Service Manual Service Manual F20, F40, F60, F85 & FCI20, FCI30, FCI40 FCI60, FCI85 Cube Ice Mak er Foster Refrigerator Oldmedow Road, King’s L ynn, Norfolk PE30 4JU England T el: 01553 691 122 Fax: 01553 691447 Website: www .fosterrefrigerator .
CONTENTS Page 1. General Information and Installation Instructions 2 1.1 Introduction 2 1.2 Unpacking and Inspection 2 1.3 Location and Leveling 2 1.4 W ater Supply and Drain Connections 2-3 1.5 Final Checklist 3 1.6 Installation Practice 3 2. F20 and F40 T echnical Data and Operating Instructions 4 3.
1. General Information and Installation Instructions 1.1 Introduction The Electronic Cubers are quality designed, engineered and manufactured. Their ice making systems are thoroughly tested providing the utmost in flexibility to fit the needs of a particular user .
fittings and a shut off valve installed in an accessible position between the water supply line and the unit. W A TER SUPPL Y - W A TER COOLED MODELS. The water cooled versions require two separate inlet water supplies on models 40 and 60, one to supply water for the ice production and one for the water cooled condenser .
2. F20 and F40 T echnical Data and Operating Instructions 2.1 T echnical Data Model F20 F40 Output – kg/24hr 19.5 34.5 Bin storage capacity – kg 6.5 15 Cubes per cycle 16 24 Cubes kg per cycle 0.28 0.42 Cycle time – minutes 20.7 17.5 Amps start/run 1 1Amps/2Amps 17Amps/3.
3. F60 and F85 T echnical Data and Operating Instructions 3.1 T echnical Data Model F60 F85 Output – kg/24hr 60 83 Bin storage capacity – kg 27 27 Cubes per cycle 48 48 Cubes kg per cycle 0.84 0.84 Cycle time – minutes 19.0 15.5 Amps start/run 19/4.
I. The machine may stop working if the condenser temperature exceeds the pre-set temperature of the Over T emperature Thermostat (non- adjustable) due to a very high ambient temperature, condenser fan failure, dirty/ blocked condenser. T o restart the machine, depress the protruding button on the Alarm Reset.
F20 & F40 A/W Wiring Diagram 7 the service and inspection operations. IN OPERA TION: The unit is running through the freezing and defrost cycle stopping automatically only at full bin situation.
4. T echnical Specification - R22 Machines MODEL FCI 20 FCI 30 FCI 40 FCI 60 FCI 85 Output – kg/24hr . 18 (20.5) 26 (34) 34 (42) 57 (70) 78 (90) Bin storage capacity – kg 6.5 15 15 27 27 Cubes per cycle 16 24 24 48 48 kg per cycle 0.28 (0.38) 0.42 (0.
COMPRESSOR, W A TER INLET SOLENOID V AL VE, HOT GAS V AL VE NOTE: The length of the defrost cycle is (non-adjustable) automatically determined by the microprocessor of The P .C. BOARD in relation to the time T2 necessary for the unit to reduce the evaporator temperature from 0˚C (35˚F) to -1 3˚C (8.
7. The DIP . SWITCH keys setting is made in consideration of the model and of the type of condenser used (air or water cooled). In T able B, page 12, are indicated the various lengths of the third portion of freezing cycle (T ime mode) in accordance with the different combinations of the DIP .
B. ICE BIN LEVEL SENSOR The ice bin level temperature sensor , secured to one of the storage bin walls, stops the operation of the entire ice maker at the end of the defrost cycle when its sensing probe (in contact with the stored ice) reaches the temperature of +2˚C (35˚F) lighting up, in the meantime, the third RED LED.
7. Dip Switch Positions DIP SWITCHES FCI 20 FCI 30 FCI 40 FCI 60 FCI 85 1 ON ON ON ON ON 2 OFF OFF OFF OFF OFF 3 ON OFF ON ON ON 4 OFF OFF OFF ON ON 5 ON ON ON ON ON 6 OFF OFF OFF OFF OFF 7 ON ON ON O.
7. Dip Switch Positions DIP SWITCHES FCI 20 FCI 30 FCI 40 FCI 60 FCI 85 1 ON ON ON ON ON 2 OFF OFF OFF OFF OFF 3 ON OFF ON ON ON 4 OFF OFF OFF ON ON 5 ON ON ON ON ON 6 OFF OFF OFF OFF OFF 7 ON ON ON O.
B. ICE BIN LEVEL SENSOR The ice bin level temperature sensor , secured to one of the storage bin walls, stops the operation of the entire ice maker at the end of the defrost cycle when its sensing probe (in contact with the stored ice) reaches the temperature of +2˚C (35˚F) lighting up, in the meantime, the third RED LED.
7. The DIP . SWITCH keys setting is made in consideration of the model and of the type of condenser used (air or water cooled). In T able B, page 12, are indicated the various lengths of the third portion of freezing cycle (T ime mode) in accordance with the different combinations of the DIP .
COMPRESSOR, W A TER INLET SOLENOID V AL VE, HOT GAS V AL VE NOTE: The length of the defrost cycle is (non-adjustable) automatically determined by the microprocessor of The P .C. BOARD in relation to the time T2 necessary for the unit to reduce the evaporator temperature from 0˚C (35˚F) to -1 3˚C (8.
4. T echnical Specification - R22 Machines MODEL FCI 20 FCI 30 FCI 40 FCI 60 FCI 85 Output – kg/24hr . 18 (20.5) 26 (34) 34 (42) 57 (70) 78 (90) Bin storage capacity – kg 6.5 15 15 27 27 Cubes per cycle 16 24 24 48 48 kg per cycle 0.28 (0.38) 0.42 (0.
F20 & F40 A/W Wiring Diagram 7 the service and inspection operations. IN OPERA TION: The unit is running through the freezing and defrost cycle stopping automatically only at full bin situation.
I. The machine may stop working if the condenser temperature exceeds the pre-set temperature of the Over T emperature Thermostat (non- adjustable) due to a very high ambient temperature, condenser fan failure, dirty/ blocked condenser. T o restart the machine, depress the protruding button on the Alarm Reset.
3. F60 and F85 T echnical Data and Operating Instructions 3.1 T echnical Data Model F60 F85 Output – kg/24hr 60 83 Bin storage capacity – kg 27 27 Cubes per cycle 48 48 Cubes kg per cycle 0.84 0.84 Cycle time – minutes 19.0 15.5 Amps start/run 19/4.
2. F20 and F40 T echnical Data and Operating Instructions 2.1 T echnical Data Model F20 F40 Output – kg/24hr 19.5 34.5 Bin storage capacity – kg 6.5 15 Cubes per cycle 16 24 Cubes kg per cycle 0.28 0.42 Cycle time – minutes 20.7 17.5 Amps start/run 1 1Amps/2Amps 17Amps/3.
fittings and a shut off valve installed in an accessible position between the water supply line and the unit. W A TER SUPPL Y - W A TER COOLED MODELS. The water cooled versions require two separate inlet water supplies on models 40 and 60, one to supply water for the ice production and one for the water cooled condenser .
デバイスFoster F20の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Foster F20をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはFoster F20の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Foster F20の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Foster F20で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Foster F20を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はFoster F20の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Foster F20に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちFoster F20デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。