71R-20 0 0 5/03 Operation and Maintenance Manual Entelli-Switch 250 Microprocessor Controller T ransfer Switch Control Panel GE Zenith Controls e.
P age Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3 Equipment Inspection and Storage . . . . . . . . 1 3 Final Equipment Inspection . . . .
■ GE Zenith Controls 3 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Each GE Zenith transfer switch is factory wired and tested. A complete information package is furnished with each switch which includes: a. Sequence of operation.
■ 4 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Installation (cont’ d) Engine Star t Contr ol Connections The engine-start terminals are clearly identified by a label on the microcontroller backplate.
Entelli-Switch 250 ■ GE Zenith Controls 5 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Installation (cont’ d) NO TE : When the voltage and freq uency reac h preset values, the S ource 2 A vailable LED will illuminate. 7.
■ 6 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Installation (cont’ d) A complete information package is furnished with each transfer switch including a complete connection diagram and schematic which details all necessary control circuit field connections.
Entelli-Switch 250 ■ GE Zenith Controls 7 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Entelli-S witc h 250 Contr oller Entelli-S witc h 250 Controller Consists of two major assemblies: I. The Microprocessor contains the following: A.
■ 8 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Entelli-S witc h 250 Contr oller (cont’ d) Figure 8 LCD & K e ypad These options are accessible through the LCD and keypad (see figure below).
■ GE Zenith Controls 9 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) User S et ting f or V oltage & F req uenc y Standard 3-Phase S ensing on 3 and 4 P ole Units S ourc.
■ 10 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) A ccessory Gr oup P ac kages Accessories 6P A1 A1E A3 A4 Calibrate CDT CDP **DS *DT *DW E EL/P K/P L1 .
■ GE Zenith Controls 11 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) A ccessory Definitions 6P T est Switch, Momentary 6A T est Switch, Maintained Auto/Momentary T est 6AP.
■ 12 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) M1 Single Phase Amp Meter M2 Three Phase Amp Meter M80 3000 Digital Power Monitor M82 5200 Digital Pow.
■ GE Zenith Controls 13 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) A ccessory Definitions (cont ’ d) Notes: - If S2 F r equency is less than S1 Frequency , display will show a series of (- - - - -…..) symbols. - If S2 Frequency is greater than S1 Frequency , display will show a series of (+++++….
■ 14 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Ho w to Set the S ystem Cloc k How to S et the System Cloc k Set System Clock, time and date · If the clock is not set, the display will show SET SYSTEM CLOCK on the second line of the S1 OK screen.
■ GE Zenith Controls 15 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Load or No-Load One event Exerciser with adjustable Timer . Exercise duration can be set between 5 and 60 minutes in 1 minute increments. Can be configured to run every 1,7,14, or 28 days.
■ 16 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) SET EXERCISER 00:0 0 T o save value and to move cursor to next field to be c hanged.
■ GE Zenith Controls 17 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Entelli-S witc h 250 User Setup - CFG Menu —TIMER EXERCISER (CDT) 1, 7, 14, 28 Day (pg. 11 & 15) —CLOCK EXERCISER LOAD OR NO LOAD (CDP) 1, 7, 14, 28, 365 Day (pg.
■ 18 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Entelli-S witc h 250 User Setup - SET Menu —SET SYSTEM CLOCK (pg.14) —DA YLIGHT SAVINGS ON/OFF —CLOCK EXERCISER (CDP) (pg.11 & 16) —EXER S2 RUNTIME (CDT) (pg.
■ GE Zenith Controls 19 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Entelli-S witc h 250 User Setup - S ystem Inf o —PHASE TO PHASE VOL T AGE, S1 & S2 —FREQUENCY INDICA TION FOR S1 & S2 (K/P) (pg.
■ 20 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) T esting Intr oduction A manual operator handle is provided with the transfer switch for maintenance purposes only . Manual operation of the switch must be checked before it is operated electrically .
■ GE Zenith Controls 21 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Entelli-Switch 250 T esting (cont ’ d) NO TICE A periodic test of the transfer switc h under load conditions is recommended to insure proper operation.
■ 22 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) T esting (cont ’ d) NO TICE A periodic test of the transfer switc h under load conditions is recommended to insure proper operation.
■ GE Zenith Controls 23 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) T esting (cont ’ d) Emergenc y Service P rocedure f or Extended P arallel T ime ZTSCT T ransfer Switc h If Source 2 breaker shunt trip was triggered after an extended parallel time (malfunction) occurred.
■ 24 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) S equence of Operation Standard T ransition Source 1 Power Failure: When Source 1 voltage or frequency.
■ GE Zenith Controls 25 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) S equence of Operation (cont ’ d) Closed T ransition GE Zenith Closed T ransition T ransfer Switches are designed to T ransfer the Load between two available sources with out interrupting power to the Load (Make-Before-Break).
■ 26 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Standard T ransition Each MX250 microprocessor based A TS controller requires a relay/transformer box to apply line voltage to the A TS operator via coil control relays.
■ GE Zenith Controls 27 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Dela yed / Closed T ransition Rela y/T ransformer (R/T Bo x) (cont ’ d) R/T Box Primar y 1 VA 25 VA Assembl y Voltage XFM R X FMR Part No. at 50/60 Hz Part No.
■ 28 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Rela y/T ransformer (R/T Bo x) (cont ’ d) 20 21 22 31 30 GND 903 902 80 1 90 1 807 804 803 904 905 9.
■ GE Zenith Controls 29 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) T r oubleshooting and Diagnostics HAZARDOUS V OL T A GES C AN C A USE SEVERE INJUR Y OR DEA TH . These c harts may indicate problems that req uire authorized GE Zenith service per sonnel.
■ 30 GE Zenith Controls ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ) Maintenance and T esting A preventive maintenance program will insure high reliability and long life for the transfer switch.
■ GE Zenith Controls 31 ■ Entelli-Switc h 250 Operation and Maintenance Manual (71 R -2 000 ).
A Product of GE Industrial Systems General Electric Company 830 West 40 th Street, Chicago, IL 60609 USA 773 299-6600 , Fax: 773 247-7805 www .geindustrial.
デバイスGE Entelli-Switch 250の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
GE Entelli-Switch 250をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはGE Entelli-Switch 250の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。GE Entelli-Switch 250の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。GE Entelli-Switch 250で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
GE Entelli-Switch 250を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はGE Entelli-Switch 250の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、GE Entelli-Switch 250に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちGE Entelli-Switch 250デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。