Precision Cooling For Bu siness-Critical Con tinuit y Li eb er t E nv i r osou r ce ™ Us er Manu al - 1.5 to 10 T ons, 60Hz.
.
i T ABLE OF CONTENTS 1.0 I NTRODUCTI ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2.0 S EQUENCE OF O PERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii.
Introd uction 1 1.0 I NTRODUCTION The Envirosource Module is an ac cessory to the Process Chiller, fo r use on systems that circulate water and/or glycol solutions that require an isolat ed loop from the emergency water source.
Sequence of Opera tion 2 2.0 S EQUENCE OF O PERATION During normal operation, cold fluid flow from th e chiller passes across the flow switch, through the heat exchanger, through the pump bypa ss check valve, past the supply temperature sensor and out to the load (see Figu res 1 and 2 ).
System Components 3 3.0 S YSTEM C OMPONENTS RCM4 Monitor is configured to a ctivate an LED and an audible alarm . The common alarm output contacts will close in response to a loss of flow or high supply fluid temperature. The silence/reset but- ton silences the alarm.
Installation 4 4.0 I NST ALLATION Prepare the location(s) for the unit (see Figure 4 ). Allow adequate clearanc e for convenient mainte- nance. Anchor the unit to the floor or bolt it secu rely to the wall using appropriate anchors (supplied by others).
Maintenance 5 5.0 M AINTENANCE Periodic preventive maintenance sh ould incl ude a monthly manual swi t chover to ensure that the sys- tem operates properly.
Maintenance 6 Figure 2 General piping arrangement—Envir osour ce st andby pump and cooling module with Process Fluid Chiller 8-10 ton air coole d models with electronic hot gas byp ass.
Maintenance 7 Figure 3 Physical dat a ENV20G-_00 ENV05G-_00 / ENV10G-_00 Pump Heat Exchanger City W ater Supply Supply from Chil ler To D r a i n Supply to Load Pump Heat Exchanger To D r a i n City W.
Maintenance 8 T able 3 T echnical dat a—Envirosource module, 60 Hz Process Fluid Chiller PS018A PS 024A PS036A PS048A PS060A PS096A PS120A Model Number ENV05G ENV05G EN V10G ENV10G ENV10G ENV20G ENV20G Circulating Fluid—Water Flow Rate, gpm (l/s) 2.
Maintenance 9 Figure 4 Service clearances ENV05G / ENV10G / ENV20G Shaded areas ind icate recommended clearan ce for component access and removal..
Maintenance 10 Figure 5 Equipment layout Load Envirosource (ENV05G or ENV10G) City W ater Process Chiller Drain Outdoor (Glycol) Applica tion.
Maintenance 11 Figure 6 Cabinet dimensions for Envirosourc e ENV05G and ENV10G.
Maintenance 12 Figure 7 Cabinet dimensions for Envirosourc e ENV20G.
Maintenance 13 Figure 8 Electrical schematic.
Maintenance 14.
.
Ensuring The Hi gh Av aila bilit y 0f Mission-Critic al Dat a And Appli c ations. Emerson Net work P ower , the global leader in enabling business-critical continuity , ensures net work resiliency and.
デバイスEmerson ENV20Gの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Emerson ENV20Gをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはEmerson ENV20Gの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Emerson ENV20Gの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Emerson ENV20Gで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Emerson ENV20Gを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はEmerson ENV20Gの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Emerson ENV20Gに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちEmerson ENV20Gデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。