OWNER'S OPERA TING MANUAL Uninterruptible Power Supply Models: SG800-1, SG800-2 SG1K-1T , SG1K-2T SG2K-1T , SG2K-2T , SG2K-2TXI SG3K-1T , SG3K-2T , SG3K-2TX Det ailed SG Series product specifications are available in PDF format at www .falconup s.
SG UPS Features. ...... 1 SG Series Online UPS Block Diagram. .... 1 Import ant Safety Instructions (READ FIRST) .... 2 Chapter 1. SG Series UPS Overview ..... 3 T rue Regenerative Online Design .... 3 Input Power Factor Correction .... 3 Microprocessor Control .
SG SERIES UPS FEA TURES SG SERIES ON-LINE UPS SYSTEM BLOCK DIAGRAM T rue Double Conversion On-Line Design Input Power Factor Correction Wide Input V oltage W indow Pure Sinewave Output Precision Outpu.
IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS This manual contains import ant instructions which must be followed during the installation, operation and maintenance of this UPS and its batteries. Please read all instructions before operating this equipment and save this manual for future reference.
CHAPTER CHAPTER 1 1 SG Series UPS - Overview T rue Regenerative On-Line Design As new and innovative technologies have become the backbone of today's businesses, maxi- mum system availability is critical and downtime is more expensive than ever .
CHAPTER CHAPTER 2 2 INST ALLA TION INSTRUCTIONS 1. V erify the following is included in the UPS shipping carton: (1) UPS, (1) Software Diskette(s) & Manual, (1) Power Cord (800V A-1KV A models only), (1) Owners Manual & (1) UPS/Computer Cable.
5. For SG800 - SG1K models, connect the power cord to the UPS inlet located on the UPS rear panel. On SG1.5K - SG3K models the line cord is permanently att ached to the UPS. 6. Select a suitable location for the UPS near enough to the computer or equipment to to be protected.
DIP SWITCHES SELECTION TABLE ON = 1 OFF = 0 SW2 SW1 VOLTAGE Down Down 100V Down Up 110V Up Down 120V (Factory default) Up Up 115V SW2 SW1 VOLTAGE Down Down 220V Down Up 230V (Factory Default) Up Down .
TYPICAL EXTENDED BA TTER Y BANK & UPS INTERCONNECTION (Mini-tower models shown; same applies for floor st anding banks) INST ALLA TION PROCEDURE FOR EXTENDED BA TTERY BANKS 1. Remove the battery fuse located on the UPS rear panel. See illustration above.
BATTER Y OP TION MODEL S W/O C h a r ger SGB2S7-1K3 SGB4S7-1K3 SGB5S7-1K3 SG B10S7-1K 6 SG B10S7-1K 6 BATTER IES 6 Piece s 12V, 7AH 12 Piece s 12V, 7AH 15 Piece s 12V, 7AH 30 Piece s 12V, 7AH 60 Piece s 12V, 7AH BATTER IES IN UPS 3 each of 12V, 7A H # of CASES In c h e s (mm) 1 Mini-To w er 13.
9 CHAPTER CHAPTER 3 3 OPERA TION 1 2 3 4 5 6 7 8 9 10 11 UPS FRONT P ANEL INDICA TOR AND FUNCTION KEYS 1. LOAD LEVEL INDICA T OR LEDS *The first or bottom LED is lit when the output load is greater than 25% of the rated output of the UPS. *The second LED is lit when the output load is greater than 50% of the rated output of the UPS.
5. BYP ASS INDICA T OR LED When this LED is lit the UPS bypass is active. Should the Alarm LED be lit at the same time, the UPS detected an internal failure and the UPS must be serviced. 6. INVERTER INDICA T OR LED When this LED is lit, the UPS inverter is operating and powering the connected load.
AUDIBLE ALARMS Audible alarm signals are divided into two different levels of alarm st atus. Category one alarms represent normal or correctable operational alarms. Category two alarms are sounded in the event of abnormal operation. 1. Category one alarms : a.
OPTIONAL EXTERNAL BATTERY CONNECTOR OUTPUT RECEPTACLES (6 places without ex t ernal batter y option, 4 plac es as shown) COVER PLATE FOR OPTIONAL DIP SWITCHES RS- 232 CONNECTOR COOLING FAN DO NOT BLOC.
