38AN,BK with 40QN009,012 Cooling Only/Heat Pump Systems Installation, Start-Up an Service Instructions (For Use in High Wall Applications) CONTENTS Page SAFETY CONSIDERATIONS ................... 1 GENERAL .................................. 1,2 INSTALLATION .
combinations, and Table 2 for application range. Refer to this manual for proper installation of the complete system. Refer to Table 1 to make sure the correct indoor unit is in- stalled with the correct outdoor unit. Be sure the unit will be operated within the application guidelines shown in Table 2.
m 8 "....._ + 36" *A clearance of 31,_" is the absolute minimum. A clearance of 10" is recommended. NOTE: Remove unit front cover for control box access. Fig. 2 -- Minimum Required Fan Coil Unit Clearances 4. Select walls that are: a.
Table 4A-- Physical Data, 38AN Cooling Only Condensing Units* UNIT 38AN NOMINAL CAPACITY (Tons) OPERATING WEIGHT (Ib) REFRIGERANT TYPE Control (Cooling) Factory Charge (Ib) COMPRESSOR TYPE Model Oil (Recharge) (oz) Crankcase Heater Accumulator OUTDOOR FAN Rpm Diameter (in.
Table 4C -- Physical Data, 38BK009,012 Outdoor Heat Pump Units* UNIT 38BK NOMINAL CAPACITY (Tons) OPERATING WEIGHT (Ib) REFRIGERANT TYPE Control (Cooling) Control (Heating) Factory Charge (Ib) COMPRESSOR TYPE Model Oil (Recharge) (oz) CRANKCASE HEATER (Watts) OUTDOOR FAN Rpm Diameter (in,),.
Table 4D -- Physical Data, 40QNEIH Heat Pump High Wall Units UNIT NOMINAL CAPACITY (Tons) NOMINAL SIZE (Btuh) OPERATING WEIGHT (Ih) MOISTURE REMOVAL RATE (Pints/hr) REFRIGERANT Control (Cooling) Control (Heating) Factory Charge (Ib)t INDOOR FAN RpndCfm High Rpm/Cfm Medium RpndCfm Low Motor Watts Blowers Quantity.
2'_0" [6103 - 19 u 2 O" C6101 , 1 7/8"- [2513 °..5 o._s ciso, l' i I I,,', i-- --* _ ' _ _ "_q _ _ ._ - , TOP VIEW 2"_2 o HIGH VOLTA_I_ TO _1 INDOOR _ECT]ON _! I 1/8" Dik.
MINIMUM CLEARANCE FOR SERVICE I_T A]R ! I I I I I I I_] DU_ (NOTE 3) NOTES: 1, Dimensionsare in inches. Dimensions in [ ] are in millimeters, 2. _ Diroction of airflow. 3. _erant, d_in, Bnd power conneofions ruby be _de rear, left side or right side. 4.
Table 5 -- System Piston Guide and Refrigerant Charges UNIT INDOOR PISTON Indoor Outdoor SIZE 40QNB009 38AN009 Capillary Tube 40QNB012 38AN012 Capillary Tube 40QNEO09 38BK009 321" 40QNH012 38BK012 421" OUTDOOR PISTON SIZE Capillary Tube Capillary Tube 30t 42"_ REQUIRED SYSTEM CHARGE (Ib)* 1.
FAN COIL 0 o2-P, UNIT / SCREW NOTE: Use either point "A" or point "B." J _2 W_TYP DIA Fig. 8 -- Wall Hole Location For Fan Coil Unit Rear Piping (Size 009 Shown) -." i ": (INDOORSIDE) I " WALL . I (OUTDOOR SIDE) NOTE:Slope condensate lineat a minimum pitchof % in.
2. Connect piping to the indoor section: a. Shape tube with a tube bender so that the tube ends coincide with flare connections. b. Carefully remove the flare nut fitting from the indoor seetinn tubing. c. Thoroughly clean all tubing connection points to pre- vent foreign matter from entering the refrigerant circuit.
INCORRECT 6 6 b INCORRECT INCORRECT CORRECT P, 6 6 _WALL UNIT DRAIN "_-_'-" PIPING Fig. 10 -- Fan Coil Unit Drainage System (Rear Piping Shown) Table 7 -- Electrical Data UNiT Outdoor S.
outdoor unit. For installation simplicity, the field- supplied conductor should be black, white, and bare cop- per for009 applications and black, red, and bare copper for012 applications. 6. Wire the outdoor units as follows: • Cooling-Only, Size 009 Systems: Connect the 2 black leads to terminal block location L.
