FMR-7033 Keypad 1 LEDs 3 Keys 2 Keypad Display Testing Select any of seven special test modes using the [Test] key on the built‑in and FMR‑7033 keypads. Walk test The Walk Test allows a technician to alarm each point manually to ensure that detectors connected to a point send an Alarm report to the control panel.
i Notice! This test is available only if your system sends alarms and system information to a monitoring service, and was programmed by the security installing company to permit communicator tests.
5. Show Status: After you select a device and press [#/Enter], this test shows detailed status information for the selected device. Eight conditions (not all status conditions apply to or are supported by all devices) are shown. See the display shown below (which updates automatically every five seconds).
Figure 6.3: Mapping inputs, zones, and outputs 1 Input Point 1 is assigned to Zone 1, mapped to NAC Point 1. 4 Input Point 4 is assigned to Zone 2, mapped to NACs 1 and 2. 2 Input Point 2 is assigned to Zone 2, mapped to NACs 1 and 2. 5 Input Point 5 is assigned to Zone 3, mapped to NAC 2, LR 1 and RR1.
Zone Condition 61 General Waterflow (Non-silenceable). Active when any waterflow alarm is present. 62 General Trouble. Active while any system trouble is present, not active in test and programming modes. 63 General Alarm, Waterflow (non-silenceable).
i Notice! To disable a phone number, set the FORMAT to 0=disable. To completely disable the commu- nicator, set FORMAT to 0=disable for both phone numbers, and set MONITOR to 0=NO for both phone lines. i Notice! Do not install this control panel on a phone line that might be required for other emergency use.
Programming Danger! Untested systems! After any programming change, and especially after remote programming changes, completely check the operation of the control panel. Hazards to life and property can result if the system is not tested to detect possible improper programming.
Program feature or option Permitted in UL864 (Yes/No) Possible settings Settings permitted in UL864 NAC Config Yes Steady Pulsing California March Temporal Wheelock Gentex System Sensor Steady Pulsing.
Function Configuration Local only? Silenceable? Loop response 1. Pull Station Fire No No Fast 2. Smoke Detector Fire No No Fast 3. Reset Keyswitch Reset Yes No Fast 4. Silence Keyswitch Silence Yes No Fast 5. Supervisory Input Supervisory No Yes Fast 6.
Key Values 7 P R S 7 2 8 T U V 8 2 9 W X Y 9 2 0 Prog Q Z 0 # Enter Enters the description and returns to the programming menu. Back * Returns to the programming menu without entering changes. Silence Moves the cursor one space to the right. Disable Moves the cursor one space to the left.
Figure 7.1: Essential keys for alpha programming 1 Number keys (including 0) - used to enter alphanumeric values. 4 [Disable] key - moves the cursor one space to the left. 2 [*/Back] key - used to exit alpha programming, or exit the programming mode entirely.
BFSK Similar to the programming of system events for 4/2 formats, five system events can be programmed for two unique digits each when the BFSK format is used. This programming is done under 7- PROG FORMATS, 3- BFSK RPT CODS . The BFSK format supports only a three-digit account number.
Program menu tree Main Menu Level 1 Level 2 Level 3 Level 4 Level 5 1-PROG TIME 2-SECURITY 1-SYSTEM 2-AUTO TEST 3-DA YLIGHT SA V 1-TEST TIME 2-TEST FREQ 1-DISABLE 2-ENABLE 1-PINS 2-AUTHORITY 1-PROGRAM.
Figure 7.3: Program Menu - continued For factory defaults, see Appendix D. Shortcuts You can use shortcuts to reduce repetition and provide speedy instructions for programming the control panel. The first level in the system is the Main Menu. For all system programming, <PROG/0> is your Main Menu choice.
The second level in your system provides eight options: PROG TIME, SECURITY, PROG SYSTEM, PROG INPUTS, PROG OUTPUTS, PROG ACCOUNTS, PROG FORMATS, and HISTORY DEFAULTS. When the D7039 MUX Expander is installed, a ninth option appears: PROGRAM MUX. The second number in the shortcut enters the Level 2 option and allows access to Level 3.
inhibited (but alarm monitoring continuing), the system indicates SYSTEM TROUBLE, RMT PRG ACTIVE during remote programming. Sounders do not activate during this mode, but other outputs programmed for Zone 62, general system trouble, do activate.
