FriedrichメーカーXQ05M10の使用説明書/サービス説明書
ページ先へ移動 of 47
Service Manual R-410A Models R o o m A i r C o n d i t i o n e r s 2 0 1 1 Cool Only Cool with Electric Heat X-Star-ServMan (1-1 1) 1 15-V olt: XQ05M10 * , XQ06M10 * , XQ08M10 * , XQ10M10 * 1 15-V olt: EQ08M1 1 * * Last character may vary . M one y F a n Se t H r .
1 T able Of Contents Important Safety Information .......................................................................................................................................... 2-4 Unit Identifi cation ....................................
IMPORT ANT SAFETY INFORMA TION The information contained in this manual is intended for use by a qualifi ed service technician who is familiar with the safety procedures required for installation and repair , and who is equipped with the proper tools and test instruments required to service this product.
• Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel, and sleeve on the room side of the air conditioning unit while cleaning.
PROPERTY DAMAGE HAZARDS FIRE DAMAGE HAZARDS: • Read the Installation/Operation Manual for this air conditioning unit prior to operating. • Use air conditioner on a single dedicated circuit within the specifi ed amperage rating. • Connect to a properly grounded outlet only .
Serial Number Decade Manufactured L=0 C=3 F=6 J=9 A=1 D=4 G=7 B=2 E=5 H=8 A A A Y 00001 Production Run Number Y ear Manufactured A=1 D=4 G=7 K=0 B=2 E=5 H=8 C=3 F=6 J=9 Product Line X-Start Month Manu.
PERF ORM ANCE DA T A * Installation Inf ormation / Sl eev e Dimensions * Min imum exte nsi ons w hen m oun ted in a w ind ow. ** M ini mum w idt hs ac hi eved usi ng on e si de cu r ta in as sem bly as opp ose d to bo th in a s tan dar d inst al lat ion.
ELECTRICAL D A T A ELECTRIC SHOCK HAZARD W ARNING Tur n of f el e c t ri c p ow e r b ef o r e s e r v ic e o r installation. All el ect ri cal con ne ct io ns an d wiri ng MUS T be in sta ll ed b y a qu al ifi e d el ec tr ic i an a nd co n f or m to th e Na tio n al Ele ct rica l Cod e an d al l lo cal code s wh ic h h a v e j u ris d ict io n .
ELECTRICAL SHOCK HAZARD W ARNING Make sure your electrical receptacle has the same configuration as your air conditioner’s plug. If different, consult a Licensed Electrician. Do not use plug adapters. Do not use an extension cord. Do not remove ground prong.
T o st a r t u n i t s i t i , e l c a t p e c e r r e p o r p a o t n i d e g g u l p d n a d e l l a t s n i s i r e n o i t i d n o c r i a r u o y f I rea dy t o go . The firs t tim e the u ni t i s sta rted , the co mpr ess or wi ll d el ay f or t hre e minut es.
T o s e t t h e t i m e r NOTE: Y ou can set the ST ART and STOP times a mini mum of one ho ur apart, and a maximum of 23 hours apart. 9 TIMER ST AR T - Press Star t . g n i l o o c r o f e m i t t r a t s t n e r r u c e h t w e i v o t Continue pressing the Star t button until you arrive at the start time you desi re.
MODE CONTROL The mode control pad(s) allow the selection of the operating modes of the unit. There is a two second delay before the mode activates its appropriate relay .
ME C HANI C AL C OMPON EN TS P len um asse mb ly Diffu se r wit h di r ect i on al lou v ers us e d to di r ec t th e co n di ti one d a ir fl o w . Bl ow er wh eel A ttac he s to th e in d oo r sid .
13 TESTING THE ELECTRONIC CONTROL BOARDS FOR XQ MODELS Activating T est Mode: Activate test mode by pressing at the same time the “MODE” button and the “TEMP ” button on XQ models . LEDs for Hour , Start, and Stop will blink 1 bps while T est Mode is active.
TEST : 1 . Remov e leads from ther mostat . 2. Tu r n t h e r m o s t a t k n o b c l o c k w i s e t o i t s c o l d e s t position. 3. T est for continuity between t he t wo terminals. Contacts should be clos ed. 4. T urn thermost at knob counterclo ck wise to its warmest position.
