CHAPTER Cisco 6100 Series User Guide 3-1 3 Cisco 6100 Ser ies System Cab les This chapter provides Netw ork Equipment Building Systems (NEBS) compliance cabling guidelines, cabling configuration diag.
3 Cisco 6100 Series System Cables 78-6643-01 09/27/99 Cisco 6100 Series User Guide 3-2 T able 3-1 shows an ov erview of the cables used for each Cisco 6100 Series system configuration.
78-6643-01 09/27/99 Cisco 6100 Series System Cables 3 Cisco 6100 Series User Guide 3-3 3.1 NEBS Compliance Cabling Guidelines T o comply with NEBS requirements, ensure that all cables are scre wed in to the backplane and that the Champ connectors are tie wrapped.
3 Cisco 6100 Series System Cables 78-6643-01 09/27/99 Cisco 6100 Series User Guide 3-4 3.2.1 MC to PSC Cab les Y ou can use the following cables when you are cabling the MC to the PSC in a Direct Connect with a PSC configuration: • One-to-one cables—Used to connect the MC to the PSC for systems using dual-port CAP or DMT -2 A TU-C modules.
78-6643-01 09/27/99 Cisco 6100 Series System Cables 3 Cisco 6100 Series User Guide 3-5 Figure 3-2 shows the cabling between the MC and the PSC in which the cables listed in T able 3-2 are used.
3 Cisco 6100 Series System Cables 78-6643-01 09/27/99 Cisco 6100 Series User Guide 3-6 T w o-to-One Cab les Y ou can use two-to-one cables to connect one MC to two PSCs for systems using dual-port or quad-port A TU-C modules. Quad-port A TU-C modules will be av ailable in a future release.
78-6643-01 09/27/99 Cisco 6100 Series System Cables 3 Cisco 6100 Series User Guide 3-7 Figure 3-4 shows the cabling between one MC and tw o PSCs in which the cables listed in T able 3-3 are used.
3 Cisco 6100 Series System Cables 78-6643-01 09/27/99 Cisco 6100 Series User Guide 3-8 3.2.2 PSC to MDF Cab les Y ou can use the following cables to connect the PSC to the MDF in a Direct Connect with a PSC configuration: • One-to-one cables—Used to connect the PSC to the MDF .
78-6643-01 09/27/99 Cisco 6100 Series System Cables 3 Cisco 6100 Series User Guide 3-9 Figure 3-6 shows the cabling between the PSC to the MDF in which the cables listed in T able 3-4 are used.
3 Cisco 6100 Series System Cables 78-6643-01 09/27/99 Cisco 6100 Series User Guide 3-10 Note When you use the two-to-two cable, see T able C-3 on page C-8 for port mapping information.
78-6643-01 09/27/99 Cisco 6100 Series System Cables 3 Cisco 6100 Series User Guide 3-11 Figure 3-9 shows the cabling between the xDSL subscriber line connectors on the PSC and the MDF in which the cables listed in T able 3-5 are used.
3 Cisco 6100 Series System Cables 78-6643-01 09/27/99 Cisco 6100 Series User Guide 3-12 3.3.1 T wo-to-Three Cab les T o associate the MDF wire pairs and the MC modem ports, the two-to-three cable remaps the wire pairs from the MC connectors to the MDF connectors.
78-6643-01 09/27/99 Cisco 6100 Series System Cables 3 Cisco 6100 Series User Guide 3-13 Figure 3-12 shows the cabling between the MC and the MDF in which the cables listed in T able 3-6 are used. Figure 3-12 MC to MDF Cabling Diagram with T w o-to-Three Cables 3.
3 Cisco 6100 Series System Cables 78-6643-01 09/27/99 Cisco 6100 Series User Guide 3-14 Figure 3-13 shows the three-to-three cable. Figure 3-13 Three-to-Three Cable 23648 J40 J41 P5 Slots 7, 8, 21 to .
78-6643-01 09/27/99 Cisco 6100 Series System Cables 3 Cisco 6100 Series User Guide 3-15 Figure 3-14 shows the cabling between the MC and the MDF in which the cables listed in T able 3-7 are used. Figure 3-14 MC to MDF Cabling Diagram with Three-to-Three Cab les 3.
3 Cisco 6100 Series System Cables 78-6643-01 09/27/99 Cisco 6100 Series User Guide 3-16 Figure 3-15 shows the fi ve-to-six cable. Figure 3-15 Five-to-Six Cable Figure 3-16 shows the cabling between the MC and the MDF in which the cables listed in T able 3-8 are used.
78-6643-01 09/27/99 Cisco 6100 Series System Cables 3 Cisco 6100 Series User Guide 3-17 3.4 DOH Configuration Cables In a DOH configuration, use only designated cables to connect the MC, LCC, PSC, and MDF .
3 Cisco 6100 Series System Cables 78-6643-01 09/27/99 Cisco 6100 Series User Guide 3-18 Figure 3-17 shows the cabling connecting the DOH components in which the cables listed in T able 3-9 are used. Figure 3-17 Cabling Components f or a DOH Configuration 3.
78-6643-01 09/27/99 Cisco 6100 Series System Cables 3 Cisco 6100 Series User Guide 3-19 One-to-One Cables Y ou can use one-to-one cables to connect the PSC to the MDF or external v oice equipment.
3 Cisco 6100 Series System Cables 78-6643-01 09/27/99 Cisco 6100 Series User Guide 3-20 Figure 3-20 shows the cabling between the PSC and the e xternal voice equipment in which the cables listed in T able 3-10 are used.
78-6643-01 09/27/99 Cisco 6100 Series System Cables 3 Cisco 6100 Series User Guide 3-21 Figure 3-21 shows the tw o-to-two cable. Figure 3-21 T wo-to-T wo Cable Figure 3-22 shows the cabling between the xDSL subscriber line connectors on the PSC and the MDF in which the cables listed in T able 3-11 are used.
3 Cisco 6100 Series System Cables 78-6643-01 09/27/99 Cisco 6100 Series User Guide 3-22 Figure 3-23 shows the cabling between the v oice lines on the PSC and the voice switching equipment that provides local PO TS service. The cables listed in T able 3-11 are used for the connection.
78-6643-01 09/27/99 Cisco 6100 Series System Cables 3 Cisco 6100 Series User Guide 3-23 3.5.1 Cab ling Diagr ams T wo DS3 system I/O cards are currently av ailable. Figure 3-24 shows the basic cabling of the subtended network configuration with the DS3 system I/O card that is a v ailable from Release 2.
3 Cisco 6100 Series System Cables 78-6643-01 09/27/99 Cisco 6100 Series User Guide 3-24 Figure 3-25 shows the basic cabling of the subtended netw ork configuration with the DS3 system I/O card that is av ailable earlier than Release 2.4.0. Figure 3-25 Basic Cabling f or Subtending Before Release 2.
78-6643-01 09/27/99 Cisco 6100 Series System Cables 3 Cisco 6100 Series User Guide 3-25 3.6 Siecor PO TS Splitter Cables The Siecor ADSL PO TS Splitter Rack-Mount Shelf is compatible with the Cisco 6130. If you use the Siecor PO TS splitter, you need six one-to-one cables to connect the PO TS splitter to the Cisco MC connectors J39 through J44.
3 Cisco 6100 Series System Cables 78-6643-01 09/27/99 Cisco 6100 Series User Guide 3-26.
デバイスCisco Systems 6100の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Cisco Systems 6100をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCisco Systems 6100の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Cisco Systems 6100の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Cisco Systems 6100で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Cisco Systems 6100を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCisco Systems 6100の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Cisco Systems 6100に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCisco Systems 6100デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。