381333–136 C 50 Hanove r Road, F lorham Park, New J ersey 07932–1591 USA For sales or service call 1 800 800–2726 (A SCO ) www.ascopower .com AS CO PO WER TECH NO LOGI E S CA NA DA PO Box 1238, .
SECT ION 1 INST ALLA TION 1 --- 1 The ASCO 7000 Se ries A ut omatic Closed–T ransiti on T ransfer & Bypass–Isolation Switch ( ACTB) consists of an upper bypass–i solatio n sw it ch, a transfer swit ch, a monitoring and transfer control ler, and door–mounted controls.
INST ALLA TION (cont inued) 1 --- 2 De–energ ize the conductors b efo re m aking a ny line or a uxiliary circuitry co nnections. Be sure that Norma l and Emergency line co nnections are in prop er phase rota tion. Pla ce engine gen - erator sta rting control in the OFF position.
INST ALLATIO N (continued) 1 --- 3 RED RED GREEN GREEN obse rve these li ghts RED RED RED Figure 1- 3. Standard controls and i ndicators. F unctio nal T est R ead all instruc tions on the W irin g Diagrams and label s affi xed to t he A CT B. Note the control features tha t are provided and r eview their operation before pro ceeding.
INST ALLA TION (cont inued) 1 --- 4 RED RED GREEN GREEN obse rve these li ghts RED RED RED oper at e this s w itch Figure 1- 4. Standard controls and i ndicators. 2 – Electrica l Op eratio n Th i s pro ced ur e che cks e le ctr i cal op er at i on o f t he A T S.
SECT ION 2 TEST ING & SERVICE 2- -1 TRA NS FE R TEST T est the A utom atic Closed –T ran sition T ransf er Switc h portion of t he 7000 Series ACTB at least once a month. This proc edure chec ks the elec trical oper ation of the T ransfer Switc h and Control P anel.
TEST ING & SERVICE (continued) 2- -2 TROUBL E-SHOOTING Note any opti onal accessories that may be furnished on the ACTB and review their operation. R efer to any sepa- rate draw ings an d/or instr uction s that may be p acked with the A CTB. T abl e 2-1.
SECTION 3 B YP ASS ING & ISOLA TING 3 --- 1 BY PA S S I N G T H E A T S * This pr ocedu re expl ains h ow to Byp ass the c los ed autom atic transfer sw itch contac ts.
B YP AS SING & ISOLA TING (continued) 3 --- 2 ISOLATING THE A TS Isolating is required before any service work can be perform ed on the automatic trans fer switch ( A TS). R efer to Figures 3–4, 3–5, 3–6, and 3–7. 1. Bypass t he closed automatic trans fer switch c ontacts.
B YP AS SING & ISOLA TING (continued) 3 --- 3 RETURN TO SERVI CE This proc edure explain s how to r eturn the automatic tr an sf er s wi tch ( A T S ) to s er vi ce a f te r i ns pe cti o n and maintena nce. Observe t he Byp ass Sw itch P osition in dica- tor and lights).
B YP AS SING & ISOLA TING (continued) 3 --- 4 RETURN TO SERVI CE cont inued* This proc edure exp lains how to return the Bypass Switc h Hand le to the OPEN position . Th e Bypass Handl e must be i n the CLOSED positi on (yellow indicator on NOR - MAL or EMERGENCY ) and the Is olation Handl e must be in t he TEST posi tion (window).
INDEX Printed in U .S.A . Copy right ASCO Power T echnologies, L.P . 2007 A Alarm R eset pushbutton, 1–4, 2–2 auxil iary cir cuits, 1 –2 B bus connections, 1–2 bypassing t he A TS, 3–1 C cat.
デバイスEmerson 7ACTBの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Emerson 7ACTBをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはEmerson 7ACTBの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Emerson 7ACTBの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Emerson 7ACTBで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Emerson 7ACTBを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はEmerson 7ACTBの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Emerson 7ACTBに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちEmerson 7ACTBデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。