CAP ACIT ORS ELECTRIC SHOCK HAZARD W ARNING T urn off electric power before servicing. Discharge capacitor with a 20,000 Ohm 2 W att resistor before handling. Failure to do so may result in personal injury , or death. Many motor capacitors are internally fused.
HEA TING ELEMENT (See Figure) All elect ric heat mod els are equi ppe d with a heat ing e lem ent . The EQ08 has a 1.15 KW element. The heating element contains a fuse link and a heater limit switch.
Suction Line Evaporator Coil Metering Device Refrigerant Strainer Discharge Line Condenser Coil Compressor Refrigerant Drier Liquid Line A good understanding of the basic operation of the refrigeration system is essential for the service technician.
• R-410A pressure is approximately 60% higher than R-22 pressure. • R-410A cylinders must not be allowed to exceed 125 F , they may leak or rupture.
Proper refrigerant charge is essential to proper unit operation. Operating a unit with an improper refrigerant charge will result in reduced performance (capacity) and/or effi ciency . Accordingly , the use of proper charging methods during servicing will insure that the unit is functioning as designed and that its compressor will not be damaged.
3. Install a process tube to sealed system. 4. Make necessary repairs to system. 5. Evacuate system to 200 microns or less. 6. Weigh in refrigerant with the property quantity of R410-A refrigerant. 7. Start unit, and verify performance. 8. Crimp the process tube and solder the end shut.
Underchar ged R efrigerant Systems An undercharged system will result in poor performance (low pressures, etc.) in both the heating and cooling cycle. Whenever you service a unit with an undercharge of refrigerant, always suspect a leak. The leak must be repaired before charging the unit.
R estricted R efrigerant System T roubleshooting a restricted refrigerant system can be diffi cult. The following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions.
Lock ed Rotor V oltage (L.R.V .) T est Locked rotor voltage (L.R.V .) is the actual voltage available at the compressor under a stalled condition. Single Phase Connections Disconnect power from unit.
Single Phase Resistance T est Remove the leads from the compressor terminals and set the ohmmeter on the lowest scale (R x 1). T ouch the leads of the ohmmeter from terminals common to start (“C” to “S”). Next, touch the leads of the ohmmeter from terminals common to run (“C” to “R”).
R ecommended procedure for compr essor replacement 1. Be certain to perform all necessary electrical and refrigeration tests to be sure the compressor is actually defective before replacing. 2. Recover all refrigerant from the system though the process tubes.
1. 2. 3. 4. 5. ELECTRIC SHOCK HAZARD W ARNING T urn off electric power before service or installation. Failure to do so may result in personal injury , or death. S e al e d R e f ri ge r a t io n Sy s t e m c o nt a i n s r e fr ig e r a nt a n d o i l u nd e r hi g h pr e s s ur e.
R OUTINE MAINTENANCE AIR FIL TER Clean the unit air intake fi lter at least every 300 to 350 hours of operation. Clean the fi lters with a mild detergent in warm water and allow to dry thoroughly before reinstalling.
SLEEVE / DRAIN Inspect the sleeve and drain system periodically (at least yearly or bi-yearly) and clean of all obstructions and debris. Clean both areas with an antibacterial and antifungal cleaner . Rinse both items thoroughly with water and ensure that the drain outlets are operating correctly .
29 29 Due to variations in room design, climate zone and occupancy , larger areas may require the use of multiple units to provide the optimal cooling solution. This is a general guide. Please consult manual J or M for exact load calculations. 1. If heavily shaded, reduce capacity 10%.
Problem Possible Cause Possible Solution Unit does not operate. The unit is turned to the off position, T urn the unit to the on position and raise or lower temperature setting (as appropriate) to call for operation. The LCDI power cord is unplugged. Plug into a properly grounded 3 prong receptacle.
Unit Does Not Cool/Heat On And Off T oo Frequently (continued). The outside temperature is below 60° F (16° C). Do not try to operate your air conditioner in the cooling mode when the outside temperature is below 60° F (16° C). The unit will not cool properly , and the unit may be damaged.
COOLING ONL Y ROOM AIR CONDITIONERS: TR OUBLESHOO TING TIPS n o i t c A e s u a C e l b i s s o P m e l b o r P Compressor does not run Low voltage Check voltage at compressor . 1 15V & 230V units will operate at 10% voltage variance T -stat not set cold enough or inoperative or electronic control board is bad Set t-stat to coldest position.
