Carrierメーカー50XJ064-104の使用説明書/サービス説明書
ページ先へ移動 of 64
Manufa cturer res erves the right to discon tinue, or chang e at any time , specificat ions or designs witho ut notic e and wit hout inc urring obligati ons.
2 Comf or t Contr oller I/O Module (PCB2) — This input/output module is factory installed in the 50XJ unit and allows additional field points (8 inputs and 8 outputs): VFD (variable frequency dri ve) Bypass, V A V T erm inals Control, Building V e ntilation, and Heating Interl ock.
3 Table 1 — Control Inputs and Outputs LEGEN D DESCRIPTION ABBREV . TYPE CONTROLLER I/O NO . DIP SWITCH SETTINGS Water Econ. Units Air Econ.Un its Switch N o.
4 Carrier Comfort Netw ork Interface — The 50BV , XJ units can be connected to the CCN (C arrier Comfort Network) if desired. System el ements are connec ted to the com munica- tion bus in a daisy chain arrangeme nt.
5 Dependencies — W ater Econom izer option is enabled, and Fan is On, and Inle t W ater T e mperature is below set poi nt; or from “Remote Scheduler,” or from “Remote Linkage.” Economizer mode i s switched to Off or no start if: there is no condenser waterflow , F ire Input is On, Fan is not On, or Un- occupied mode is On.
6 by the freeze condition. Unit reset is automatic when t he contacts on t he freeze protect ion switch c lose again. T he contacts on the freez e protection sw itch open below 37 F . TO WER SUMP TEMPERA TURE SENSOR (50XJ PC B 3) — This sensor is used for moni t oring (only) the tower sump temperat ure.
7 AIR TERMINALS AND FRESH AIR DAMP ER (50XJ PC B 2 ) — The V A V T erminal Open (TRMOP), V entilation Output (VENTR), V A V T erminals Control ( TRMCT), and Heat Interlock Relay (HIR) terminals prov.
8 CONTROLS AND FUNCTIONS Usin g the Local In terface Displa y — The Local Interface De vice (LID) is a CCN operator interface tha t gives the user the capability to view and modify all configuration and service data for the C C6400 control system. The LID also allows the user to override all point display and maintenance data.
9 • Pres sing the appr opriate LID numeri c key (i.e., 2) and the appropriate function key (i .e., ) to directly access an item without having to scroll through all the items in that category .
10 Table 6 — Quick Access Chart LEGEND NOT ES: 1. T o ch ange from Edit m ode to S tatus m ode, press o r press again. 2. Not all availab le se lections will have items to select in su ble vels. A utomatic Run T est — The 50BV ,XJ unit controls are programmed with an automat ic run test that checks conne ction and operation of major components.
11 2. Press 3 and then . The LID display will show: Controller Password 3. Press . The LID display w ill show: L o gi nt oC o n t r o l l e r Enter Passw ord NOTE: The LID display has two modes: Edit mode and Status/Maintenance mode. If the LID display is in Edit mode, then the di splay will onl y show the word “pass- word.
12 22. The control forces CMP4 (compressor 4) on, if config- ured, then waits 5 sec onds. The LID display shows: Factory/F ield T est Sto p The yellow LED will go off, and the red LED will go off. 23. The control forces CMP4 off. 24. The r un tes t is c omplet e.
13 8. Enter the la st two digits of the current year . Press then press . The LID display will show: Update Clock No 9. Press 1 and then to cause the controller to update the clock. The LID display wi ll flash. Press twice to view the default display and the clock should update to the input time and date.
14 Table 7 — Controller S et Points LEGEN D Chec k System P arameter s — T o check s ystem parameters, press the button. The LID display will show: “Hardware Points T abl e 1.” Press to view the hardware points. The user can navigate up and down through the points with the up and down arrows.
15 Table 8 — Controller Hardware Points Table 9 — Software Points Table 10 — Configura tion Parameters LEGEND Set Contr oller Addr ess — T o set the address of the OMNIZONE ™ System Control panel c ontroller , pe rform the following procedur e: 1.
