M_FC01_LQ_0408_e

Please follow these installation and adjustment instructions carefully. Failure to comply with these instructions or misuse of this equipment will void your warranty coverage.
Equipment installation, connection and adjustment by qualified personnel only!
The instructions cover software version 1.00.









The Flow Meter FC01-LQ may be used with calorimetric monitoring heads type CSx (CSP, CSF).
The transistor outputs enable the user to additionally process fault, status and volume pulse indications in the control system.
As relay outputs or transistor outputs the digital signals enable the user to integrate the FC01-LQ into a control and monitoring system.
These quantities are made available to the user as analogue electrical signals, physically isolated, as current or voltage output and may be monitored by means of a limit monitor.
The Flow Meter FC01-LQ is designed to detect flow speed, flow volume and medium temperature of water (other liquids upon request).
Description 1


The flow rate is determined by mass flow.
Major benefits of this method are:
Two temperature-sensitive resistors (sensor elements RS and RM) are immersed in the medium. Sensor RM assumes the temperature of the medium ϑM whilst heater resistor RH heats element RS to temperature ϑS. As a function of the medium, the temperature differential Δϑ = ϑS - ϑM is preselected as a reference variable by the CTD control and is kept constant. The required heater current IH is a function of mass flow so that the control variable y of the control can be used for evaluation.
Fig. 1 is a schematic diagram of a CTD method based sensor.
The temperature difference Δϑ between the two sensors is kept constant and the mass flow is determined by measuring the calorific power.
The thermal measuring method CTD (Constant-Temperature-Difference) is based on following principle:
A body with a temperature higher than its surroundings supplies a medium flowing past that body with energy in the form of heat. The amount energy supplied is a function of temperature difference Δϑ and mass flow.
The calorimetric measuring procedure is based on the physics of heat dissipation.
y m: mass flow w: reference variable ( ) x : actual value ( S- M)
2 Description

1 Input voltage DC supply (terminal XV)
The system comprises the following hardware functional modules:
5 Controller system:
3 Keyboard/Display:
2.2 User interface 2
2.1 User interface 1
1 Input voltage:
Sensor- interface calorimetric monitoring head CSx_
2.2 analogue outputs 1 and 2 (terminal XAO)
signal processing I/O - controlling monitoring parameter memory fig. 2
calorimetric monitoring head type CSx_
keypads LC display 2 x 16 digits
relay outputs: 2 limit values transistor outputs: 2 limit values + 1 error indication + 1 busy signal or frequency output (software selected) analogue outputs current or voltage

(optional) Please see the ordering number to find out whether it is a current or voltage output.
(optional) Two-channel physical isolation, relay change over contact
This mainly applies to monitoring head selection, signal outputs (switch point setting) and analogue outputs (zero point setting and scaling).
System configuration and parameter setting are by means of the keyboard if default values need to be changed. (paras. 5 and 6)
Cables and user interface connections are shown in para. 2.3.2 and circuit diagram 2.3.2.1/ 2.3.2.2.
Connection of the monitoring heads is by means of precut cable links.
There is no electrical isolation between monitoring head and central electronic unit.
The power supply is physically isolated between power supply input and system power supply output. This also applies to the analogue and signal outputs which are physically isolated from each other as well as from the other electronics.
The shields of the signal cables should be applied on one side only.
Shield connections are ungrounded.
20% zero elevation and FS value can be programmed. (See para. 5.11)
These FS (full scale) output quantities apply to both channels (flow and temperature) as standard.
Please see para. 8.4.2 for electrical connection.
Channels 3 and 4: Both channels may be assigned individually or in pairs to the physical quantities of temperature or flow. The switch on or off values of each transistor output can be set as desired.
Four-channel physical isolation, transistor output - collector/emitter (NPN) freely connectable
Please see para. 8.4.1 for electrical connection.
The channels may be assigned in menu “CONFIGURATION”, either individually or in pairs, to the physical quantities of temperature or flow. The switch on and off values can be set as desired in menu “PARAMETERS” (yet within the measuring range) for each contact.
0/4 - 20 mA FS (option C1)
0/2 - 10 V FS (option V2)
4 Description

Please see para. 8.2.1 for technical characteristics.
A PTC resistor provides protection from overcurrent. The element automatically resets upon removal of the disturbance or after disconnection of the supply voltage of the FC01-LQ for approx. 1 s (e.g. remove terminal XV).
Noise emission on the connection cable is limited by circuit design and filter.
Internal switch mode power supply with physical isolation of the primary and secondary side.
Description 5

Hastelloy 2.6410 is a material with a chemical resistance generally exceeding that of stainless steel and copper-based alloys. They are particularly suitable for alkaline media (pH > 7). They should however be examined for suitability for each specific application using resistance tables and pragmatical values.
Nickel-based alloy (Hastelloy 2.4610)
Stainless steel heads must not get in contact with steel parts other than stainless steel or with chemically dissimilar metals, as this would cause electrolytic corrosion.
Stainless steels owe their resistance to rust mainly to their alloy combination with chromium, the formation of chromic oxide on the steel surface resulting in a passive state. Contamination, deposits on the surface, or foreign rust may however neutralize the passivity. Therefore care should be taken to keep the surfaces clean.
The resistance of this stainless steel should however be verified by the user, particularly when it is used in medium mixtures that may from time to time be exchanged with cleansing agents. Its chemical resistance also depends on temperature, flow rate and concentration of the medium.
The standard monitoring head material is stainless steel 1.4571/AISI 316 Ti, an austenitic, acid- resisting stainless steel that is commonly used throughout industry. Manufacturers claim it also withstands oxidizing organic and anorganic acids, and partly even reductive media.
Stainless steel 1.4571 / AISI 316 Ti
These are general directions for the application of calorimetric measuring heads which from application to application should be reviewed by the user in accordance with individual requirements.
6 Installation