Control Panel Programming Main Menu: SYSTEM NORMAL SELECT: PROG/0 SELECT: ENTER/# SELECT: TEST SELECT: HISTORY SELECT: DISABLE SELECT: DRILL Programming Menu: PROG/0 1-PROG TIME 2-SECURITY 3-PROG SYST.
AUTOMATIC TEST 1-TEST TIME 2-TEST FREQNCY Press [1] to select Test Time. The following window appears: AUTO TEST TIMEHHMM: _______ Enter the time followed by the [#/Enter] key. Test Frequency Shortcut: 0- PROG , 1- PROG TIME , 2- AUTO TEST This feature allows you to program how often the automatic test reports are sent.
2-AUTHORITY Personal Identification Numbers (PINs) Programmer PIN Shortcut: 0- PROG , 2- SECURITY , 1- PINS The Programmer PIN is the code used by the installer to configure and operate the panel. Factory default code is 9876 and may be changed at any time.
PIN Authority Level Allowed Operations Maximum (1) All control panel operations, including programming and disable. Medium (2) System test modes, fire drill, reset, silence, view history.
This feature determines how long the smoke detector power is off after reset. No alarms are registered by the system for 5 sec after power is returned. The display scrolls through the TIMERS options. Press [1] for Smoke Reset. The following window appears: SMOKE RESET (__ ) (1-16 SECS):_______ Enter the time and press [#/Enter].
i Notice! If the condition that caused and alarm is not corrected after an alarm is silenced (automatical- ly or manually), the alarm sounds again after 24 hours. The system must eventually be reset after silencing to allow the alarmed zones to restore and detect new alarms.
! Warning! Inoperable, unsupervised devices! Be sure the count of devices displayed when this operation completes matches the number of devices installed on both buses. Devices not detected during the update bus operation will not operate and will not be supervised.
PIN REQUIRED? 1- LOCAL 2- REMOTE Press [1] to require a PIN at the local keypad. The following window appears: LOCAL KEYPD PIN? _______: YES(1) NO(0) Press the number key that corresponds to your selection. The existing setting is shown in front of the colon on the second line.
Remote programming Shortcut: 0- PROG , 3- PROG SYSTEM , 7- REMOTE PGM Remote programming allows the panel to be called from a remote site by phone to reconfigure any of the programmable options. When remote programming is disabled, you can still connect to the control panel for diagnostics and to view the existing program.
Pressing [Drill] retrieves the next point. For instance, if you are programming Point 2 and you press [Drill], you retrieve the setting for Point 3. Pressing [History] retrieves the previous point. For instance, if you are programming Point 2 and you press [History], you return to the setting for Point 1.
OUTPUT ZONE ZZZ (01 - 50):_______ Press the number key that corresponds to your selection. ZZZ indicates the point being programmed. The existing setting is shown on the second line.
Enter the description using the numeric, [Silence] and [History] keys, then press [#/Enter] to save the description. Point function Shortcut: 0- PROG , 4- PROG INPUTS , 2- POINT FUNCTION There are 16 .
– AC Fault: When activating, the control panel waits for the AC Delay Timer to expire before indicating or sending a trouble condition. When the timer expires, it shows an AC Fault on the control panel and the trouble LED turns on. Enter the point number you wish to program and press [#/Enter].
Loop response Shortcut: 0- PROG , 4- PROG INPUTS , 2- POINT FUNCTION This feature allows you to configure points to activate with standard response time (setting 1) or one system-wide programmed response time (setting 2). Enter the point number you wish to program and press [#/Enter].
COPY FROM POINT:_______ Enter the point you wish to copy from and press [#/Enter]. COPY TO FIRST POINT:_______ Enter the first point you wish to copy to and press [#/Enter]. COPY TO LAST POINT:_______ Enter the last point you wish to copy to and press [#/Enter].
NAC CONFIG ( ) 1- STEADY 2- PULSING 3- CALIFORNIA MARCH 4- TEMPORAL 5- WHEELOCK 6- GENTEX 7- SYSTEM SENSOR For acceptable programming selections for UL864 9 th edition Listed applications, see Programming features for UL864 , 49 . These selections control the pattern (code) for the selected NAC.
Zone Pre-Assigned Condition 52 General Fire Alarm (non-silencing) 53 General Fire Alarm, (silencing) 54 Ground Start 55 General Supervisory, (silencing) 56 General Waterflow, (silencing) 57 Communicat.