16 OPERA TION Occupancy Determination — The O MNIZONE™ controller can determi ne occupancy in many ways. Local occu- pancy is dete rmined by either a local schedule containe d in the CC6400 controller , the use of the ROCC discrete input point or by sett ing the L ocal/O ff/Remot e switc h to Local .
17 COMRES triggers the compressor staging routine that controls the number of compressors energized. Units are equipped with 4 compressors piped in s eparate refrigerant circuits, and staged On/Off in a fixed sequenti al manner (compressor no. 1 through compressor no.
18 Units not equipped with a water economizer ca n be ordered with the r everse/hea d pressure control valve fact ory install ed and a pressure transduce r located in t he discharge line of compressor no.
19 LOW -PRESSURE SWITCH ( LPS) — T h e L o w - P r e s s u re Switch is loca ted i n the sucti on refrige rant line of each compressor , and is set to open a t pressures below 27 psig. It is wired in the 1 15 va c control power line of the compressor contactor (in seri es with the HPS and EFS), and activates the COL board (above) when it opens.
20 S T A T U S M O N I T O R M O D E — In Status M onitor mode, it i s possible to monitor t he VFD status (freque ncy comman d, output voltage, c urrent, ter minal info rmatio n, etc.
21 T a b l e1 3—V F DT r i pM e s s a g e sf o r5 0 X JU n i t LEGEND LED MES SA GE EXPLA NA TION nErr Displa yed in the trip history in standard monitor mode when no trip has been recorded since the last VFD reset or t rip clear .
22 Table 14 — VFD Mode Summary for 50XJ Unit 50BV V ariable F requenc y Drive Contr ol — The variable frequency drive is factory wired and program med for proper operation with the unit controls; no installation or service adjustments are normal ly required.
23 ECN lamp Lights when ene rgy-sa ving m ode is in operation . RUN ke y l a mp Lights w hen the RUN ke y i s enab led. RUN k ey Pressing th i s key whil e the RUN key lam p is lig hted starts operat i ons. RUN l a mp Lights w hen the in verter is operat i ng.
24 Table 15 — Non-Trip Messa ges for the 50BV VFD NO TES: 1. ST : T er minal of stand by function. 2. When the ON/OFF function is selected f or DC braking (DB), using the input terminal selection par ameter , you can judge the in ver ter to be normal if “db” disappears when opening the circuit betw een the terminal and CC.
25 Table 16 — Tr ip Messages fo r 50BV VFD (cont) ERROR CODE COMMUNICA TION NO . PROB LEM POSSIB LE CAUSES REMEDI ES OP3 C Overvoltage during constant-speed operation • The input voltage fluctuates abnor mally . (1) The power supply has a c apacity of 200kV A or m ore.
26 Table 16 — Tr ip Messages fo r 50BV VFD (cont) *With a parameter, y ou c an choose between tr ip-on and -off. NO TES: 1. During operation, the f ollowing alarms may be displa yed, which ha ve the same m eaning as pre v iously defined alarms.
27 TROUBLESHOOTING Refer to T abl es 17-21 for troubleshooting information. Run T est T roub leshooting — The automatic run test is a diagnostic tool used during unit start-up. T able 17 describes troubleshooting specifically for the automated run test .
28 Table 20 — Alarms Displayed at Unit LID NO TES: 1. Unit display will indicate alar m by displa ying “There is 1 Alar m” or “There are X alarms”, for the activ e alar ms in the controller . 2. Red light on, indicating alar m . 3. Y ellow light is on, indicating a warning.
29 Table 21 — Compressor MUX Board Voltages CO N D EN S E R W A T ER F L O W — This is an optional switch tha t can be used with t he OMNIZO NE™ cont roller .
30 APPENDIX A — WIRING DIA GRAMS 50BVJ,K Low Voltage Schemat ic TRANS-1 (24V AC) CBR 1 2 16 3 14 13 12 15 5 4 6 7 10 9 8 11 2 1 3 5 1 2 4 3 8 6 7 10 9 13 12 11 14 15 16 ALARM RED +- + WARN - - IN OU.