Material of the area exposed to medium: stainless steel 1.4571/AISI 316 Ti, electropolished O ring viton
2.2.1 Insertion head CSP for sensor adapter TP-.. and ball valve BV-..
Installation 7

To ensure the safety label is clearly visible, it should be affixed on to or close to the measuring point.
2.2.1.2 Mounting instructions (monitoring head CSP-.. with sensor adapter TP-.. )
Material of the area exposed to medium:
The sensor adapter TP-.. is available in 6 pipe diameters from 1/2" to 2". Sensor adapter is available as screw-in (fig. 4 top) or welding type (fig. 4 bottom).
2.2.1.1 Sensoradapter TP-..

Sealing of the monitoring head in the sensor adapter is by means of the O ring provided (fig. 3).
Correct immersion depth of the monitoring head is ensured by the stop provided.
The retention pin ensures correct alignment of the monitoring head after the union nut has been tightened.
The monitoring head should only be installed or removed when the pipes are unpressurised.
- stainless steel 1.4571/AISI 316 Ti
DN Type TP-01 … TP-02 … TP-03 … TP-04 … TP-05 … TP-06 …
8 Installation · - brass or · retention pin

The monitoring head may also be replaced in pressurised pipe systems on duty.
The ball valve of Postberg GmbH at D-63485 Bruchköbel is available in 4 nominal diameters from 1" to 2". The ball valve ensures the sensors are fully immersed in the medium.
❑Please see the applicable drawing of Postberg GmbH for mounting instructions and dimensions, if necessary.

Ball valve BV-… · Installation 9


Material of the area exposed to medium:
Style: smooth shank, 18 mm dia., immersion depth adjustable within the PG16 cable gland (accessory) or mounting in the stainless steel cutting ring gland
- threaded installation bush stainless steel 316 (cutting ring) (see fig. 7)
- cable gland PG16 nickel-plated brass (see fig. 7)
Accessories:
- M7 sensor stainless steel 1.4571 /AISI 316 Ti, shank aluminium
- M1 sensor and shank stainless steel 1.4571 /AISI 316 Ti (sensor)
monitoring head should be aligned in direction of flow (see arrow)
10 Installation


2.2.2.1 Mounting instructions for monitoring head CSF-11
The shoulder of the sensor (7 mm from the tip) must be at the position 1/8 from dia. i.
The two sensors (M) should be screwed into the pipeline far enough to ensure that they are aligned side by side directly across the direction of flow. The sensors are correctly positioned when the wrench flats (S) are aligned parallel with the pipeline.
monitoring head should be aligned in direction of flow (see arrow)
Installation 11


The locking chain must be mounted as tightly as possible.
- Put chain catch (2) into link and fasten with the tight chain.
- Fix first link of chain (1) into the clip (3) (tightening torque 10 Nm).


5 x D 20 x D
D = nominal pipe diameter
12 Installation


1 chain 4 x 32 DIN 5685 (approx. 1 m) 2 catch for chain NG 5 3 clip with screws and nuts DN15 to DIN 11850 (tightening torque 10 Nm)
Cable Do + Ka type xx (depends on FC01-LQ version and sensor-type used - see figs. 15 and 16)
cable Kabel-Union LifYCY 4 x 2 x 0,2 mm2
Installation 13 · Locking set 01


2.3.1.1 Rail-mounted version FC01-LQ-U1...
2.3 Installation of electronic control unit FC01-LQ
14 Installation


2.3.1.2 Surface mounted version FC01-LQ-FH-U1...
Installation 15


2.3.1.3 Front panel mounted housing FC01-LQ-ST-U1...
16 Installation


XTF - Keyboard release
Connection by 3 pole connector; max. 1.5 mm2; 3 x 0.75 mm2 cable recommended
XV - Power supply
Valid for all plug-in screw terminal strips:
Bridge 2-3 inserted = keyboard blocked
Connection by 3 pole connector; factory-wired
Pin No. Signal name Function
3 -UV negative pole of supply voltage
2 +UV positive pole of supply voltage
1 SGND general reference ground/shield ground
XSK - calorimetric monitoring head XTF - keyboard release
1 2 3 4 5 6 7 8 9 10 1 2 3
Installation 17

Connection by 8 pole connector; max. 1.5 mm 2; LifYCY 4 x 2 x 0.2 mm2 cable recommended
XAH - Limit switch signal outputs - transistor outputs NPN, freely connectable as emitter (-) and collector (+) have been brought out separately.
Connection by 8 pole connector; max. 1.5 mm2; LiYCY 3 x 0.38 mm2 cable recommended for each signal output
XAH - Limit switch signal outputs - relay outputs - change over contacts
* Apply shield on one side only.
Pin selection for analogue outputs (option: V1, V2, C1)
Connection by 8 pole connector; max. 1.5 mm2; LiYCY 2 x 0.25 mm2 cable recommended for each analogue output
XAO - - Analogue outputs
Pin No. Signal name Function
Pin No. Signal name Function
Pin No. Signal name Function
4 /BUSY/PULSE C availability signal or frequency output - collector terminal
3 /BUSY/PULSE E availability signal or frequency output - emitter terminal
2 /ERROR C summarized error indication - collector terminal
1 /ERROR E summarized error indication - emitter terminal
8 /LIM2 inverted signal output 2 (N/C)
7 LIM2COM common change over input 2
6 LIM2 non-inverted signal output 2 (N/O)
5 SGNDL2 shield ground 2
4 /LIM1 inverted signal output 1 (N/C)
3 LIM1COM common change over input 1
2 LIM1 non-inverted signal output 1 (N/O)
1 SGNDL1 shield ground 1
7 ANA2GND reference potential for analogue output 2
6 ANAO2 analogue output 2 - temperature
5 SGNDA2 shield ground for analogue output 2 (ungrounded) *
4 SGNDA1 shield ground for analogue output 1 (ungrounded) *
3 ANA1GND reference potential for analogue output 1
2 ANAO1 analogue output 1 - flow
18 Installation · 8 NC none · 1 NC none

