506488-01 Page 1 Issue 1008 T ABLE OF CONTENTS SAFETY ............................................................... 2 INST ALLA TION .................................................... 2 ST AR T -UP .................................................
Page 2 506488-01 Issue 1008 INST ALLA TION These instructions must be hung on or near the furnace in a conspicuous place. These units are single p ackage air conditioners with gas heat designed for outdoor inst allation on a rooftop or a slab. The units are completely assembled.
506488-01 Page 3 Issue 1008 Location Use the following guidelines to select a suitable location for the unit. 1. Unit is designed for outdoor installation only . Unit must be installed so all electrical component s are protected from water . 2. Condenser coils must have an unlimited supply of air .
Page 4 506488-01 Issue 1008 Roof Curb Inst allation If a roof curb is used, follow the manufacturer ’s Inst allation Instructions and be sure that all required clearances are observed (see following Clearances section). Clearances All units require certain clearances for proper operation and service.
506488-01 Page 5 Issue 1008 a sidewalk, patio, or other walkway where the condensate could cause the surface to become slippery . The products of combustion must not be allowed to accumulate within a confined space and recirculate.
Page 6 506488-01 Issue 1008 Condensate Drain The PGE/SG package unit is equipped with a 3/4" FPT coupling for condensate line connection. Plumbing must conform to local codes. Use a sealing compound on male pipe threads. The condensate drain line must be properly trapped and routed to a suitable drain.
506488-01 Page 7 Issue 1008 The gas supply line should be routed through the grommet on the side of the unit. Refer to Figure 7 to locate this access opening. If local codes allow the use of a flexible gas appliance connector , always use a new listed connector .
Page 8 506488-01 Issue 1008 Check all connections for leaks when piping is completed, using a soapy solution. Some soaps used for leak detection are corrosive to cert ain metals.
506488-01 Page 9 Issue 1008 T ypical Wiring Connections Figure 8 RR C C Y Y W THERMOST A T OUTDOOR UNIT G G WITH ECONOMIZER C R R Y1 THERMOST A T OUTDOOR UNIT ECONOMIZER YELLOW W G G GREEN Y2 BLACK BLUE W W ORANGE (Not Used) WITHOUT ECONOMIZER L2 L1 POWER WIRING 208/230-1-60 (75°C MIN.
Page 10 506488-01 Issue 1008 ST ART -UP Pre-Start Check List Complete the following checks before starting the unit: 1. Check the type of gas being supplied. Be sure it is the same as listed on the unit nameplate. 2. Make sure that the vent hood has been properly installed.
506488-01 Page 11 Issue 1008 x 3600 x = Cubic Feet Per Revolution BTU/HR INPUT # Seconds Per Revolution Heating V alue For Natural Gas: Check the gas input rate by observing the gas meter , when available, making sure all other gas appliances are turned off.
Page 12 506488-01 Issue 1008 in the 10-second interval, then the ignition control will de-energize the gas valve. 4. The ignition control is designed to repeat this “trial for ignition” a total of three times.
506488-01 Page 13 Issue 1008 V ariable Speed Motor Units equipped with a variable speed circulation air blower motor will deliver a constant airflow within a wide range of external static pressures. Other features of this variable speed motor include: Sof t S t art/S top – The variable speed motor will slowly ramp up to normal operating speed.
Page 14 506488-01 Issue 1008 CONTROL SYSTEM DIAGNOSTICS Fault Codes T able 5 Out door Coil Dirt and debris should not be allowed to accumulate on the outdoor coil surface or other part s in the air circuit. Cleaning should be as often as necessary to keep coil clean.
506488-01 Page 15 Issue 1008 Figure 1 1 Connection Diagram Single Phase – PSC Motor.
Page 16 506488-01 Issue 1008 Figure 12 208/230V -1-60 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Y G W1 R C Y G W R C BLU GRN YEL WHT RED Y R C DIAGNOSTIC MODULE G Y.
デバイスAllied Air Enterprises 4PGEの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Allied Air Enterprises 4PGEをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAllied Air Enterprises 4PGEの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Allied Air Enterprises 4PGEの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Allied Air Enterprises 4PGEで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Allied Air Enterprises 4PGEを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAllied Air Enterprises 4PGEの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Allied Air Enterprises 4PGEに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAllied Air Enterprises 4PGEデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。