COOLING ONL Y ROOM AIR CONDITIONERS: TR OUBLESHOO TING TIPS n o i t c A e s u a C e l b i s s o P m e l b o r P Unit does not run Fuse blown or circuit tripped Replace fuse, reset breaker .
COOLING ONL Y ROOM AIR CONDITIONERS: TR OUBLESHOO TING TIPS n o i t c A e s u a C e l b i s s o P m e l b o r P Compressor runs for short periods only .
COOLING ONL Y ROOM AIR CONDITIONERS: TR OUBLESHOO TING TIPS n o i t c A e s u a C e l b i s s o P m e l b o r P W ater “spitting” into room Sublimation: When unconditioned saturated, outside air m.
HEA T / COOL ONL Y R OOM AIR CONDITIONERS: TR OUBLESHOO TING TIPS n o i t c A e s u a C e l b i s s o P m e l b o r P Roo m t empe rat ure une ven (He ati ng cycl e) Hea t a ntic ipa tor (r esi sto r) s hor ted (o n a ppl icab le mod els ) Dis con nec t po wer to un it.
37 ELECTR ONIC CONTR OL COOL ONL Y MODELS: XQ05M10 * XQ06M10 * XQ08M10 * XQ10M10 * * Last character may vary ..
38 ELECTR OMECHANICAL CONTR OL COOL WITH ELECTRIC HEA T MODEL: EQ08M11 * * Last character may vary ..
4 INSTRU CTIONS F OR USING COOLING LO AD ESTIMA TE F ORM FOR R OOM AIR CONDITIONERS (AHAM PUB. NO. RAC-1) A. This cooling load estimate form is suitable for estimating the cooling load for comfort air conditioning installations which do not require specifi c conditions of inside temperature and humidity .
5 COOLING L O AD ESTIMA TE F ORM HEA T GAIN FROM 1. WINDOWS: Heat gain from the sun. Northeast East Southeast South Southwest West Northwest North 2. WINDOWS: Heat by conduction (T otal of all windows.) Single glass Double glass or glass block 3. W ALLS: (Based on linear feet of wall) a.
6 F ol lo wi ng is a n e x amp le u si ng the h eat loa d form: A sp ace to be con dit i on e d is pa rt o f a ho u se geo gr ap hica l ly lo ca t ed in a n are a wh er e th e lo w es t ou tdo or a mb i en t wi n t er te mpe ra tur e is 40° F . Th e cal cu l at ed h e at lo ss i s 1 84 B TU/ Hr .
7 HEA TING LOAD FORM FRIEDRICH ROOM UNIT HEA T PUMPS BTU/HR PER W ALLS: (Linear Feet) °F TEMP . DIFFERENCE 2” Insulation Lin. Ft. x 1.6 A verage Lin. Ft. x 2.6 WINDOWS & DOORS (Area, sq. ft.) Single Glass: Sq. Ft. x 1.13 Double Glass: Sq. Ft. x 0.
43 Frie dr ic h Ai r Con di t ion in g Com pa ny 10001 Reunion Place, Suite 500 San A nton io, T X 78216 1-800-541-6645 ww w .fried rich.com R OOM AIR CONDI TIONER S LIMITED W ARR ANT Y FIRST YEA R AN.
TECHNICAL SUPPORT CONT ACT INFORMA TION 44 FRIEDRICH AIR CONDITIONING CO. 10001 Reunion Place, Ste. 500, San Antonio, TX 78216 (210) 546-0500 877-599-5665 x 261 F AX (210) 546-0731 Email: tac@friedrich.
.
X-Star-ServMan (1-1 1) FRIEDRICH AIR CONDITIONING CO. 10001 Reunion Place, Ste. 500, San Antonio, TX 78216 P 210-546-0500 | F 210-546-0731 www .friedrich.
デバイスFriedrich XQ05M10の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Friedrich XQ05M10をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはFriedrich XQ05M10の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Friedrich XQ05M10の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Friedrich XQ05M10で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Friedrich XQ05M10を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はFriedrich XQ05M10の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Friedrich XQ05M10に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちFriedrich XQ05M10デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。