Only for connection of cable shield (not released for user)
(XAS - secondary current supply)
Pre-sized connecting cable Do+Ka type 15 or Do+Ka type 18 with plug-in screw terminal strip (see 2.2.3).
XSK - Connection of calorimetric monitoring head type CS_x
Pin No. Signal name Function
3 SGND /shield ground
8 LIM1 C limit value 1 - collector terminal
7 LIM1 E limit value 1 - emitter terminal
6 LIM2 C limit value 2 - collector terminal
5 LIM2 E limit value 2 - emitter terminal
Installation 19

2.3.2.1 Circuit diagram FC01-LQ
* recommended ** SGNDA1 SGNDA2 Apply shield one side only.

1 2 3 4 5 6 7 8 9 10 1 2 3
signal outputs analogue outputs ** C1, V1, V2
LifYCY 4x 2x0.2 mm2
20 Installation · power supply · calorimetric monitoring head

2.3.2.2 Circuit diagram FC01-LQ
* recommended ** SGNDA1 SGNDA2 Apply shield one side only.
E/ - emitter terminal C/+ collector terminal

1 2 3 4 5 6 7 8 9 10 1 2 3
signal outputs analogue outputs ** C1, V1, V2
Installation 21 · power supply · calorimetric monitoring head


Typical circuit (example 1)
If the frequency output of the FC01-LQ is connected to an electronic counter, computer or PLC, the load current should not exceed 10 mA so as to ensure low level is 0.8 V. The max. admissible voltage level of 48 V is irrelevant in this connection.
Electronic signal processing (fig. 17)
The shield cables can be connected to connector XAS, pin 3.
Select cable size ≤1.5 mm 2 to make the connections.
The pulse length is 50 ms (±1%) continuously.
Signal ground shall be connected to pin 3 (BUSY E/-) and the driving load to pin 4 (BUSY C/+).
The quantity-dependent pulse may be selected in the menu item “DISPLAY SELECT”. A square pulse signal is available for driving a counter or a primary control at the plug XAH /BUSY E/- and /BUSY C/+ (pins 3 and 4) (see fig. 16 - circuit diagram FC01-LQ - transistor outputs).
2.3.2.3 Electrical connection - frequency output (version FC01-LQ-U1T4)
22 Installation



Typical circuit (example 2)
If a separate relief network is preferred to the integral network, care should be taken when processing the max. frequency of 10 Hz to ensure the energy stored in the operating coil has dissipated by the time the counter output is reset. The time to do this should be below 40 ms, making due consideration to switching times and pulse variations.
It should therefore be ensured that the counter can be increased by one during the time available.
The counter should be able of processing a counting frequency of ≥10 Hz, as the puls e length is 50 ms (±0.1%) constinuously.
The FC01-LQ driver output comprises an integral safety circuit which when isolating the counter operating coil will limit overvoltages caused by inductance and convert the energy stored.
Electromechanical pulse counter (fig. 18)
❑ As there will be a reset pulse available at the output in the moment the supply voltage of the FC01-LQ is applied, make sure that the counter is switched on delayed or set to zero after it has been switched on
tON - switch-on time tL - time constent of switch-off current
Installation 23



It is also required for setting the unit to simultaneously press UP and DOWN = .
Setting and configuration is by means of three front keypads MODE, UP and DOWN.
All functions are distributed on the three following menu levels:
Clear menu-driven control, via keyboard and display, enables easy definition of parameters and configuration. This provides high system flexibility, making the FC01-LQ the optimum solution for a wide variety of measuring, monitoring and display tasks.
The FC01-LQ can only be set or operated when connector XTF (keyboard release) is removed!
CONFIGURATION LEVEL (MENU)
MAIN LEVEL (MENU)
24 Operating system

reset by simultaneously pressing UP and DOWN = .
Selected data such as MIN, MAX values, totalized quantity or LAST ERROR can be deleted or
Afterwards the data are still available even after switching the FC01-LQ repeatedly on and off.
A permanent transfer of settings and values is only effected when quitting the menu, after a plausibility check of all entries.
Pressing MODE transfers the set value or the selected menu option to a volatile memory.
The longer UP or DOWN are pressed, the faster the increase or reduction.
Each time UP or DOWN are pressed, the value indicated will be increased and reduced respectively, by one numeral skip.
menu option, the value indicated can be changed by pressing UP or DOWN.
Some menu options require numerical values to be entered. After selecting the appropriate
Simultaneously pressing UP and DOWN = calls the selected menu option, or causes skipping to the selected submenu.
Calling a menu option
Pressing MODE after the last menu option will cause skipping to the first option of the menu.
The next menu option is selected by pressing MODE (forward paging).
After configuration and parameter selection re-connect plug XTF (keyboard release) to protect the system against unauthorised access!
▲ + ▼ ▼ ▲
▲ + ▼ ▼ ▲

