CPG Signals 2519 4 th Ave., P.O. Box 590, Moline, IL 61265 (800) 577-5758 / (309) 7 62-0731 / FAX (309) 762-8215 www.cpglifesafety.com CPG #2561255 Rev.
CPG #2561255 F IRE L ARM 2500 Operating Manual Warranty CPG products are cove red by a limited warranty. See CPG’s warranty statement for more information (document #780-0762 ).
D C B A 5 4 3 2 1 CPG #2561255 F IRE L ARM 2500 Operating Manual i Contents Contents 1 Overview ............................................................................... 1-1 1.1 General de scription ..............................................
Contents CPG #2561255 F IRE L ARM 2500 Operating Manual ii 4.1.1 B1 St robe de vice ......................................................................................................... ............. 4-1 4.1.2 B1 Tem poral pa ttern ...............
E D C B 2 3 4 5 A 1 CPG #2561255 F IRE L ARM 2500 Operating Manual 1-1 1 Overview 1.1 General description The F IRE L ARM 2500 is an economical, conventional Fire Alarm Control Panel (FACP) with an e xtensive list of features.
Contents 1 CPG #2561255 F IRE L ARM 2500 Operating Manual 1-2 1.3 Specifications 1.3.1 Electrical specifications Primary (AC) power: Accessory (battery ) voltage 120VAC, 60 Hz, 1.
E D C B 2 3 4 5 A 1 CPG #2561255 F IRE L ARM 2500 Operating Manual 1-3 • Size 18-½" x 14-¼" x 3-¾" • Finish Red. • Knockouts Combination ½" / ¾", 2 on each side, top and back. • Option Bezel trim for semi-flush mounting.
Contents 1 CPG #2561255 F IRE L ARM 2500 Operating Manual 1-4.
E D C B 3 4 5 A 2 CPG #2561255 F IRE L ARM 2500 Operating Manual 2-1 2 Operation 2.1 Touchpad The touchpad provides user cont rol over the operation of the panel.
1 Contents 2 CPG #2561255 F IRE L ARM 2500 Operating Manual 2-2 Secondary Function Secondary Function Description (DELETE) Deletes the value at the cursor location whe n entering numeric val ues. Num e r i c entry of 1. Num e r i c entry of 2.
E D C B 3 4 5 A 2 CPG #2561255 F IRE L ARM 2500 Operating Manual 2-3 2.3 Normal Standby Condition The AC LED indicator is on with all other LED’s off. The fire alarm system is constantly monito ring all circuits for alarm signals, faults and remote communication.
1 Contents 2 CPG #2561255 F IRE L ARM 2500 Operating Manual 2-4 2.5.3 NAC trouble / silence Notification appliance circuit: An increase of current to approximately 3.5mA when not in alarm or a decrease in current to approximately 1.5mA on the notification applianc e circuit will result in the following: Operation of the bell trouble LED.
E D C B 3 4 5 A 2 CPG #2561255 F IRE L ARM 2500 Operating Manual 2-5 With the exception of the loss of the AC-ON LED and transfe r of the auxiliary trouble relay cont acts, none of the trouble indicators will operate on loss of AC unless an ade quately charged battery i s connected to the proper terminals.
1 Contents 2 CPG #2561255 F IRE L ARM 2500 Operating Manual 2-6.
E D C B 4 5 A 3 CPG #2561255 F IRE L ARM 2500 Operating Manual 3-1 3 Installation 3.1 Safety message to installers People's lives depend on your safe installation of our products. It is important to read, understand, and fo llow all instructions ship ped with this product.
Contents 1 2 3 CPG #2561255 F IRE L ARM 2500 Operating Manual 3-2 3.2.5 Requirements for Centra l Station Fire Alarm Systems • Connect both phone lines t o the optional ZDACT and OPLCD and prog ram the telephone numbers for the reporting station. • Set the AC trouble report delay from 6 to 12 hours.
E D C B 4 5 A 3 CPG #2561255 F IRE L ARM 2500 Operating Manual 3-3 3.4 Wiring Refer to Figures 3-5 through 3-7 for wirin g information. 1. Install all required conduits, external wiring.
