MODEL SC6120B—USER’S MANUAL AC POWERED SMOKE AND CARBON MONOXIDE ALARM WITH BA TTER Y BACK-UP AND SILENCE FEA TURE M06-1059-001 1/02 PLEASE READ CAREFULL Y AND SA VE: This unit was shipped with a user’ s manual that contains important information about its operation.
T ABLE OF CONTENTS Chapter 1: Introduction . . . . . . . . . . .Inside Cover Basic Features . . . . . . . . . . . . . . . . .Front Cover Basic Safety Information . . . . . . . . .Inside Cover Smoke/CO Alarm Specifications . . . . . . . . . . . .2 How Y our Smoke/CO Alarm W orks .
1 Basic safety information (continued)... Installation of this unit must conform to the elec- trical codes in your area; Article 760 of NFP A 70 (NEC), NFP A 72, NFP A 101; SBC (SBCCI); UBC (ICBO); NBC (BOCA); OTFDC (CABO), and any other local or building codes that may apply .
2 Basic safety information (continued)... T est this Smoke/CO Alarm once a week. If it ever fails to test correctly , have it replaced immediately! If the Alarm is not working properly , it cannot alert you to a problem. Do not paint over the Smoke/CO Alarm.
3 Specifications (continued)... Standards: Underwriters Laboratories Inc. Single and Multiple Station Carbon Monoxide Alarms UL2034. According to Underwriters Laboratories Inc.
4 In general, install combination Smoke and Carbon Monoxide Alarms: • On every level of your home, including finished attics and basements. • Inside every bedroom, especially if people sleep with the door partly or completely closed. • In the hall near every sleeping area.
5 Installing Smoke/CO Alarms in Mobile Homes For minimum security install one Smoke/CO Alarm as close to each sleeping area as possible. For more security , put one unit in each room. Many older mobile homes (especially those built before 1978) have little or no insula- tion.
6 A VOIDING DEAD AIR SP ACES “ Dead air ” spaces may prevent smoke fr om reaching the Smoke/CO Alarm. T o avoid dead air spaces, fol- low installation recommendations: On ceilings, install Smoke/CO Alarms as close to the center of the ceiling as possible.
7 IMPORT ANT INST ALLA TION P ARTS The Mounting Bracket: T o remove the mounting bracket from the Smoke/CO Alarm base, hold the alarm base firmly and twist the mounting bracket off. The mounting bracket installs onto the junction box. It has a vari- ety of screw slots to fit most boxes.
8 TO LOCK THE BA TTER Y COMP ARTMENT This step should not be done until installation is complete and AC power can be turned on as soon as possible to conserve battery power . Activate the battery and test the battery back-up before locking the battery compartment.
9 Unlock the Battery Compartment (continued)... 5. Reconnect the power connector to the back of the Alarm, reattach the Alarm to the mounting bracket, and restore the power as soon as possible to conserve battery power . When replacing the battery , always test the Alarm after relocking the battery compartment.
10 HOW TO INST ALL THIS ALARM This unit is designed to be mounted on an standard wiring junction box up to a 4-inch size on either the ceiling or wall. Read “ Where to Install Alarms ” and Where Not to Install Alarms ” befor e you begin installa- tion.
11 Installing a Single (Stand-Alone) Alarm (continued)... ELECTRICAL SHOCK HAZARD. Do not restore power until all Alarms are completely installed. Restoring power before installation is complete may result in serious electrical shock, injury or death.
12 Interconnecting Multiple Alarms (continued)... • The total length of wire inter connecting the units should be less than 1000 feet (300 meters). The interconnect wire should be #18 gauge or lar ger , rated at least 300V . • If an interconnect wir e is not already part of your household wiring, you will need to install one.
13 Interconnecting Multiple Alarms (continued)... 7. T est each Alarm. Press and hold the test button until the unit alarms. When testing a series of interconnected units you must test each unit individually . Make sure all units alarm when each one is tested.
14 CHAPTER 3: IF YOUR SMOKE/CO ALARM SOUNDS WHA T TO DO FIRST – IDENTIFY THE TYPE OF ALARM T ype of Alarm What Y ou See and Hear Carbon Monoxide CO Light: (CO) Flashing RED Horn: 4 beeps, pause, 4 b.
15 WHA T TO DO IF SMOKE IS DETECTED RESPONDING TO AN ALARM • Don ’ t panic; stay calm. Follow your family escape plan. Y our safe escape may depend on thinking clearly and remembering what you have prac- ticed. Get out of the house as quickly as possible.