Programming relays Shortcut: 0- PROG , 5- PROG OUTPUTS , 2- RELAYS The main control panel includes three on-board relays (Relay 1, Relay 2, and Relay 3). The FPD‑7024 can also support up to two D7035 Octal Relay Modules (Remote Relay 1 and Remote Relay 2), that offer a total of 16 remote relays (eight relays per module).
i Notice! The @ x shows the address of the relay module in the system. The lower number address is Relay 1; the higher one is Relay 2.When you address a MUX Module, you assign an address. If you have a dual point, it would have two consecutive addresses.
7- ALT.COMM Phone Numbers/IP Addresses Shortcut: 0- PROG , 6- PROG ACC’NTS , 1- PHONE/IP NUMS The system can be programmed with two reporting phone numbers or IP addresses. Phone/ IP #1 is used with Account Number 1; Phone/IP #2 is used with Account Number 2.
Several keys assist when you enter phone or IP numbers. For these keys, see the following table: Press Action [SILENCE] Advance to next position [DISABLE] Go back one position [RESET] Clear position Table 8.4: Phone number assistance keys i Notice! For a phone number, you must enter 1 as a prefix before the special character >.
For example, if the necessary wait time is 30 sec, digits 14 through 16 should be 0, 3, 0 respectively. In larger installation sites using alternate communications as a destination, set the wait time to a higher value to compensate for network congestion delays.
Anti-Replay – Digit 20, Default: 1 Digit 20 of the phone number enables the Anti-Replay Feature for central station communications. A zero in this location disables this feature.
i Notice! If using the B420 models, the DX4020, or the ITS-DX4020-G for reporting events, the Modem IIIa 2 and Contact ID formats are possible: Account Numbers Shortcut: 0- PROG , 6- PROG ACC’NTS , 1- PHONE/IP NUMS The account numbers identify the control panel when it sends reports to the central station.
PHONE CONTROL #1 1- MONITOR LINE 2- DIALING TYPE For explanations of the phone control options, see the following sections for Monitor Line and Dialing Type.
i Notice! If any reports are directed to Phone/IP Number 2 (including the default, PHONE 2 BACKUP), a phone number and account number must be programmed for Phone/IP Number 2. The con- trol panel indicates a COMM FAULT if it sends a report (using Phone Number 1 parameters) which references unprogrammed Phone/IP Number 2 parameters.
RING COUNT (01-15, 00=DIS) _______ Enter the information and press [#/Enter]. The previous window appears. An entry of [0/Prog] [0/Prog] disables ring detection. For acceptable programming selections for UL864 9 th edition Listed applications, see Programming features for UL864 , 49 .
i Notice! This feature offers the use of hexadecimal digits (0 through F). Because the specific keys A through F are not available on the keypad, use the following equivalent keys: History=A, Test=B, .
4/2 Report Codes Shortcut: 0- PROG , 7- PROG FORMATS , 1- 4/2 RPT CODS 4/2 Report Codes apply to system conditions but only when 3/1 or 4/2 format is selected.
SYSTM IN TST ( ) 0 THRU 9 <HISTORY>: A <TEST>: B <DISABLE>: C <DRILL>: D <SILENCE>: E <RESET>: F Enter digits that correspond to the selected condition by pressing a number key, or one of the special keys if a hex character is needed.
Enter the number of history records you wish to delete, and press [#/Enter]. The previous menu appears. Default EE ! Warning! Lost programming! All programming, including zone configurations and option installations, are lost when this op- eration is performed.
PROGRAM MUX 1- MUX EDIT 2- MUX PROGRAM 3- BUS TYPE 4- AUTO PROGRAM MUX Edit Shortcut: 0- PROG , 9- PROGRAM MUX , 1- MUX EDIT To add MUX devices to the system, use the MUX Edit option. Each device must have a unique address programmed using the address switches.
If no devices are connected on Bus A, the following window appears. Otherwise an error message appears. PROGRAM MUX 1- NORMAL 2- FAST Select normal programming to add one or two devices. Select fast programming to program larger quantities of identical devices to sequential addresses.
If a device is defective or not connected properly, the control panel shows: ERROR - DEVICE FAILED Fast Programming Fast programming proceeds the same as normal programming, except that when the devic.
Figure 8.1: D7039 Mounting Location 1 D7039 MUX Expansion module 5 Addresses 9 to 128 2 Enclosure 6 MUX Class A 3 FPD‑7024 Control board 7 Addresses 129 - 255 4 I/O module for the D7039 MUX Expansio.