Contents 1 2 3 CPG #2561255 F IRE L ARM 2500 Operating Manual 3-4 Table 3-1: Current Requirements. Module/Device Standby mA Alarm mA 2500 with LCD display 2500 without LCD display CAM (Class A module).
E D C B 4 5 A 3 CPG #2561255 F IRE L ARM 2500 Operating Manual 3-5 Figure 3-5. Four-wire detector connections ( St y le B, Class B cuircuit 4-WIRE DETECT ORS N.O . N.O. N.O . ZONE TERMINALS ALL CONT ACTS SHOWN IN NORMAL ST ANDBY CONDITION 290-0007 42 43 OUT IN OUT IN OUT IN EOL RESIST OR 5.
Contents 1 2 3 CPG #2561255 F IRE L ARM 2500 Operating Manual 3-6 PO WER RA TING 120V A C - 60 HZ (2) 12V , 6.5 AH min. batteries are required. Maximum battery charge current: 1A The battery set must be replaced every 4 years or earlier if capacity is excessiv ely reduced.
E D C B 4 5 A 3 CPG #2561255 F IRE L ARM 2500 Operating Manual 3-7 3.8 Notification Appliance Circuits Connections The control panel has two Style Y (Class B) notificati on appliance circuits whi ch can be upgraded to Style Z (class A) by the addition of a model CAM (Class A M odule).
Contents 1 2 3 CPG #2561255 F IRE L ARM 2500 Operating Manual 3-8.
E D C B 5 A 4 CPG #2561255 F IRE L ARM 2500 Operating Manual 4-1 4 Configurati on and Programming 4.1 Selecting connected devi ce options (DIP switches) A series of DIP switches are use d to configure dev ices connected to the fire alarm control panel.
1 2 3 Contents 4 CPG #2561255 F IRE L ARM 2500 Operating Manual 4-2 4.1.3 Reverse polarity circuits configuration This panel is equipped with two pola rity reversal-typ e outputs. This permits alarm and trouble signal s to be transmitted to one location and supervisory and tro uble signals to be transmitted to a secon d location.
E D C B 5 A 4 CPG #2561255 F IRE L ARM 2500 Operating Manual Order of characters ← key key → ! " # $ % & ' ( ) * + , - . / 0 1 2 3 4 5 6 7 8 9 : ; < = > ? ~ A B C D E F.
1 2 3 Contents 4 CPG #2561255 F IRE L ARM 2500 Operating Manual Order of characters ← key key → ! " # $ % & ' ( ) * + , - . / 0 1 2 3 4 5 6 7 8 9 : ; < = > ? ~ A B C D E F G H I J K L M N O P Q R S T U V W X Y Z [ ] ^ _ ' a b c d e f g h i j k l m n o p q r s t u v w x y z { l } ← → (space) 4-4 4.
E D C B 5 A 4 CPG #2561255 F IRE L ARM 2500 Operating Manual Order of characters ← key key → ! " # $ % & ' ( ) * + , - . / 0 1 2 3 4 5 6 7 8 9 : ; < = > ? ~ A B C D E F.
1 2 3 Contents 4 CPG #2561255 F IRE L ARM 2500 Operating Manual Order of characters ← key key → ! " # $ % & ' ( ) * + , - . / 0 1 2 3 4 5 6 7 8 9 : ; < = > ? ~ A B C D E F G H I J K L M N O P Q R S T U V W X Y Z [ ] ^ _ ' a b c d e f g h i j k l m n o p q r s t u v w x y z { l } ← → (space) 4-6 4.
E D C B A 5 CPG #2561255 F IRE L ARM 2500 Operating Manual 5-1 5 Maintenance Most modern control units do not require perio dic adju stment or field repair other than re placement of a module or printed circuit board assem bly.
1 2 3 4 Contents 5 CPG #2561255 F IRE L ARM 2500 Operating Manual 5-2 7. Press . All audible and visual indicators on the panel and NAC out puts should operate. Restore AC power and ve rify panel is in normal standby conditio n. 8. Press to enter auto reset mode.