The following operating data may be retrieved in the main menu during the measuring cycle: (see para. 4.2.1).
Analogue output, limit switches etc. can be set beyond the measuring range. When per cent display is selected, the defined measuring range will correspond to 0 ... 100% (>100% when the defined range is exceeded).
This feature will not affect the accuracy specified for the measuring ranges defined whilst no accuracy information can be given for conditions where the measuring ranges are exceeded.
Theoretically established measuring values will be used when the measuring range of calorimetric monitoring heads is exceeded (0.05 … 3 m/s for water). The FM-LQ 1 can thus be operated beyond the measuring values defined (up to 4 m/s for water).
Over limits of the measuring range
may be deleted simultaneously operating the UP and DOWN = switches without affecting the measuring operations.
All options of the main menu may be addressed without affecting the measuring and monitoring function.
Upon completion of the heating up period and availability of the first measured value, the display will change to measuring cycle, and the user interfaces such as analogue outputs or limit switches will be up-dated.
If during the test no error was found, the display will indicate HEATING UP. The FC01-LQ will then be in the heating up period required for the measuring procedure.
During this period, the integral controller will conduct test routines (see para. 7.1, Test and diagnosis).
Upon power application POWER ON TEST will be shown on the display for approx. 1 sec., with the software version number being indicated in the second line.
4 Operation and main menu
26 Operation and main menu
❒ It is not possible to configure or select parameters of the system during the measuring operations!
LAST ERROR
PEAK VALUE MAX
PEAK VALUE MIN
▲ + ▼ ▼ ▲
Menu option values

The analogue bar has different meanings, depending on its configuration (see para. 5.7 - menu option BARGRAPH).
The lower line of the display will optionally show the switching condition of the limit switches and an analogue bar with a 10-segment resolution, or the flow volume/time unit pertinent to the indicated flow rate or the totalized flow volume (totalizer function).
Flow rate and medium temperature are indicated by the units selected in the upper line of the LC display.
4.2.1.1 Measured value(s)
Operation and main menu 27
T F
F
T F
T F
T F
T F F
5.0 m/s -13.5 ° C
5.0 m/s -13.5 ° C
5.0 m/s -13.5 ° C
5.0 m/s -13.5 ° C
5.0 m/s -13.5 ° C
22206.9 l/min
37004567.9 l
1332.4 m 3 /h
370.1 l/s
P
T
P
F
T
Frequency output selected (invers representation) „switch-on condition“
Temperature, active (invers representation) „switch-on condition“

The user may purposely delete the error memory in the condition selected by simultaneously pressing UP and DOWN = . ▲ ▼ ▲ + ▼
Other than the peak value memories described above, the contents of this memory will be retained even upon power failure.
This error memory comprises the number of the last error (see section 7). It may be very helpful when commissioning the FC01-LQ.
The last main menu option to be called is the error memory.
▲ + ▼ ▼ ▲
After switch-on or NOT-BUSY indication, the minimum and maximum values are deleted and will be continuously updated (non-return pointer principle). The peak values may be retrived in the main menu and are deleted by simultaneously pressing
They store the lowest and highest value of flow rate and medium temperature.
The FC01-LQ comprises four specific measured-values memories.
The following figures show the display variants under menu option “Measured value(s)” (para. 5.6 - menu option DISPLAY SELECT and 5.9 - menu option FREQUENCY OUTPUT).
Limit switches lying within the analogue bar range are also represented at the appropriate place of the analogue bar (see para. 5.7).
If F and T are shown reversed, the limit switch is in the switch-on condition.
The limit switches are identified according to their physical assignment, i.e. by F for flow rate and T for medium temperature, at the first or last place of the second line on the display.
28 Operation and main menu
UP and DOWN = .
Power failure or disconnection of the power supply will delete the contents of the four measured-values memories.
MAX VALUE flow rate
MIN VALUE flow rate
MAX VALUE medium temperature fig. 21
MIN VALUE medium temperature

4.2.1.4 Main menu
Operation and main menu 29

HEATING UP *
* not available with turbine-type sensor
See section 6 · See section 5 · power-on

Available sizes are:
The nominal diameter of the ball valve is selected in menu option BV SIZE SELECT.
Enter the following characteristics when selecting a CSP monitoring head:
Enter the following characteristics when selecting a CSF monitoring head. The setting is menu driven:
These characteristics are specified by the sensor code which together with the monitoring head type number is marked on the monitoring head housing.
To operate the FC01-LQ with a calorimetric monitoring head, it is necessary to set sensor- specific characteristics.
The monitoring head programme is continuously extended - please enquire.
The appropriate sensor can be selected from the following menu (for type designation see type label or CPI catalogue).
This menu option comprises all monitoring heads that can be used with the FC01-LQ (issue 07.2003).
The CONFIGURATION menu serves to adjust the FC01-LQ to the application within the entire system. During system configuration, measuring operations are not possible (see appendix 1). Configuration possibilities are:
Take care to repeat these settings after replacing the monitoring head or electronic control unit FC01-LQ, as the accuracy of measurements is determined by the sensor code.
Menu option SENSOR SELECT may influence data in the parameter selection menu (see para. 5.12, Quitting the configuration menu).
30 Configuration