COVER PLATE FOR OPTIONAL SNMP AGENT DIP SWITCHES RS-232 CONNECTOR COOLING FANS DO NO BLOCK MAIN POWER SW ITCH & INPUT CIRCUIT BREA KER INPUT LINE CORD OUTPUT FUSE S (2 pl aces) OPUTPUT RECEPTACLES (6) NEMA 5 -15R STANDARD EXTERNAL BATTERY CONNECTOR COVER PLATE OTHER OUT PUT RECEPTACLE CONFIGURATIONS ARE AVAILABLE.
14 SG2K-2TXI & SG3K-2TX T ypical Rear Panel Overview COVER PLAT E FOR COMMUNICATIONS SLOT EX TE R NAL BA TTERY CONNECTOR COVER PLATE OUT PUT FUSES FO R THE TOP R ECE P T AC LE 208- 240V ac OUTPU T.
CHAPTER CHAPTER 5 5 COMMUNICA TIONS INTERF ACES RS-232 INTERF ACE 15 P in # Function explan ation I/O 9 RS 232 Rx INP UT 6 RS 232 Tx OUT PUT 7 Gr ound Location: The RS-232 interface is standard on all SG series UPS models. The port is located on the UPS rear panel, via a DB-9 female connector .
16 DR Y CONT ACT & OPTO COUPLER INTERF ACE BOARD OPTIONS JP1 JP2 JP3 J1 J2 J3 DB- 9 T ypical Falcon Dry Contact Relay Board PIN DESCRI PTION 1 Low Battery ( When UPS reaches low battery, c ontact acti vat es) (J1, 1-2 short = N.O) (J1, 2-3 short = N.
17 PIN ASSIGNMENT FOR THE F ALCON UA88373 OPTO-COUPLER OPTION BOARD (no-byp ass signal) PIN DESCRI PTIO N 1 Not Used 2 Uti lity Los s ( N.O.) ( C l os es upon ut i li t y loss) 3 Utili t y Loss (N.C.) ( O pens upon util it y loss) 4 Comm on for pins 2, 3 & 5 5 Lo w Batte ry (N .
APC Style Dry Cont act Relay Board PIN DESCRIPTION 1 Remote Shutdown (on battery operation only) 2 Remote Shut down Common 3 Not Used 4 Low Ba ttery Co m mon 5 Low Ba tte ry ( N .
CHAPTER CHAPTER 6 6 Maintenance & T echnical Support 1. Care & Maintenance Falcon ® SG Series UPSs are designed to be maintenance-free. They can be cleaned with a damp cloth or non-abrasive cleanser , providing the UPS is turned off and the input plug is disconnected from the utility source.
The following precautions should be observed by a qualified technician when working with batteries. 1. Remove watches, rings, or other met al objects. 2. Use tools with insulated handles. 3. W ear rubber gloves and boots. 4. Do not lay tools or met al parts on top of batteries.
6. T echnical Support Y our F ALCON ® Electric SG Series UPS is backed by one of the finest customer service teams assembled. Write, call, fax or email should you require technical assistance or service. Falcon Electric Inc. 5106 Azusa Canyon Road Irwindale, CA.
GENERAL PROVISIONS F ALCON® ELECTRIC INC., hereby warrants product shipped under this agreement to be free from defective workmanship for a period of two years following date of shipment. This Limited New Product W arranty Agreement only applies to covered repairs to the product occurring within the United S tates and Canada.
SG Series TM UPS PLUS ® 800VA to 1.5kVA Model Number SG800 -1T SG1K -1T SG1K - 2T SG1.5K -1T Nominal VA 800 1000 1000 1500 Electrical I nput Nominal AC Voltage 120V 120V 230V 120V AC Voltage Range 87- 140V 87-140V 170 -275V 87- 140V Current - Amps 5.
SG Series TM UPS PLUS ® 2kVA & 3kVA Electrical Input Nominal AC Voltage 120V 230V 120V 230V 230V AC Voltage Range 87 – 140V 170 – 275V 87 – 140V 170 – 275V 170 – 275V Current – Amps 14.2 7.4 21.4 11.2 7.5 11.3 Frequency 50/60 Hz ± 5% (Auto – Tracking) Power Factor Correction > 0.
デバイスFalcon SG2K-2TXIの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Falcon SG2K-2TXIをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはFalcon SG2K-2TXIの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Falcon SG2K-2TXIの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Falcon SG2K-2TXIで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Falcon SG2K-2TXIを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はFalcon SG2K-2TXIの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Falcon SG2K-2TXIに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちFalcon SG2K-2TXIデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。