START-UP Complete the following checks and the Start-Up Check- list on pages CL-1 and CL-2 before system start-up. 1. Check condensate drainage system. Refer to Fig. 4 and 10. Add water to check the drainage flow. If water does not flow steadily, check the pipe slope or see if there are any restrictions.
o_ o 2S _ -,_ III m ON/OFF'"---" BUTTON Fig. 14 -- Remote Controller START COOL* START COC_.ING. DIRECT LOUVI_RS SO AIR BLOWSSTRAIGHT _ _ OU'T HORIZONTAL DISCHARGE) SWIN G Pd_IGE_'_ is" SWING RANGE HEA'i3 NG - DIRECT LOIJVERS $O AIR BLOWS DOWN VERTICAL _ISCHARGE) HEAT *Potential range.
will stop 30 seconds after the compressor stops. After 3 minutes, the indoor fan runs at ultra-low speed for 30 seconds. The normal dehumidification operation is re- peated forthe newly sensed room temperature.
4O DEFROST REGION THREE (NO DEFROST OPERATION) 3O LU LU Q. LU I-- O o o Q F- 0 2O 10 0 DEFROST REGION TWO (MINIMUM UNIT RUNTIME = 6 HOURS*) -10 -10 0 10 20 ADJUSTS IF LONG DEFROST I (MORE THAN 6 MINUTES) ADJUSTS IF SHORT LESS THAN _ MINUTES) DEFROST REGION ORE (MINIMUM UNIT RUN TIME = 50 MIN.
CLEANING AND MAINTENANCE To avoid the possibility of electric shock, before per- forming any cleaning and maintenance operations al- ways turn off power to the system by pressing the orange ON/OFF button on the remote controller. Turn off the outdoor disconnect switch located near the out- door unit.
To Clean Indoor Unit Front Panel -- If the front panel of the unit becomes dirty or smudged, wipe the out- side of the front panel with a soi_ dry cloth.
SERVICE ry_l 'k'k'k'k'k'k'k'k'kS_.d ;] H ff [_ When servicing unit, turn off all electric power to unit to avoid shock hazard or injury from rotating parts. Do not vent refrigerant to atmosphere when servicing unit.
Table 11 -- 40QN Thermistor Properties* MINIMUM NOMINAL MAXIMUM TEMP MINIMUM NOMINAL MAXIMUM THERMISTOR THERMISTOR THERMISTOR (F) OHMS OHMS OHMS VOLTS -- DC VOLTS -- DC VOLTS -- DC -40 303,300 342,700 356,200 4.80 4.82 4.84 -30 211,500 237,276 265,444 4.
WALL CAP" AIRFLOW WIRELESS CONTROLLER* AIRFLOW WEATHERPROOF FUSED DISCONNECT PER NEC t 2 WIRES (+)GROUND CONNECTION AIRFLOW LEGEND NED -- National Electrical Code "Standard. t Field supplied. NOTES: 1. All piping must follow standard refrigerant techniques.
AGING -- AS C CAP -- CH COMP -- CN EMI FMC FU GND -- HA HS IDC Th -- IFM JEM-A -- K ODA Th -- ODC Th -- OFM -- OL PCB PTC LEGEND AND NOTES FOR FIG. 22-25 For Bum-In Test (short these terminals) RA Th .
38AN009 OUTDOOR SECTION AA Th IDC Th rr_ ( T_N ILU 40QNB009 FAN COIL DISPLAy pCB AS ] 1_ CNIO CNI1 JEH-A rTT'JTT_ CNI0 CNI i CN12 Ct_18 TI_-e AGING _-iO_t T P1 P2 CONTROL PCB A55"Y 'rl_ D $CO_q_C T $ .s-,-_o : : . _J i -..--7.. - ...-_ -- -- - ]""-"_ u Lmff " .
38AN012 OUTDOOR SECTION RA Th 40QN B012 FAN COIL CONTROL FI'_ IFII TB Fig. 23 -- 38AN012 with 40QNB012 Cooling Only System Wiring Diagram 25.
38BK009 OUTDOOR SECTION 40QNE009 FAN COIL ODC Th OOATh T1Q iii ii I i II i II i II I i II i I i J i I i I i I I I i I i I i I i I TB2 Fig. 24 -- 38BK009 with 40QNE009 Heat Pump System Wiring Diagram 2.
38BK012 OUTDOOR SECTION _ - - - -- _'_ r_Th 11_ I _ RA Th ,o° T. CONTROL PCB A55" Y I I I T31 M _-__ -__ _E_ E i I ii i I i I iI ii i I i I i I i I i I i I i I i ] i I i I i I Fig.
.
.
Copyright 1999 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
デバイスCarrier 38AN,BKの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Carrier 38AN,BKをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCarrier 38AN,BKの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Carrier 38AN,BKの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Carrier 38AN,BKで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Carrier 38AN,BKを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCarrier 38AN,BKの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Carrier 38AN,BKに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCarrier 38AN,BKデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。