31 NOTES: SEE W/D NUMBER CNTL0038A-EM FOR PCB1 LOW VOL T AGE WIRING. SEE W/D NUMBER CNTL0038B FOR PCB2 LOW VOL T AGE WIRING. SEE W/D NUMBER CNTL0038D FOR LEGEND.
32 TRANS-1 (24V AC) CBR 1 2 16 3 14 13 12 15 5 4 6 7 10 9 8 11 2 1 3 5 1 2 4 3 8 6 7 10 9 13 12 11 14 15 16 ALARM RED +- + WARN - - IN OUT SPEED SF 5 3 BYP AS SF + - CMP4 + - 2 1 3 CLO4 LOGIC CLO3 LOG.
33 NOTES: SEE W/D NUMBER CNTL0038A-MA FOR PCB1 LOW VOL T AGE WIRING. SEE W/D NUMBER CNTL0038B FOR PCB2 LOW VOL T AGE WIRING. SEE W/D NUMBER CNTL0038D FOR LEGEND.
34 TRANS-2 (24V AC) CBR 1 2 16 3 14 13 12 15 5 4 6 7 10 9 8 11 2 1 3 5 1 2 4 3 8 6 7 10 9 13 12 11 14 15 16 17 18 MA_RA FL TS 3 5 TRMOP COMMON TB 2 31 TO PCB1 (J7) J7 J3 J4 J1 PCB2 12345678 SW1 123456.
35 TRANS-1 (24V AC) CBR 1 2 16 3 14 13 12 15 5 4 6 7 10 9 8 11 2 1 3 5 1 2 4 3 8 6 7 10 9 13 12 11 14 15 16 ALARM RED +- + WARN - - IN OUT SPEED VIA CC P24 CC S1 R SF 5 3 BYP AS VFD1 SF + - CMP1 CLO1 .
36 TRANS-1 (24V AC) CBR 1 2 16 3 14 13 12 15 5 4 6 7 10 9 8 11 2 1 3 5 1 2 4 3 8 6 7 10 9 13 12 11 14 15 16 ALARM RED +- + WARN - - IN OUT SPEED VIA CC P24 CC S1 R SF 5 3 BYP AS VFD1 SF + - CMP4 + - 2.
37 LEGEND AND NO TES FOR ALL 5 0BV WIRING DIA GRAMS LEGEND ALARM — Unit Alarm Relay (Critical Faul t) ALM-CM — Alar m/Warning Relay Common AO — Analog Output AQ UA — Aquastat BM — Blower Mot.
38 3 4 2 1 C V S HIR ROCC ALM-CM - + 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 - IN OUT - + + 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 1 2 3 3 LOGIC 1 2 3 LOGIC 1 2 3 LOGIC 1 2 3 LOGIC 1 2 LOW VOL T .
39 9 10 T1 T2 M1 M2 OLR2 T1 T2 M1 M2 OLR1 H1 X2 X1 H2 H3 H4 11 5 V T4 300 BLK 302 WHT 301 BLK TB3 N TB2 11 5 V 310 BLK 31 1 BLK CMP1 HRN1 306 BLK 308 WHT 320 WHT HRN1 HRN1 309 WHT 307 BLK 312 BLU LPS1.
40 GND S T R U W V VFD IFM 107 BLK 11 7 BLU 11 2 YEL L2 L3 L1 GND DISC1* USE COPPER SUPPL Y WIRES. TB1 COMP1 COMP2 129 BLK 135 BLU 132 YEL 128 BLK 134 BLU 131 YEL 127 BLK 133 BLU 130 YEL 140 BLK 146 B.
41 1 2 3 J7 PCB2 3 2 1 CB GRN 24 V X2 X1 TRAN GRN 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 PCB3 J3 J4 J2 1 2 3 J7 SW1 12345678 1 0 RED WHT BLK T ower Sump T emp 0 1 HEA T 1 Building Pressure Leavi.
42 LEGEND AND NO TES FOR ALL 50XJ WIRING DIA GRAMS LEGEND ALARM — Unit Alarm Relay (Critical Faul t) ALM-CM — Alar m/Warning Relay Common BPS_S — F an Start/Stop Rela y (VFD Bypass Mod e) BYP AS.