When the scanning is completed, the FPD‑7024 checks for missing devices. Missing devices are addresses with no devices on the multiplex buses, but are programmed into the FPD‑7024’s site-specific memory area.
NEW DEVICE @ xxx 2 – SINGLE INPUT 3 – I/O MODULE 4 – MUX SMOKE 5 – SMOKE W/FRZ 6 - DUAL INPUT 7 - OCTAL INPUT 0 – NO DEVICE Use this menu to define the device type. Press the number key that corresponds with the device type installed at the address.
3 Point is at an illegal address The addresses at which multi-address devices can be installed are restricted. 4 Too many multiplex relays Only 20 input output devices can be supported on a given bus.
PROGRAM MUX 1- MUX EDIT 2- MUX PROGRAM 3- BUS TYPE 4- AUTO PROGRAM From the Program MUX menu, press [1] to select MUX Edit. The following window appears: DEVICE TYPE ( ) 0- NO DEVICE 2- SINGLE INPUT 3.
Specifications i Notice! When a local relay is programmed for trouble it is energized in the normal state. This causes the common and normally-open terminals to be shorted when not in the trouble condition. Electrical Power (Input): 120 V 60 Hz or 220 V 50 Hz, 2.
Appendices Appendix A: Abbreviations on Control Panel Display Abbreviation Definition Abbreviation Definition 3/1 3/1 Tone Burst (reporting format) KPAD, KYPAD, KYPD Keypad 4/2 4/2 Tone Burst (reporti.
Abbreviation Definition Abbreviation Definition FRQNCY, FREQ, FREQUENCY Frequency SYS, SYSTM System FUNC Function T, TRBL, TRB, TROUB Trouble GRND Ground TST Test HI High VER Version HSTRY History W, WFLW, WTF Waterflow INIT Initialize ZN, ZON Zone IP Internet Protocol address Table 10.
FPD-7024 Panel Display Message Panel Display Message Definition SYSTEM TROUBLE General trouble message. Refer to second line of the display for more information. TRBL OPEN LNAC A Local NAC circuit is open. Check the field wiring and the EOL resistor. TRBL OPEN RNAC An FPD‑7038 Remote NAC circuit is open.
Appendix C: Reporting Summary for Fire Communicator i Notice! For information about the receiver output when the Modem IIIa 2 reporting format is used with a Bosch Security Systems, Inc.
Report Index Default Values Alternate Default 3/1 BFSK SIA Contact ID 4/2 digit 1 4/2 digit 2 4/2 digit 1 4/2 digit 2 POINT SUPERVISORY DISABLE 14 see #12 p see #12 p see #12 Fz FBz 1 571 00 zzz POINT.
Report Index Default Values Alternate Default 3/1 BFSK SIA Contact ID 4/2 digit 1 4/2 digit 2 4/2 digit 1 4/2 digit 2 SYSTEM IN TEST RESTORE 41 E 1 3 7 E ED TE0 3 607 00 000 SILENCE 42 9 F 9 F 9 FD KB.
Report Index Default Values Alternate Default 3/1 BFSK SIA Contact ID 4/2 digit 1 4/2 digit 2 4/2 digit 1 4/2 digit 2 EEPROM FAILURE 60 see #56 see #56 see #56 see #56 see #56 FD UT18 1 307 00 018 EEP.
Report Index Receiver output POINT SUPERVISORY TROUBLE 6 dd/dd tt:tt ql ACCT aaaa FIRE TROUBLE +++ ACCT aaaa AREA=1 POINT=zzz POINT MONITOR TROUBLE 7 dd/dd tt:tt ql ACCT aaaa FIRE TROUBLE +++ ACCT aaa.
Report Index Receiver output POINT WATERFLOW DIRTY RESTORE 25 dd/dd tt:tt ql ACCT aaaa ANALOG RESTORE +++ ACCT aaaa AREA=1 POINT=zzz POINT SUPERVISO Y DIRTY RESTORE 26 dd/dd tt:tt ql ACCT aaaa ANALOG .
Report Index Receiver output PHONE 2 RESTORE 55 dd/dd tt:tt ql ACCT aaaa PHONE RESTORAL +++ ACCT aaaa PHONE LINE=2 SYSTEM TROUBLE 56 dd/dd tt:tt ql ACCT aaaa EQUIPMENT FAIL +++ ACCT aaaa SDI=001 COND=.
