AMERICA’S BEST AIR CONDITIONER 2002 HAZARDGARD ® ROOM AIR CONDITIONER Service & Parts Manual Models SH14J30B-A SH20J30B-A HG2002 (02/02).
2 T ABLE OF CONTENTS Specifications ................................................................................................................. ... 3 Performance Data ..............................................................................
3 * Rating Conditions: 80 ° F . Room Air T emperature and 59% Relative Humidity with 95 ° F . Outside Air T emperature at 40% Relative Humidity . PERFORMANCE EV APORA T OR AIR OPERA TING ELECTRICAL R-22 COMP . DA T A * TEMP° F PRESSURES RATINGS REFRIG.
4 COMPRESSOR WINDING TEST (See Figure 2.) Remove the compressor terminal box cover and disconnect the wires from the terminals. Using an ohmmeter , check continuity across the following: DISCONNECT EL.
5 F AN MOTOR (Figure 4) A 230 volt single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A running capacitor is wired across the start and run terminals of the motor . The motor is totally enclosed and is protected with a line voltage overload located internally of the motor .
6 RED DOT RUN CAP ACIT OR FA N MOT OR COMPRESSOR FIGURE 6 RUN CAP ACITOR HOOK–UP CAP ACIT OR, RUN A run capacitor is wired across the auxiliary and main winding of a single phase permanent split capacitor motor such as the compressor and fan motors.
7 Note: The temperature must be within the range listed to check the thermostat. Refer to the troubleshooting section in this manual for additional information on thermostat testing. TEST Remove the wires from the thermostat. T urn the thermostat to its coldest position.
8 LOW AMBIENT BY–P ASS V AL VE The HazardGard unit is designed to operate at low outside ambient temperatures. This is accomplished by the use of a bypass valve installed in the refrigeration circuit. The valve is connected between the discharge line at the compressor and the suction process tube.
9 10 . Evacuate the system to an absolute holding pressure of 200 microns or less. NOTE: This procedure can be speeded up by the use of heat lamps, or by breaking the vacuum with refrigerant or dry nitrogen at 5,000 microns. Pressure system to 5 PSIG and leave in the system a minimum of 10 minutes.
10 NOTE: All inoperative compressors returned to Friedrich must have all lines properly plugged with the plugs from the replacement compressor . REFRIGERANT CHARGE 1. The refrigerant charge is extremely critical. Measure the charge carefully and as exactly as possible to the nameplate charge.
11 PROBLEM POSSIBLE CAUSE TO CORRECT Unit does not run. PROBLEM POSSIBLE CAUSE TO CORRECT Dirty Filter . Restricted air flow . Inoperative thermostat. Short of refrigerant. Partially restricted capillary . Inoperative fan motor . Evaporator coil freezes up.
12 PROBLEM POSSIBLE CAUSE T O CORRECT Compressor attempts to start, or runs for short periods only . Cycles on overload. Allow a minimum of two (2) minutes to allow pressures to equalize before attempting to start. Check voltage with unit operating. Check for other appliances on the circuit.
13 PROBLEM POSSIBLE CAUSE T O CORRECT Replace selector switch. Replace relay . Selector Switch Relay PROBLEM POSSIBLE CAUSE T O CORRECT Refer to Installation Instructions for proper installation. Adjust motor mount to attain proper fan blade and blower wheel clearance.
14 WIRING DIAGRAM FOR SH14J30B-A & SH20J30B-A.
15 HazardGard Cabinet Parts.
16 HazardGard Chassis Parts.
17 HAZARDGARD P ARTS LIST REF . P ART NO. DESCRIPTION APPLICA TION SS HH 12 40 JJ 33 00 BB -- AA 1 61 1-935-49 Compressor , T ecumseh, 230/208V; 60 Hz 1 Ph, Model A WG5515EXN ...................... 1 1 1 61 1-935-50 Compressor , T ecumseh, 230/208 V ; 60 Hz 1 Ph, Model AWG5519EXN .
18 HAZARDGARD P ARTS LIST REF . P ART NO. DESCRIPTION SS HH 12 40 JJ 33 00 BB -- AA APPLICA TION 14 618-028-02 Partition, Control Box ............................................................................................. ............ 1 1 4 618-043-02 Partition, Control Box .
19 * 618-092-00 Lever , Fresh Air & Exhaust .................................................................................................. 1 1 * 618-062-00 Connector , Louver ....................................................................
20 Friedrich Air Conditioning Co. 4200 North Pan Am Expressway P .O. Box 1540, San Antonio, T exas 78295-1540, USA T el. (210) 357/4400 Fax: (210) 357/4480 Printed in the U.
デバイスFriedrich SH14J30B-Aの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Friedrich SH14J30B-Aをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはFriedrich SH14J30B-Aの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Friedrich SH14J30B-Aの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Friedrich SH14J30B-Aで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Friedrich SH14J30B-Aを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はFriedrich SH14J30B-Aの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Friedrich SH14J30B-Aに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちFriedrich SH14J30B-Aデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。