Mode of operation, limit value and hysteresis of the limit switches are set in menu PARAMETER SELECTION.
The following combinations are available:
The FC01-LQ comprises two limit switches (LS1 and LS2) which are assigned to the physical quantity/quantities to be monitored in submenu LIMIT SWITCHES.
Available sizes are:
The internal diameter of the sensor adapter is selcted in menu option TYPE SELECT.
Enter the following characteristics when selecting a CSP monitoring head with sensor adapter TP-..:
Menu option LIMIT SWITCHES may influence data in the parameter selection menu (see para. 5.12, Quitting the configuration menu).
limit switch 2 flow rate
limit switch 1 medium temperature
limit switch 2 medium temperature
limit switch 1 flow rate
limit switch 2 medium temperature
limit switch 1 medium temperature
limit switch 2 flow rate
limit switch 1 flow rate
Configuration 31

In both cases the totalizer will restart from zero.
The content of the totalizer is deleted by simultaneously pressing UP and DOWN =
When the display changes from m3 to litre or gallons, or from litre or gallons to m3, the value already counted will be converted.
Where totalizer function has been selected, the totalizer will start at zero counting in the unit selected (litre, m3 or gallons).
When the first line of the LC display in the main menu indicates the flow rate in the unit selected as well as the medium temperature in °C, °F or K, it is possible to select the second line from the following menu options (see para. 5.14).
The FC01-LQ enables the user to define the 2nd line of the display 2 in certain points.
All other entries relating to the medium temperature (limit value, analogue output, etc.) refer to the unit selected there. When the temperature unit is changed, all configuration and parameter data relating to medium temperature will automatically be converted.
Options are:
This submenu is used to select the medium temperature unit (1st line top left).
When the flow rate unit is changed, all configuration and parameter data relating flow rate will automatically be converted!
Standard percent is displayed when BLANK (no unit) is selected.
Any further entries relating to flow rate (e.g. limit value, analog ue output etc.), refer to that unit.
This menu option is used to set the desired flow rate unit:
At these point (1st line top left) the requested unit for the flow velocity will be set.
, or when the max. display value (99999999.9 l, m3 or gallons) is reached.
▲ + ▼ · 32 Configuration · ▲ ▼

For representation details see para. 4.2.1 (Operating data).
The representation of the limit switches in the bar graph depends on the switch-on value of the limit switch.
The bar graph also comprises the representation of the limit switch(es) as far as they can be indicated in the bar range selected.
When entering the initial or final value, the user should observe reasonable resolution!
Independent of its assignment, the bar graph has a constant resolution of 10 segments.
This menu option allows the user to set the bar graph as desired. The following settings should be made:
Skipping to the submenu BARGRAPH or PIPE SIZE is effected depending on the selected menu option.
resulting in the analogue bar graph display shown below:
Final value - analogue bar graph: 30 °C
Initial value - analogue bar graph: 20 °C
The content of the totalizer is deleted in the event of power failure or disconnection of the power supply!
20 °C 21 °C 25 °C 29 °C 30 °C
T T
23 ° C
Configuration 33

This means that only the content of the totalizer is deleted.
As the frequency output refers to the content of the totalizer, although its operation is not dependent on the content of the totalizer, a totalized quantity that is smaller than that set per pulse will not be lost.
= in the main menu.
The content of the totalizer may be deleted by simultaneously pressing UP and DOWN
Behaviour of the frequency output when the content of the totalizer is deleted
When the measurement is stopped (as caused by priority II error and calling the configuration or parameter selection menus), the pulses for the quantity already counted will be available. Thereafter the output of pulses will be stopped, with the frequency output becoming high- resistive until the measurement is restarted.
Behaviour of the frequency output when the measurement is stopped
Error No. 20, 30, 60, 40, 41.
If a combination of priority III errors occurs simultaneously, they are indicated or stored in the error memory observing the following sequence:
The max. frequency being exceeded will not cause the measurement to stop but will rather cause the error output to signal error 60 on the display. This error is included in priority group III.
Behaviour of the frequency output when the max. frequency is exceeded
Potential setting range of the frequency output: 1 pulse per 0.1 … 999.9 [litre], [m3], [gallons]
When the quantity-proportional pulses are assigned, the frequency of the frequency output must no exceed 10 Hz. The limits that can be displayed are determined by the flow velocity range and the pipe diameter.
The proportional quantity pulses have been determined as follow:
The totalizer function of the FC01-LQ has been expanded by the output of proportional quantity pulses. The function can only be displayed by version FC01-LQ-U1T4 (transistor outputs).
This is provided by selecting the pipe diameter in menu option PIPE SIZE comprising pipe diameters from 10.0 … 999.9 mm.
If flow volume/time unit display has been selected, it is necessary to indicate the pipe diameter to calculate mass flow.
The frequency output will supply 1 pulse per 10 litres (totalized quantity).
1 pulse / quantity (totalizer unit selected)
34 Configuration · ▲ + ▼ · ▼ ▲

Priority of entry errors in the CONFIGURATION menu:
“CONFIG. OK!” is indicated when the data are found correct. The menu may than be quitted by pressing MODE. Errors found during the plausibility check are indicated in the following sequence of priority.
To quit the configuration menu, the controller will check the data entered for plausibility.
Upon configuration of the analogue outputs, the menu may be quitted or re-set to the start (SENSOR SELECT).
When entering the initial or final value, the user should observe a reasonable resolution!
Options are:
In conformance with the configuration “Flow rate analogue output” it is possible to adjust the medium temperature analogue output to the requirements of the entire system.
With a flow volume/time unit selected in menu DISPLAY SELECT and when setting the initial and end values, the pertinent flow volumes will also be indicated.
When entering the initial or final value, the user should observe a reasonable resolution!
This menu option allows adjustment of the flow rate analogue output specifically to the requirement of the entire system.
Options are:
Configuration 35

