R-410A Models Service Manual 2 0 1 1 HG-ServMan (1-1 1) SH15M30 * SH20M30 * Cool Only H a z a r d o u s D u t y R o o m A i r C o n d i t i o n e r * Last character may vary .
T able Of Contents Important Safety Information ..................................................................................................................... 2-4 Introduction ....................................................................
IMPORT ANT SAFETY INFORMA TION The information contained in this manual is intended for use by a qualifi ed service technician who is familiar with the safety procedures required for installation and repair , and who is equipped with the proper tools and test instruments required to service this product.
• Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel, and sleeve on the room side of the air conditioning unit while cleaning.
PROPERTY DAMAGE HAZARDS FIRE DAMAGE HAZARDS: • Read the Installation/Operation Manual for this air conditioning unit prior to operating. • Use air conditioner on a single dedicated circuit within the specifi ed amperage rating. • Connect to a properly grounded circuit only .
Serial Number Decade Manufactured L=0 C=3 F=6 J=9 A=1 D=4 G=7 B=2 E=5 H=8 A A A R 00001 Production Run Number Y ear Manufactured A=1 D=4 G=7 K=0 B=2 E=5 H=8 C=3 F=6 J=9 Product Line R = RAC Month Manu.
U L L i st e d fo r u s e i n C l as s I , D i v i s i o n 2 , G ro u p s A , B , C a n d D h a z a rd o u s lo ca t i o n s . Ha za rdga rd i s s pe c i cal ly d es ig ne d t o coo l l iv in g q u.
SPEC IF IC A TIONS AND PERFORMA NCE D A T A 7 Due to c on tinui ng eng inee rin g res earc h and te chn olo gy , spe c L ¿ c ati ons ar e subje ct to c han ge wit hou t noti ce. M anuf actu red un der U.S. D esi gn Patent DES 3 68 , 30 6 de co rat ive fro nt; Ut ilit y Pate nt 5, 62 2, 05 8.
ELECTRICAL D A T A ELECTRICAL REQUIR EME NTS ELECTRIC SHOCK HAZARD W ARNING Tur n of f el e c tr i c p ow e r be f o re s e rv i c e o r installation. All el ec tri cal con ne ct io ns an d wiri ng MU.
Permanent Split-Capacitor , totally enclosed fan motor to assure effi cient operation even under adverse electrical conditions. Motor has a special stainless steel shaft to resist corrosion and a hermetically sealed overload for arc-free operation. High capacity compressor with internal hermetically sealed overload.
COMPONENT DEFINITIONS A. Mechanical components B. Electrical components C. Hermetic components Plenum assembly Dif fuser with directional louvers used to direct the conditioned airfl ow .
F AN MOTOR SWITCH, ON-OFF Line side SOLID ST A TE RELA Y Load side LED indicates contacts closed when lit F AN MOTOR A 230 volt single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A running capacitor is wired across the start and run terminals of the motor .
RANGE: Thermostat (Part No. 618-225-02) 60 ° F ( ± 2 ° ) to 90 ° F( ± 4 ° ) SENSING BULB LOCA TION THERMOST A T A cross ambient thermostat is used to maintain the desired comfort level. The thermostat reacts only to a change in temperature at the bulb location.
• R-410A pressure is approximately 60% higher than R-22 pressure. • R-410A cylinders must not be allowed to exceed 125 F , they may leak or rupture.
Proper refrigerant charge is essential to proper unit operation. Operating a unit with an improper refrigerant charge will result in reduced performance (capacity) and/or effi ciency . Accordingly , the use of proper charging methods during servicing will insure that the unit is functioning as designed and that its compressor will not be damaged.
3. Install a process tube to sealed system. 4. Make necessary repairs to system. 5. Evacuate system to 200 microns or less. 6. Weigh in refrigerant with the proper quantity of R-410A refrigerant. 7. Start unit, and verify performance. 8. Crimp the process tube and solder the end shut.