E D C B A CPG #2561255 F IRE L ARM 2500 Operating Manual A-1 Appendix A. Optional Accessories A.1 Remote Annunciator with Liqu id Crystal Display (2500-RALCD) Part # 2500-RALCD UL Listed: For use with the FireLarm 2500 Dimensions: 4 ½” W X 4 ½” H X 7/8” D (approximate) Weight: 5.
1 2 3 4 5 Contents A CPG #2561255 F IRE L ARM 2500 Operating Manual A-2 A.2 Zonal Digital Alarm Communicat or Transmitter (2500-ZDACT) UL LISTED: For use with the FireLarm 2500 Transient protected Power requirements: Input current Standby: 50mA Alarm current: 90mA max.
E D C B A CPG #2561255 F IRE L ARM 2500 Operating Manual A-3 A.3 Style Z (Class A) Module for NAC circuits (CAM) UL LISTED: For use with the FireLarm 2500 Part No. 345-0234 TRANSIENT PROTECTED BUILT IN 5.1K END OF LINE RESISTOR POWER REQUIREMENTS IN ALARM: Approx.
1 2 3 4 5 Contents A CPG #2561255 F IRE L ARM 2500 Operating Manual A-4 A.4 Master Box Module (Model MBM) UL LISTED: For use with the FireLarm 2500 Part No. 345-0235 Power requirements: Standby: 30mA Max @24VDC Alarm: 300 mA Max @24VCD Master Box Coil Resistance: 14.
E D C B A CPG #2561255 F IRE L ARM 2500 Operating Manual A-5 INSTALLATION Mount the snap track with the double-si ded tape provi ded and secure with two #6 sh eet metal screws. This module may be installed in a separate hou sing (HSI #327-0089) that is adjacent to and clo se- nippled to the fire alarm control panel.
1 2 3 4 5 Contents A CPG #2561255 F IRE L ARM 2500 Operating Manual A-6.
E D C B CPG #2561255 F IRE L ARM 2500 Operating Manual B-1 Appendix B. Smoke Detector Compatibility HARRINGTON SIGNA L (MAX. NO. OF DETECTORS PER ZONE IS 25) DET. MODEL IDENTIFIER BASE MODEL IDENTIFIER H511C S10A N/A H511CXT S11A N/A N/A ESL (MAX. NO.
1 2 3 4 5 A Contents B CPG #2561255 F IRE L ARM 2500 Operating Manual B-2.
E D C CPG #2561255 F IRE L ARM 2500 Operating Manual C-1 Appendix C. NAC Compatibility The following devices are comp atible with the FireLarm 2500 . CPG Signals 460 series sounders SPLF, SPAF, SPHP, .
B 1 2 3 4 5 A Contents C CPG #2561255 F IRE L ARM 2500 Operating Manual C-2 4415, 4495 series AC chimes 4765, 4775 series DC chimes 3431, 3436, 4496, 4411, 4416 se ries AC bells 4461, 4464, 4466, 4761.
E D CPG #2561255 F IRE L ARM 2500 Operating Manual D-1 Appendix D. Ordering Information Base Components Model No. Description Stock No. 2500-LCD 4 Zone Control Panel (red cabi net) – with LCD 2500-LCD 2500-LED 4 Zone Control Panel (r ed cabinet) – no LCD 2500-LED 2500-MAN FireLarm 2 500 Installation Instruction Manual 2500-MAN 12V6.
C B 1 2 3 4 5 A Contents D CPG #2561255 F IRE L ARM 2500 Operating Manual D-2.
E CPG #2561255 F IRE L ARM 2500 Operating Manual E-1 Appendix E. Quick Reference Operating Instructions FireLarm 2500 Normal Standby Green AC indicator on.
D C B 1 2 3 4 5 A Contents E CPG #2561255 F IRE L ARM 2500 Operating Manual E-2.
デバイスCPG CPG #2561255の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
CPG CPG #2561255をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCPG CPG #2561255の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。CPG CPG #2561255の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。CPG CPG #2561255で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
CPG CPG #2561255を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCPG CPG #2561255の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、CPG CPG #2561255に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCPG CPG #2561255デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。