43 APPENDIX B — C ONTROL SCREENS Displa y Screens DESCRIPTION V ALUE UNITS ST A TUS FORCE NAME OMNIZONE::HWP01-32:Hardware points T able 1 Supply Air T emperature 67 dF SA T Duct Static Press ure 0.2 in H2O DSP Comp. St atus MUX 1.86 V olts CSMUX Fire Alarm /Shut Down Enable FSD Cond.
44 Displa y Sc reens (cont) DESCRIPTION V ALUE UNITS ST A T US FORCE NAME OMNIZONE:Custom Configuration Compressor Stages 2 NUM_CMP Reset Ratio 3 dF RSET_RT O CD WF 0 =NO ,1=YES 0 CDFW_SWT ECON 0=NO,1=YES 0 EWT_SN S EWT Reset 0=NO,1=YES 1 EWT_RST MOD .
45 Configurati on Screens *Def ault values from factory . NO T E: See CC6400 Com f or t Controller Overview and Configuration Manual for configuation inf o rmation. DESCRIPTION V ALUE* UNITS NAME OMNIZONE::CC6400:Controller Identification Description: OMNIZONE VP A C DevDesc Location: T est V ers ion 0.
46 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation.
47 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t C ontroller Ov er view and Configuration Manual for configuration i nformat ion. DESCRIPTION V ALUE* UNITS N AME OMNIZONE::PRES: Head Pressure (Comp1) Low Input Endpoint 0.
48 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation.
49 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t C ontroller Ov er view and Configuration Manual for configuration i nformat ion.
50 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation.
51 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t C ontroller Ov er view and Configuration Manual for configuration i nformat ion.
52 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation.
53 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t C ontroller Ov er view and Configuration Manual for configuration i nformat ion.
54 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation.
55 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t C ontroller Ov er view and Configuration Manual for configuration i nformat ion.
56 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation.
57 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t C ontroller Ov er view and Configuration Manual for configuration i nformat ion.
58 Configurati on Screens (cont) *Def ault values from factory . NO T E: See CC6400 Comf or t Co ntroller Ov er view and Configuration Manual for configurat ion inf ormation.
59 Maintenance Screens (cont ) DESCRIPTION V ALUE UNITS ST A TUS FORCE NAM E OMNIZONE::ANCTL01: Supply F an Status Discrete Output P oint Off Control V alue Sensor Group/SPT Sensor 0.
60 Maintenance Screens (cont) DESCRIPTION V ALUE UNITS ST A TUS FORCE NAME OMNIZONE::PRES: Head P ressure(Comp1) System V alue 118.76 PS IG Sysv alue Fo r c e 0F o r c e Status 0 HwStat Alarm Statu s Nor mal AlmStat Sensor V alue 118. 76 PSIG SenV alue Hardware V alue 1.
61 Maintenance Screens (cont ) DESCRIPTION V ALUE UNITS S T A TUS FORCE NAME OMNIZONE::DXV A V01: Com pressor Staging Discrete Output P oint 1 Off V alue Discrete Output P oint 2 Off V alue Discrete O.
62 Maintenance Screens (cont) DESCRIPTION V ALUE UNITS S T A TUS FORCE NAME OMNI ZONE::HCV A V01: AO - Heating V A V 01 Heating Coil V a lve 0 % V alu e F an Status P oint Off Control V alu e Sensor G.
63 Maintenance Screens (cont ) DESCRIPTION V ALUE UNITS ST A TUS FORCE NAME OMNIZONE::LMALM0 1: Supply air Sensor (T ypical Limit Alar m) Monitored Input P oint 66.
Manufa cturer reser ves the right to discon tinue, or change at any time, specificat ions or designs w ithout not ice and without incurrin g obligations.
デバイスCarrier 50XJ064-104の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Carrier 50XJ064-104をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCarrier 50XJ064-104の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Carrier 50XJ064-104の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Carrier 50XJ064-104で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Carrier 50XJ064-104を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCarrier 50XJ064-104の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Carrier 50XJ064-104に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCarrier 50XJ064-104デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。