Underchar ged R efrigerant Systems An undercharged system will result in poor performance (low pressures, etc.) in both the heating and cooling cycle. Whenever you service a unit with an undercharge of refrigerant, always suspect a leak. The leak must be repaired before charging the unit.
R estricted R efrigerant System T roubleshooting a restricted refrigerant system can be diffi cult. The following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions.
Lock ed Rotor V oltage (L.R.V .) T est Locked rotor voltage (L.R.V .) is the actual voltage available at the compressor under a stalled condition. Single Phase Connections Disconnect power from unit.
Many compressor failures are caused by the following conditions: 1. Improper air fl ow over the evaporator . 2. Overcharged refrigerant system causing liquid to be returned to the compressor . 3. Restricted refrigerant system. 4. Lack of lubrication.
3. After all refrigerant has been recovered, disconnect suction and discharge lines from the compressor and remove compressor . Be certain to have both suction and discharge process tubes open to atmosphere. 4. Carefully pour a small amount of oil from the suction stub of the defective compressor into a clean container .
R OUTINE MAINTENANCE AIR FIL TER Clean the unit air intake fi lter at least every 300 to 350 hours of operation. Clean the fi lters with a mild detergent in warm water and allow to dry thoroughly before reinstalling.
Discharge Air Plenum Slot T ab Latches Return air grille Latch Slot T ab Return Air Grille R OUTINE MAINTENANCE (Continued) Do not drill holes in the bottom of the drain pan or the underside of the unit.
ROOM AIR CONDITIONER UNIT PERFORMANCE TEST D A T A SHEET DA TE: _______________ MODEL:_______________ SERIAL:________________ YES NO IS THERE A FRIEDRICH SLEEVE INST ALLED? ____ ____ IS THERE A CHASSI.
TROUBLESHOO TING Problem Possible Cause Possible Solution Possible Solution Possible Solution Possible Solution Possible Solution Unit does not run Power disconnected. Check power source. Branch circuit fuse blown or circuit breaker tripped. Replace fuse, reset breaker .
Problem Possible Cause Possible Solution Possible Solution Possible Solution Compressor attempts to start, or runs for short periods only . Cycles on overload. Compressor attempts to start before system pressures are equalized. Allow a minimum of 3 minutes to allow pressures to equalize before attempting to start.
Problem Possible Cause Possible Solution Possible Solution Possible Solution Possible Solution Fan motor does not run. Defective switch (On-Off) Check continuity across terminals 2 and 3. Fan capacitor open. T est with capacitor analyzer . Replace if bad.
ELECTR OMECHANICAL CONTR OL COOL ONL Y MODELS: SH15M30 * SH20M30 * 27 * Last character may vary ..
Friedrich Air Conditioning Company 10001 Reunion Place, Suite 500 San Antonio, TX 78216 1-800-541-6645 www .friedrich.com HAZARDGARD ® ROOM AIR CONDITIONERS LIMITED W ARRANTY LIMITED ONE YEAR P ARTS W ARRANTY 1.
TECHNICAL SUPPORT CONT ACT INFORMA TION 29 FRIEDRICH AIR CONDITIONING CO. 10001 Reunion Place, Ste. 500, San Antonio, TX 78216 (210) 546-0500 877-599-5665 x 261 F AX (210) 546-0731 Email: tac@friedrich.
.
HG-ServMan (1-1 1) FRIEDRICH AIR CONDITIONING CO. 10001 Reunion Place, Ste. 500, San Antonio, TX 78216 P 210-546-0500 | F 210-546-0731 www .friedrich.com Printed in the U.
デバイスFriedrich R-410Aの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Friedrich R-410Aをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはFriedrich R-410Aの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Friedrich R-410Aの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Friedrich R-410Aで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Friedrich R-410Aを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はFriedrich R-410Aの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Friedrich R-410Aに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちFriedrich R-410Aデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。