An overview of the configuration menu and a summary of the measuring ranges and menus available for the sensor type selected are shown on the following pages.
Reason: Changing the physical assignment of limit switch 2 will adjust its switch-on and switch-off values to the new assignment (flow rate).
Example: Changing the limit switch assignment from LS1 →F / LS2 →T to LS1 →F / LS2 →F
of the configuration menu by pressing UP or DOWN and select the menu option with the incorrect entry for correction.
The menu can only be quitted after correction of the error(s). To do this, return to the beginning
In this event it is imperative to branch into parameter selection menu to set the data in conformance with the desired application.
If during the configuration data are affected which are accessible in the parameter selection menu, (which may be the case for the options Sensor Selection, Medium Selection and Limit Switch Assignment), the option “PARAMETERS” in the main menu will be flashing.
LS2 OFF = end of measuring range (depending on the medium selected)
36 Configuration · ▼ ▲


END OF CONFIG.? M→yes ▲ or ▼ → no
CONFIGURATION SENSOR SELECT
CONFIGURATION
G
F
E
D
B
A
See:


A
TYPE S-No. xxx
SENSOR CODE
PIPE SIZE DIAM. = xxx.x mm
Conf.
Conf.→ return to configuration menu

Conf.
Conf.
Conf.
Conf.
submenu limit switch combination
LIMIT SWITCHES LS1 → T LS2 → T LIMIT SWITCHES LS1 → F LS2 → F
LIMIT SWITCHES LS1 → T LS2 → F
or ▲ ▼ or ▲ ▼
Conf.
Conf.
Conf.
Conf.
FLOW UNIT METRE/SEC (m/s)
FLOW UNIT FEET/SEC. (FPS)
FLOW UNIT BLANK (no unit)
or ▲ ▼ or ▲ ▼ or ▲ ▼ or ▲ ▼
Conf.
Conf.
Conf.
TEMP. UNIT CELSIUS ( ° C)
TEMP. UNIT FAHRENHEIT ( ° F)
TEMP. UNIT
KELVIN (K)
or ▲ ▼ or ▲ ▼ or ▲ ▼
Conf.→ return to configuration menu


F
BARGRAPH TYP=FLOW or TEMP
BARGRAPH ZERO = 10.0 m/s
52.5 mm
ANA OUT FLOW OFFSET = (FS) ANA OUT TEMP. OFFSET = (FS)
BARGRAPH FS = 20.0 m/s
Conf.
M → yes other → no
Conf.
PULSE/ (unit)
Conf.
Conf.
Conf.→ return to configuration menu

A specific definition of the operation (closed-current or open-circuit principle) may be dropped by separately entering the switch-on and switch-off value of the limit switch, because the definition is deducted from the switch-on and switch-off value..
The hysteresis is determined by entering different switch-on and switch-off values. Its magnitude should be reasonably adjusted to current operating conditions.
Limit switch up-date is by measuring rate, independent of the set measuring time.
Depending on the configuration (see configuration menu) limit value 1 may be set either for flow rate or medium temperature. The limit value may be set over the entire measuring range and is always related to the display value.
6.2 Limit switch 1 - switch-on value (menu option: LS1 ON = ) Limit switch 1 - switch-off value (menu option: LS1 OFF = )
The set measuring time does not influence the measuring rate and display up-date.
The effect of the measuring time may be compared to that of a filter; it is used to determine the average of the last measured values (measuring time 100 ms) after each measurement.
The measuring time may be set between 1 and 30 sec., referring both to flow rate and medium temperature.
The following parameters may be set in the Parameter selection menu:
During parameter setting, measuring operations are not possible (see Appendix 1).
After configuration of the FC01-LQ in conformance with its application (configuration menu), it is possible to set parameters (e.g. limit values).
ON

For example, the scaling factor may be used to indicate the average flow rate in the pipeline rather than that available at the sensor.
The factor, which may be set between 0.01 and 9.99, allows flow rate indication changes (increasing or reducing the measured value in the display).
The scaling factor influences flow rate indication.
See limit switch 1!
6.3 Limit switch 2 - switch-on value (menu option: LS2 ON = ) Limit switch 2 - switch-off value (menu option: LS2 OFF = )
With limit switch 1 set for flow rate and a flow volume/time unit selected in menu DISPLAY SELECT, and when setting the switch-on and switch-off value, the pertinent flow volumes will also be indicated.
FC01-LQ with transistor outputs (option T4):
FC01-LQ with relay outputs (option R2):
Example for ON:
/LIM1 - LIM1COM = open
ON

An overview of the parameter selection menu is shown on the following page.
The menu can only be quitted after correction of the error(s). To do this, return to the beginning of the parameter selection menu by pressing UP or DOWN and select the menu option with the incorrect entry for correction.
Priority of entry errors in the PARAMETER SELECTION menu:
Errors found during the plausibility check are indicated in the following sequence of priority.
quitted by pressing MODE.
“PARAMETERS OK!” is indicated when the data are found to be correct. The menu may then be
Before the parameter selection menu can be quitted, the controller will conduct a plausibility check of the data entered.
switch-on value for limit switch 2 equals switch-off value for limit switch 2
switch-on value for limit switch 1 equals switch-off value for limit switch 1
switch-on and/or switch-off value for limit switch 2 outside measuring range
switch-on and/or switch-off value for limit switch 1 outside measuring range
Parameter selection 43 · ▲ ▼


