GE Digital Energy Power Quality Installation Guide Digital Energy™ SNMP / WEB ADAPTER P/N 1018959 3-ph SNMP/Web plug-in adapter P/N 1019070 1-ph SNMP/Web plug-in adapter P/N 23954 SP SNMP/Web plug-i.
Model: 3-ph SNMP/Web plug-in adapter 1-ph SNMP/Web plug-in adapter SP SNMP/Web plug-in adapter 1-ph SNMP/Web external adapter Date of issue: 13.05.2008 File name: ISG_CN T_SNM_BAS_CRD_V012 Revision: 1.2 Identification N o. P/N 1018959 P/N 1019070 P/N 23954 P/N 1019071 Up-dating Revision Concerns Date 1.
Dear Customer , We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE . We trust that the use of the SNMP/Web adapters for our Uninterruptible Power Supply systems, developed and produced to the highest standards of quality, will give you complete satisfaction.
Table of contents Page 1 SAFETY RULES ............................................................................................................................... .................. 5 1.1 WARNINGS AND CAUTIONS ......................................
1 SAFETY RULES With this document, GE gives to the user all the necessary inform at ion about the correct insta llation of the SNMP/Web adapters. Please read carefu lly this Instal lation Manual before installing or operating the adapters. We recommend that this manual be kept next to the UPS for future references.
1.1 WARNINGS AND CAUTIONS GENERAL • Always strictly observe the “ UPS Sa fety Rules ” • Check carefully the integ r ity of the equipment. In case you note some visible damage, do no t install the equipment but contact the nearest Se rvice Centre .
ENVIRONMENT • Please take care of packaging mate rial: either save it f or later use or recy cle/dispose in compliance with local and other applicable regulations. • The SNMP/Web adapt ers contain a removab le, Lithiu m coin-c ell bat tery . Dispose of used batteries in compliance with local and other applicable regulations.
1.2 EMC COMPATIBILITY 1-ph SNMP/Web plug-in adapter (P/N 1019070) 1-ph SNMP/Web external adapter (P/N 1019071) This device has been tested for co mpliance with the following standards: • EN 61000-6-.
2 INTRODUCTION 2.1 CHECKING PACKAGE CONTENTS The SNMP/Web adapters are delivered in d i fferent kits accord ing to the model. 3-ph SNMP/Web plug-in adapter (P/N 1018959) • 3-ph SNMP/Web plug-in adap.
• Third Party License ReadMe • CD-ROM AC ada p ter Serial cable 2.2 OVERVIEW 3-ph SNMP/Web plug-in adapter (P/N 1018959) LP 33 Series UPS SitePro / SG Series UPS Reset RS-232 UTP 10/100 Active LAN.
• 1 – RJ45 Connector Ethernet connection, 10Base-T or 100Base-TX • 2 – LEDs Ref. specific section • 3 – RS-232 port Local console connection (115200-N-8-1) • 4 – Reset b utton HW reset.
LEDs The various front panel LEDs have the following meaning: • LAN / Netlink Status Meaning Off No LAN connection detected LAN connection establishe d, no communication On LAN connection establishe.
2.5 ADDITIONAL DOCUMENTS The SNMP/Web adapter is provided with a CD-ROM containing the following documentation: • Installation Manual • Operating Manual • SNMP Management Information Base (MIB) • Release notes and other in structions, as applicable Modifications reserv ed Page 13/24 ISG_CNT_SNM_BAS_CRD_1GB_V012.
3 INSTALLATION NOTE ! Strictly observe the ‘ UPS Safety Rules ’. Read carefully the UPS ‘ Operating Manual & Installation Guide ’ before installing or operating the equipm ent. If any problems are encounte red with the installation procedure here described, please contact the nearest Service Centre before proceeding.
Modifications reserv ed Page 15/24 ISG_CNT_SNM_BAS_CRD_1GB_V012.doc Installation Guide SNMP/Web Ada pter 3.1.2 Installing the SNMP Card in option slot IMPORTANT: Switch off the UPS, and wait approx. 2 minut es or switch the UPS to the manual bypass. In the latter case, please ensu re that the mains input is reliable during this period.
Install procedure for SG Series SGT5000_050-080_UPS_GE_03 Q1 OFF ON Q2 ON OFF 1. Change the front plate with the sma ller one delivered with the Kit. 2. Insert the SNMP adapter in the options slot. 3. Fix the front plate of the SNMP adapter to the connectivity box, using the screw include d in the SNMP/Web adapter kit.
• Make all necessary connections (see architecture diagram in section 2.4 ). Contact i /f • Switch on the UPS or go back to normal mode from bypass. 3.3 SP SNMP/WEB PLUG-IN AD APTER (P/N 1019070) • Switch off the UPS, and wait approx. 2 minutes or switch the UPS to the manual bypass.
• Connect the power to the box (left-most connector in the picture abov e). Make sure that the SNMP/WEB Interface box is powered b y the UPS output! • The UPS / Fail LED will switch OFF once th e connection to the UPS is established . If the LED remains continuously on, chec k the UPS connection and related cabling.
4 CONFIGURATION 4.1 CONFIGURATION METHODS The SNMP/Web plug-in adapters can be co nfigured using different interfaces. 4.1.1 Configuration via serial connection • Connect the SNMP adapter to a computer using a standard 1:1 serial co mmunication cable.
NOTE : Although the console interface provides a full set of comman ds, access using the serial connection is only needed for initial configuration when no DHCP server is available, or the IP-address is unknown. The quick network configuration menu pr ovides a simple interface for basic network configuration.
4.2 NETWORK PARAMETERS The SNMP/Web adapter connects to the ne twork using the foll owing parameters: • IP address identifies the adapter on the network. • Subnet mask defines a range of addresses within the organisation. • Gateway the node used for connection to addresses outside the subnet.
5 ACCESS 5.1 WEB INTERFACE After the installation and configuration of the SNMP/Web adapter, th e connection can be tested with a web browser. • Launch the browser • Enter the URL of the SNMP/Web adapter: http://< IP>/ (e.g. http://192.168.24 .
6 CUSTOMER SUPPORT 6.1 FIRST LINE SUPPORT Please contact your local GE distri butor for problems with the ins talla tion of th e product or its use. 6.2 INTERNET On-line support available on requ est (Internet acce ss required). 6.3 WWW SERVER We have a WWW server running at www.
7 APPENDIX A SitePro EARTH CONNECTION In order to guarantee correct func tional behaviour, the SNMP/Web plug-in adapter must be connected to protective earth (UPS chassis). On SitePro UPSs manufactured before 2003 th e square plates (delivered with the 3-ph adapter kit) must be mounted – refer to the pictures below for the installation details.
デバイスGE DIGITAL ENERGY 1018959の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
GE DIGITAL ENERGY 1018959をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはGE DIGITAL ENERGY 1018959の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。GE DIGITAL ENERGY 1018959の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。GE DIGITAL ENERGY 1018959で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
GE DIGITAL ENERGY 1018959を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はGE DIGITAL ENERGY 1018959の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、GE DIGITAL ENERGY 1018959に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちGE DIGITAL ENERGY 1018959デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。