Carrierメーカー58ZAVの使用説明書/サービス説明書
ページ先へ移動 of 20
WeatherMaker 8000™ 58ZAV Downflow/Horizontal Induced-Combustion Furnaces Installation, Start-Up, and Operating Instructions Sizes 050—135, Series 140 NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will pre- vent electrostatic discharges from personnel and hand tools which are held during the procedure.
INTRODUCTION The model 58ZAV Series 140 Furnaces are available in sizes 46,000 through 135,000 Btuh input capacities. The design of the downflow/horizontal gas-fired furnace is A.G.A./C.G.A. certified for natural and propane gases and for installation on noncombustible flooring.
Improper installation, adjustment, alteration, service, mainte- nance, or use can cause carbon monoxide poisoning, explo- sion, fire, electrical shock, or other conditions which may cause personal injury, loss of life, or property damage.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices, in addition to that required by the furnace. All fuel-burning equipment must be supplied with air for combus- tion of the fuel.
Step 3—Supply Air Connections DOWNFLOW FURNACES Connect supply-air duct to supply-air opening on furnace. The supply-air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used), when installed on non-combustible material.
to attach any portion of return-air duct. Bypass humidifier connec- tions should be made at ductwork or coil casing sides exterior to furnace. Step 5—Downflow Installation NOTE: This furnace is approved for use on combustible materials or wood flooring.
Fig. 6—Furnace, Plenum, and Subbase Installed on a Combustible Floor A96285 DOWNFLOW SUBBASE SHEET METAL PLENUM FLOOR OPENING FURNACE (OR COIL CASING WHEN USED) COMBUSTIBLE FLOORING Fig.
INSTALL FURNACE 1. Position furnace in desired location. 2. Connect gas supply pipe. See Fig. 8 for typical piping entry. 3. Install field-supplied filter retainers as indicated in Fig. 11 and Table 4 before connecting return-air duct to furnace. 4. Connect supply- and return-air ducts.
Use the proper length of pipes to avoid stress on the gas control manifold. Failure to follow this warning could result in a gas leak, causing fire, explosion, personal injury, or death. Connect the gas pipe to the furnace using a backup wrench to avoid damaging gas controls.
Canadian installations, all electrical connections must be made in accordance with Canadian Electrical Code CSA C22.1, or authori- ties having jurisdiction. NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control status code indicator light will flash rapidly and furnace will not operate.
Fig. 15—Heating and Cooling Application Wiring Diagram A98521 115-V FIELD- SUPPLIED DISCONNECT AUXILIARY J-BOX 24-V TERMINAL BLOCK THREE-WIRE HEATING-ONLY FIVE WIRE NOTE 1 NOTE .
Step 12—Start-up, Adjustment, and Safety Check GENERAL NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control status indicator light will flash rapidly and furnace will not operate. The furnace must have a 115-v power supply properly connected and grounded.
Fig. 17—Furnace Wiring Diagram A98200e PCB BLOWER O FF DE LAY SELECTI O N CH ART 90 SEC 135 SEC 180 SEC 225 SEC GVR H I/L O RELAY SEC-1 SEC- 2 PL1 32 1 6 5 4 987 LED TEST/TW IN BLOWER OFF DELAY G R Y W C HUM HSIR IDR BLWR BLOWER SPEED SELECT FU1 COOL HEAT L2 PL3 PL2 VAC 120 L1 PR1 1 2 1 2 3 PR2 24 VAC-3A FUSE SPARE-2 SPARE-1 EAC-1 EAC-2 C 1.
until the end of the ignition warm up and trial for ignition periods (a total of 24 sec). The blower then comes back on at heating speed. When the W input signal disappears, the control begins the normal inducer post-purge period and the blower changes to cooling speed after a 1-sec delay.
→ Table 7—Model 58ZAV Orifice Size† and Manifold Pressure for Correct Input (Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4 Percent per 1000 Ft Above Sea Level)* ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.
→ Table 7—Model 58ZAV Orifice Size† and Manifold Pressure for Correct Input (Continued) (Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4 percent per 1000 Ft Above Sea Level)* ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics.
EXAMPLE: (0—2000 ft altitude) Btu heating input = Btu/cu ft X cu ft/hr Heating value of gas = 1050 Btu/cu ft Time for 1 revolution of 2-cu ft dial = 82 sec Gas rate = 88 cu ft/hr (from Table 9) Btu .
Recheck temperature rise. It must be within limits specified on unit rating plate. Recommended operation is at midpoint of rise or above. 3. Set thermostat heat anticipator. The thermostat heat anticipation must be set to match the amp draw of the electrical components in the R-W circuit.
デバイスCarrier 58ZAVの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Carrier 58ZAVをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCarrier 58ZAVの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Carrier 58ZAVの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Carrier 58ZAVで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Carrier 58ZAVを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCarrier 58ZAVの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Carrier 58ZAVに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCarrier 58ZAVデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。