END OF PARAM.? M→yes ▲ or ▼ → no
PARAMETERS LS1 ON = 1.24 m/s
PARAMETERS MEAS. TIME = 3 sec

Other than the above priority groups, errors No. 20, 30, 60, 40 and 41 will not cause measurements to stop; the error output will indicate and the number of the error will be shown on the display.
These test routines are also continuously carried out during operation.
These test functions are continuously carried out during operation. The occurrence of errors No. 10 and 21 will cause measurements to stop, indicating the error and monitoring the source of the error. Upon rectification of the error, the system will automatically return to measuring operation.
Priority I errors cannot be rectified by the user!
If even after several trials the switch-on test cannot be conducted without error indication, the system should be returned to the supplier for rectification, indicating the error number.
The test routines may be repeated by pressing any of the switches.
Errors No. 1 to 5 do not allow system operation.
Their implementation is indicated.
Priority group I comprises the switch-on test routines (FC01-LQ self-test) which are carried out when the system is switched on.
The FC01-LQ is provided with extensive test and diagnosis functions which may be classified as follows:
7 Errors
Errors 45

If a combination of errors occurs simultaneously, they are indicated or stored in the error memory observing the following sequence.
In order to facilitate operation, the last error is stored in a non-volatile memory. The stored error may be retrieved and deleted in the main menu.
Independent of the priority group, all errors found are indicated with their relevant number.
No. 21 Medium temperature too high
No. 10 Sensor not connected; or cable Check cable or replace sensor. between FC01-LQ and sensor defective; or defective sensor
No. 5 Internal controller error Return to supplier.
No. 4 Incorrect test sum of data memory Return to supplier.
No. 3 Incorrect test sum of program Return to supplier. memory
No. 2 Incorrect test sum of parameter Return to supplier. memory
No. 1 No system parameter available Return to supplier.
Sensor selected (configuration) Correct sensor selection in differs from sensor connected configuration menu

* Error No. 60 can only occur with version FC01-U1T4.
No. 41 Controller error (watchdog timer)
No. 40 Controller error (oscillator-watchdog)
No. 60 Assignment of quantity per pulse too low *
No. 30 Over limits of flow rate
No. 20 Medium temperature too low
Admissible EMC levels may have been exceeded
Admissible EMC levels may have been exceeded
Priority group III · Errors 47 · Error Cause Rectification

* DC 12 V possible if the FC01-LQ is used whithout option C1 (analogue outputs).
Power consumption may be up to 300 mA±10 % when analogue output C1 is fitted.
Admissible ripple: max. 20 % UV Rated current consumption: Ivnk = 170 mA with zero flow
8.2.1.1 DC voltage supply
8.2 Electrical characteristics
** The max. ambient temperature of +40 °C applies to all systems fitted with current output C1.
* Only if the modules are spaced by at least 10 mm.
rail-mounted surface mounted front panel mounted
Ivnk = 200 mA with max. flow (end of measuring range)
+U V 2
DC supply · 48 Technical data · shield 1

The output is reverse polarity protected.
* Shield ungrounded - apply on one side only.
Analogue output 2 - ANA OUT TEMP. (temperature output)
Analogue output 1 - ANA OUT FLOW (flow output)
Pin selection for analogue outputs V1, V2 and C1
The analogue outputs are physically isolated from each other as well as from the electronic control unit FC01-LQ.
analogue output - central electronic unit DC 500 V
NC - not used
reference ground 2 7
analogue output 2 - temperature 6
shield 2 * 5
shield 1 * 4
reference ground 1 3
analogue output 1 - flow rate 2
Signal name Pin XAO
Pn = 4.8 W max. flow (end of measuring range), voltage outputs
Technical data 49

8.4.1 Relay outputs R2 (DC or AC)
The signal outputs are physically isolated from each other as well as from the electronic control unit FC01-LQ.
Limit Switch 2 / N/C 8
Limit Switch 2 / common 7
Limit Switch 2 / N/O 6
Limit Switch 2 / Schirm 5
Limit Switch 1 / N/C 4
Limit Switch 1 / common 3
Limit Switch 1 / N/O 2
Limit Switch 1 / shield 1
50 Technical data

8.4.2 Transistor outputs (DC)
Inductive load - with safety circuit - AC voltage
max. leakage current ≤ 25 µA
Uce max = 60 V
Uce < 1 V at IC < 100 mA
Limit Switch 1 collector 8 +
Limit Switch 1 emitter 7 -
Limit Switch 2 collector 6 +
Limit Switch 2 emitter 5 -
/ BUSY / PULSE collector 4 +
/ BUSY / PULSE emitter 3 -
/ ERROR collector 2 +
/ ERROR emitter 1 -
signal contact - signal contact DC 500 V
Voltage level · Resistive load · Technical data 51

Capacitive load - C < 20 µF
Inductive load - L < 100 mH (DC voltage - without external safety circuit)
signal contact - signal contact DC 500 V
Resistive load · 52 Technical data

The flow measurement range is determined by the inner pipe diameter (see table). It can be calculated with the following equation:
Flow measurement ranges:
8.5.1.2 Monitoring head CSF
Flow rate measurement:
8.5.1.1 Monitoring head CSP- with sensor adapter type TP-..
Measuring is possible up to the flow rates indicated in the display range. However, the indi cated accuracy is no longer guaranteed. The repeatability value remains valid.
8.5 Metrological data
Sensor adapter Measuring range Display range type in m3/h in m3/h
TP05 0.14 … 13.6 18.1
TP04 0.1 … 8.7 11.6
TP03 0.05 … 5.3 7.1
TP02 0.04 … 3.4 4.5
TP01 0.02 … 2.2 2.9
AR [m2] - inner pipe cross-section
VN [m/h] - average standard velocity
Q = VN x AR Q [m3/h] - flow quantity
Technical data 53