Condition System event Condition System event Option bus device at address 7 failed 8 Remote NAC module 1, output 2 wiring fault 58 Option bus device at address 8 failed 9 Remote NAC module 1, output .
Condition System event Condition System event NAC 2 shorted wiring 29 Remote NAC module 1, output 3 disabled by user 79 Remote NAC module 1 ground fault- short 30 Remote NAC module 1, output 4 disable.
PROG TIME SYSTEM: Last date in EE 0000 AUTO TEST TEST TIME: 0200 TEST FREQ: 3 hr to 24 hr DAYLIGHT SAV: 2- enable SECURITY PINS PROGRAMMER: 9876 USERS: User 1 = 1234 User 2 = 0000 AUTHORITY USER 1: 2 OTHERS: 0 PROG SYSTEM TIMERS SMOKE RESET: 6 sec AC FAIL DELAY: 6 hr AUTO SILENCE: 0 min DISPLAY RATE: 4x.
Point Function 4 = 4 Point Function 5 = 5 Point Function 6 = 6 Point Function 7 = 7 Point Function 8 = 8 Point Function 9 - 255 = 10 ALARM/TROUBLE: Trouble On Open OUTPUT ZONE Point Zone 1 = 1 Point Z.
NACs Zone D: 0 NAC #2: CONFIGURATION: Steady ZONE ASSIGNS: Zone A: 53 Zone B: 61 Zone C: 0 Zone D: 0 RNACs RNAC 1 Outputs 1, 2, 3, 4 Configuration: Steady Zone Assignment: Zone A: 53 Zone B: 0 Zone C:.
RNACs Zone D: 0 RNAC 3 Outputs 1, 2, 3, 4 Configuration: Steady Zone Assignment Zone A: 53 Zone B: 0 Zone C: 0 Zone D: 0 RELAYS LOCAL: RELAY #1 Zone A: 63 Zone B: 0 Zone C: 0 Zone D: 0 RELAY #2 Zone A.
REMOTE Relay 5 / Zone A: 58 Relay 6 / Zone A: 57 Relay 7 / Zone A: 56 Relay 8 / Zone A: 53 REMOTE 2 Relay 1 / Zone A: 1 Relay 2 / Zone A: 2 Relay 3 / Zone A: 3 Relay 4 / Zone A: 4 Relay 5 / Zone A: 5 .
PROG FORMATS 4/2 ZONE REPORT 0 - FIRE ALRM D1: 0 1 - FIRE RSTR D1: 3 2 - WATERFLOW D1: 0 3 - SUPERVISE D1: 0 4 - TROUBLE D1: 6 5 - TRBL RSTR D1: 3 6 - DISABLE D1: B 7 - DSBL RSTR D1: 3 8 - MORE 1 - PO.
ALT 4/2 CODES TEST REPORT: 30 OFF NORM TST: 33 PHONE 1 TRBL: 31 PN 1 TRB RST: 35 PHONE 2 TRBL 32 PN 2 TRB RST: 36 SYSTEM TROUB: 33 SYS TRB RST: 37 BFSK RPT CDS OFF NRM TST: FD OPEN/RESET: FD SILENCE: .
4/2 POINT REPORTS POINT 6 D2: 6 POINT 7 D2: 7 POINT 8 D2: 8 POINT 9 D2: 9 POINT 10 D2: 0 4/2 RPT CODS SYSTM IN TST: 33 SYS TEST RST: 37 SILENCE: 9F FIRE DRILL: 33 FIRE DRL RST: 37 OPEN RST RPT: 9F LOW.
Other communications problems that can cause this condition include: 1. Events occurring faster than the dialer can send them, which overflows the 32 event buffer, 2. Programming errors such as missing phone numbers or account codes, over 100 Trouble reports in 24 hours, or 3.
.
.
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY, 14450 USA www.boschsecurity.com © Bosch Security Systems, Inc., 2012.
デバイスBosch Appliances FPD-7024の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bosch Appliances FPD-7024をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBosch Appliances FPD-7024の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bosch Appliances FPD-7024の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bosch Appliances FPD-7024で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bosch Appliances FPD-7024を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBosch Appliances FPD-7024の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bosch Appliances FPD-7024に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBosch Appliances FPD-7024デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。