50ZH024-060 Packaged Heat Pump Units Installation, Start-Up and Service Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS SAFETY CONSIDERATIONS ...................................................
equipment, pay attention to precautions in the literature, tags, and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
Fig. 2—Unit Base Dimensions, 50ZH024-030 UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT CENTER OF GRAVITY IN. (MM) lb kg X Y Z 50ZH024 208/230-1-60 232 106 14.0 (356) 19.0 (483) 12.0 (305) 50ZH030 208/230-1-60, 208/230–3–60 254 116 14.0 (356) 19.0 (483) 12.
Fig. 3—Unit Base Dimensions, 50ZH036–048 UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT CENTER OF GRAVITY IN. (MM) lb kg X Y Z 50ZH036 208/230-1-60, 208/230-3-60, 460–3–60 277 126 14.0 (356) 19.0 (483) 15.0 (381) 50ZH042 208/230-1-60, 208/230-3-60, 460–3–60 295 134 14.
Fig. 4—Unit Base Dimensions, 50ZH060 UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT CENTER OF GRAVITY IN. (MM) lb kg X Y Z 50ZH060 208/230-1-60, 208/230-3-60, 460-3-60 368 167 14.0 (356) 20.0 (508) 16.0 (406) C00158 REQUIRED CLEARANCE FOR OPERA TION AND SERVICING INCHES [mm] CONDENSER .
INSTALL FLANGES FOR DUCTWORK CONNECTIONS (50ZH060 ONLY) The 50ZH060 units are shipped with flanges which must be field-installed on the unit. To install unit flanges: 1. Five pieces of flange are shipped on the return-air opening of the unit. Remove the flanges from the shipping position (See Fig.
Unit removes condensate through a 1 3/64-in. ID hole (using 3/4-in. OD piping or tubing) which is located at the end of the unit. See Fig. 2-4 for location of condensate connection. Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground- level installations.
The field-supplied disconnect may be mounted on the unit over the high-voltage inlet hole. See Fig. 2-4. Operation of unit on improper line voltage constitutes abuse and may cause unit damage that could affect warranty. ROUTING POWER LEADS INTO UNIT Use only copper wire between disconnect and unit.
4. Connect the RED lead to the BLK wire from which the ORG lead was disconnected. Insulate with wirenut from Step 1. 5. Using the wirenut removed from the RED lead, insulate the loose terminal on the ORG lead. 6. Wrap the wirenuts with electrical tape so that the metal terminals cannot be seen.
Step 1—Check for Refrigerant Leaks LOCATE AND REPAIR REFRIGERANT LEAKS AND CHARGE THE UNIT AS FOLLOWS: 1. Using both high- and low-pressure ports, locate leaks and reclaim remaining refrigerant to relieve system pressure. 2. Repair leak following accepted practices.
charts to determine what the suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge.
NOTE: Be sure that all supply- and return-air grilles are open, free from obstructions, and adjusted properly. Disconnect electrical power to the unit and install lockout tag before changing blower speed. Electrical shock can cause serious injury or death.
Table 3—Electrical Data—50ZH UNIT 50ZH SIZE (–SERIES, IF USED) V-PH-HZ VOLTAGE RANGE COMPRESSOR OFM FLA IFM FLA ELECTRIC HEAT SINGLE POINT POWER SUPPLY MIN MAX RLA LRA Nominal KW* FLA MCA FUSE OR CKT BKR MOCP 024–311 208/230–1–60 187 254 11.
NOTE: Some units are equipped with a time-delay relay. On these units, the indoor fan remains on for 30 seconds after G or Y is deenergized. COOLING With the thermostat subbase in the cooling position, the thermostat makes circuit R-O. This energizes the reversing valve solenoid (RVS) and places the unit in standby condition for cooling.
supplemental electric heat. When thermostat is satisfied, contacts open, deenergizing contactor and relay; motors and heaters deen- ergize. The IFM may be controlled by a time-delay relay that keeps the fan on for 30 seconds.
NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract. The ability to properly perform maintenance on this equip- ment requires certain expertise, mechanical skills, tools and equipment.
mild detergent-and-water-solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring or air filter(s). For best results, spray outdoor- coil fins from inside to outside the unit. On units with an outer and inner outdoor coil, be sure to clean between the coils.
Step 6—Electrical Controls and Wiring Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit and install lockout tag. Remove the top panel to locate all the electrical controls and wiring.
Check valves are also located in the liquid lines near the strainers. The Strainers are the larger of the two components. Step 12—High Flow Valves Located on the compressor hot gas and suction tubes are High Flow Valves. Large black plastic caps distinguish these valves with O-rings located inside the caps.
Fig. 24–Typical Heat Pump Operation, Cooling Mode C95044 STRAINER ACCUMULA TOR COMPRESSOR STRAINER LCS OUTDOOR COIL INDOOR COIL A B D C Check V alves A Closed B Open C Closed D Open LEGEND LCS Loss of Charge Switch Acutrol Metering Device Check V alve (Arrow indicates direction of flow) COOLING CYCLE 1.
Fig. 25–50ZH Balance Point Chart C01038 Balance Point Worksheet 0 10000 20000 30000 40000 50000 60000 70000 80000 - 1 0 0 1 02 0 3 04 05 0 6 0 Outdoor Air Temp (Deg F) 024 030 036 042 048 060 Buildi.
Table 8—Troubleshooting—Cooling and Heating SYMPTOM CAUSE REMEDY Compressor and outdoor fan will not start. Power Failure Call power company Loss of Charge Switch open Evaluate unit for possible r.
START-UP CHECKLIST (REMOVE AND STORE IN JOB FILE) I. PRELIMINARY INFORMATION Model No ............................................................................................................................................................. Serial No .
Copyright 2003 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 50zh5si Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 Tab 6 8 PC 101 Catalog No.
デバイスCarrier 50ZH024-060の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Carrier 50ZH024-060をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCarrier 50ZH024-060の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Carrier 50ZH024-060の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Carrier 50ZH024-060で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Carrier 50ZH024-060を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCarrier 50ZH024-060の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Carrier 50ZH024-060に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCarrier 50ZH024-060デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。