16 The Silence Feature is intended to temporarily silence the horn while you identify and correct the problem. Do not use the Silence Feature in emer gency situations. It will not correct a CO problem or extinguish a fir e. T o use the Silence Feature, briefly press the T est/Silence button on the cover of the Smoke/CO Alarm.
17 The Latching Alarm Indicator is activated after an Alarm is exposed to alarm levels of smoke or carbon monoxide. After smoke or CO levels drop below alarm levels, the red smoke or CO LED will begin to flash once every 5 seconds. For example, if CO initiated the alarm, the red “ CO ” LED will flash.
18 CHAPTER 4: TESTING AND MAINTENANCE WEEKL Y TESTING • SMOKE ALARM: NEVER use an open flame of any kind to test the Smoke Alarm. Y ou might accidentally damage or set fire to the unit or to your home. The built-in test switch accurately tests the unit ’ s operation as required by Underwriters Laboratories, Inc.
19 REGULAR MAINTENANCE This unit has been designed to be as maintenance- free as possible, but there ar e a few simple things you must do to keep it working properly: • T est it at least once a week. • Gently vacuum off any dust on the cover at least once a month using your vacuum ’ s soft brush attachment.
20 CHAPTER 5: PROTECTING YOUR F AMIL Y FROM CO POISONING A CO Alarm is an excellent means of protection. It monitors the air and sounds a loud alarm before carbon monoxide levels become threatening for average, healthy adults. A CO Alarm is not a substitute for proper maintenance of home appliances.
21 • Keep at least one working fire extinguisher on every floor , and an additional one in the kitchen. Have fire escape ladders or other reliable means of escape from an upper floor in case the stairs are blocked. • Follow safety rules, and prevent hazardous situations: 1) Use smoking materials properly .
22 WHA T IS CO? CO is an invisible, odorless, tasteless gas produced when fossil fuels do not burn completely , or are exposed to heat (usually fire). Electrical appliances typically do not produce CO. These fuels include : W ood, coal, charcoal, oil, natural gas, gasoline, kerosene, and propane.
23 1. Excessive spillage or reverse venting of fuel appli- ances caused by outdoor conditions such as: • Wind direction and/or velocity , including high, gusty winds. Heavy air in the vent pipes (cold/humid air with extended periods between cycles).
24 Why is this important? Because you need to be warned of a potential CO problem while you can still react in time. In many reported cases of CO exposur e, victims may be aware that they are not feeling well, but become disoriented and can no longer react well enough to exit the building or get help.
25 SPECIAL COMPLIANCE CONSIDERA TIONS This unit alone is not a suitable substitute for com- plete fire detection systems in places housing many people — like apartment buildings, condo- miniums, hot.
26 DIFFERENT TYPES OF SMOKE ALARMS Battery operated units: Provide protection even when electricity fails, provided the batteries are fr esh and correctly installed. Units are easy to install, and do not require pr ofessional installation. AC powered units: Can be interconnected so if one unit senses smoke, all units alarm.
Once a minute, the alarm sounds 3 quick “ chirps ” , and the green light flashes quickly three times. Unit malfunction. Unit needs to be replaced. Based on self-diagnostic tests, the unit has detected a fault. Units under warranty should be returned to manufacturer for replacement.
28 CHAPTER 10: UNDERST ANDING THE LIGHT AND HORN P A TTERNS Condition LED (Red or Green Lights) Horn POWER UP Green LED flashes ON once, then shines continuously Horn “ chirps ” once DURING TESTIN.
29 CHAPTER 11: GENERAL LIMIT A TIONS OF THIS ALARM This Smoke/CO Alarm will not work without power . This alarm requires AC power or a 9V alkaline or lithium battery to operate. This Smoke/CO Alarm will not sense smoke or CO that does not reach the sensors.
30 LIMITED W ARRANTY Coverage: BRK Brands, Inc. ("BRK") the maker of BRK Electronics ® brand prod- ucts, warrants that for a period of 5 years from the date of purchase, this pr oduct will be free from defects in material and workmanship.
デバイスBRK electronic SC6120Bの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
BRK electronic SC6120Bをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBRK electronic SC6120Bの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。BRK electronic SC6120Bの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。BRK electronic SC6120Bで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
BRK electronic SC6120Bを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBRK electronic SC6120Bの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、BRK electronic SC6120Bに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBRK electronic SC6120Bデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。