Failure diagram for water
Setting range for internal pipe diameter: 50.0 mm … 999.9 mm
Inner pipe diamater Measuring range Display range D in mm in m3/h in m3/h
0.20 0.40 0.60 0.80 1.00 1.20 1.40 1.60 1.80 2.00 2.20 2.40 2.60 2.80 3.00 0

*** MB - measuring range
** MW - measured value
* MBE - of final value
Heating up period until full accuracy is reached: 15 min.
Technical data 55

* RTD = Resistive Temperature Device
8.6 Sensor interface
XSK10 R(Tdiff)-HI Function: terminal for positive pole of the heated RTD * Input resistance: > 1 GΩ Dielectric strength: -17 V … +30 V DC
XSK9 R(Tdiff)-LO Function: terminal for negative pole of the heated RTD * Input resistance: > 1 GΩ Dielectric strength: -17 V … +30 V DC
XSK6 IS Function: output of exitation current source for RTD * operation Exitation current: 1 mA ± 1% Admissible load range: Rload = 0 … 2 k⏐ Dielectric strength: ±15 V DC
XSK4 R(Tref)-LO Function: terminal for negative RTD * pole for medium temperature measurement Input resistance: > 1 GΩ Dielectric strength: -17 V … +30 V DC
XSK3 R(Tref)-HI Function: terminal for positive RTD * pole for medium temperature measurement Input resistance: > 1 GΩ Dielectric strength: -17 V … +30 V DC
XSK2 R(HEIZ)-HI Function: terminal for positive pole of heater element Hi-potential of heater source Output voltage range (load dependent) Ua = 21 V … 24 V DC Max. current output: Imax = 100 mA Not short-circuit proof
XSK1 R(HEIZ)-LO Function: terminal for negative pole of heater element Drain output of heating current control Max. sink current: Isink = 88 mA Dielectric strength: -0.5 V … +20 V DC
56 Technical data · Terminal Mnemonics Data

7 locking set 01 (for monitoring head CSF-11) 0Z122Z00024
6 ball valve BV
5 sensor adapter (screw-in or welding type) TP
4 calorimetric monitoring heads CSP / CSF
3 connecting cable for calorimetric monitoring head
2 front mounted housing FC01-LQ-ST
1 surface mounted housing FC01-LQ-FH
No. Accessory Ordering configuration
- Typ 18/ -60 °C … +200 °C non-halogenuous/highly flexible/paired
- Typ 15/ -10 °C … +80 °C highly flexible/paired
cable type LifYCY 4 x 2 x 0.2 mm 2 Do+Ka
Accessories 57







Appendix 1 - Performance of the digital and analogue outputs during the operating and error modes
NO ERROR NOT BUSY and
LIMIT SWITCH 2
FREQUENCY
ANA OUT
ANA OUT
OUTPUT
FLOW
TEMP.
ON
ON
ON
MAX
MAX
OFF
OFF
OFF
OFF
MIN
MIN
Error No. 1
OFF
OFF
OFF
MIN
MIN
Error No. 2
OFF
OFF
OFF
MIN
MIN
Error No. 3
OFF
OFF
OFF
MIN
MIN
Error No. 4
OFF
OFF
OFF
MIN
MIN
Error No. 5
OFF
OFF
OFF
MIN
MIN
OFF
OFF
ON
OFF
MIN
MIN
Normal duty
ON
ON
OFF
OFF
ON
OFF
MIN
MIN
OFF
OFF
ON
OFF
MIN
MIN
Error No. 10
OFF
OFF
OFF
MIN
MIN
Error No. 20
ON
Error No. 21
OFF
OFF
OFF
MIN
MIN
Error No. 30
ON
Error No. 60 *
FA
Error No. 40
ON
Error No. 41
ON
X = standard performance Y = OFF pulse FA = frequeny output 10 Hz
* When frequency output has been selected.




PERCENT (%) METRE/SEC (m/s) FEET/SEC (FPS) BLANK (no unit)
LS1 → F / LS2 → F LS1 → T / LS2 → F LS1 → F / LS2 → T LS1 → T / LS2 → T
CELSIUS (°C) FAHRENHEIT (°F) KELVIN (K)
TYPE CSP-11 WM1 TYPE CSP-11 WM1BV TYPE CSF-11 WM1 TYPE S-No. xxx
GALLONSϒ/MINUTE (GPM) LITRE (l) METRE3 (m3) GALLONS° (G)
BARGRAPH LITRE/SEC (l/s) LITRE/MIN (l/min) m3/HOUR (m3/h)
FREQUENCY OUTPUT? M →yes other → no
FREQUENCY OUTPUT PULSE/ (unit)
→ TYPE
return to configuration menu
nur bei gewählter Totalisatoreinheit
not available with sensor type CSP
call menu or delete function
select and return to configuration menu
DN25 (1 in) DN32 (1.1/4 in) DN40 (1.1/2 in) DN50 (2 in)
TP01 (1/2 in) TP02 (3/4 in) TP03 (1 in) TP04 (1 1/4 in) TP05 (1 1/2 in) TP06 (2 in)