GEメーカーK-106465Aの使用説明書/サービス説明書
ページ先へ移動 of 43
GE Multilin 215 Ander son Avenue L6E 1B3 Markham, ON -CANADA T (905) 294 6222 F (905) 294 8512 E gemultilin@ge.com Internet: www . GEMultilin.com Copyright © 200 6 GE Multilin CIO Remote CAN Digital I/O Module Instruction manual GEK-106465 A GE Multilin Avda.
TABLE OF CONTENTS GEK-106465A CIO Remote CAN Digital I/O Module 1 1. OVERVIEW 3 1.1. IMPORTANT PROCEDURES 3 1.1.1. INSPECTION CHECKLI ST...................................................................................................................
TABLE OF CONTENTS 2 CIO Remote CAN Digital I/O Module GEK-106465A 5. INPUT/OUTPUT MODULES DESCRIPTION 31 5.1. CIRCUIT SUPERVISION AND CONTACT SE AL-IN CIRCUITS 31 5.1.1. CIRCUIT SU PERVISION.............................................................
OVERVIEW GEK-106465A CIO Remote CAN Digital I/O Module 3 ! 1. OVER VIEW 1.1. IMPORTANT PROCEDURES To help ensure years of trouble free ope ration, please read through the following chapter for inf ormation to help guide you through the initial installati on procedures of your n ew rel ay.
OVERVIEW 4 CIO Remote CAN Digital I/O Module GEK-106465A 1.1.1. INSPECTION CHECKLIST - Open the relay packaging and inspe ct the relay for physical damage. Refer to the label on the side of the relay verifies that the model number i s the correct model ordered.
OVERVIEW GEK-106465A CIO Remote CAN Digital I/O Module 5 Note: If there is any physical damage dete cte d on the relay, or any of the conten ts listed are missing, please contact GE Multilin immediately at: EUROPE, MIDDLE EAST AND AFRICA: GE MULTILIN Avda.
OVERVIEW 6 CIO Remote CAN Digital I/O Module GEK-106465A 1.1.2. SAFETY INSTRUCTIONS The CIO ground screw loca ted on the re ar of the unit must be correctly grounded.
OVERVIEW GEK-106465A CIO Remote CAN Digital I/O Module 7 1.2. OVERVIEW 1.2.1. INTRODUCTION TO F650 AND F600 FAMILY OF RELAYS This platform of relays has been desig ned to meet the goals that are appearing nowadays in the environment of new substations.
OVERVIEW 8 CIO Remote CAN Digital I/O Module GEK-106465A 1.2.4. COMMUNICATIONS ARCHITE CTURE CIO units incorporate a CAN BUS port in two phy sical media: gl ass fiber optic and cabl e. The fiber optic port allo ws connection to the master unit for a singl e CIO unit.
PRODUCT DESCRIPTION GEK-106465A CIO Remote CAN Digital I/O Module 9 2. PRODUCT DESCRIPTI ON 2.1. OVERVIEW The CIO module is an in put/output extension for F650 and F 600 units.
PRODUCT DESCRIPTION 10 CIO Remote CAN Digital I/O Module GEK-106465A 2.3. ORDERING CODE CIO units are available in 1/3 19’’ rack, 6 units high, and it in cludes a power supply m odule and a communication module, plus a maximum of two I/O modules.
PRODUCT DESCRIPTION GEK-106465A CIO Remote CAN Digital I/O Module 11 2.4. TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS ARE SUBJ ECT TO CHANGE WITHOUT NOTICE 2.
PRODUCT DESCRIPTION 12 CIO Remote CAN Digital I/O Module GEK-106465A 2.4.6. PACKAGING AND WEIGHT Net weight: 2.5 kg Packaged: 3.5 kg Package dimension s (Wx HxD): 30x40x40 cm 2.4.7. TYPE TESTS CAT EGORY STANDARD CLASS TEST EMC IEC 1000-4-8 EN61000-4-8 IV Power frequency magnetic field immunity test.
HARDWARE GEK-106465A CIO Remote CAN Digital I/O Module 13 3. HARDW ARE 3.1. MODULE DESCRIPTION FIGURE 3-1 BLOCK DIAGRAM F650 units incorporate the following module s: Power supply Input/Output module Optionally, a second I/O module can be added. A relay connected to the low voltage si de of the power suppl y monitors this voltage.
HARDWARE 14 CIO Remote CAN Digital I/O Module GEK-106465A 3.2. MECHANICAL DESCRIPTION The model number and electri cal characteristics of the unit are indicated on the label locate d on the right side of the relay case. The metallic case of the unit is highly resi stant to corrosi o n.
HARDWARE GEK-106465A CIO Remote CAN Digital I/O Module 15 FIGURE 3-3 REAR PANEL MOUNTING FIGURE 3-4 DRILLING DI MENSIONS 4 , 5 " 1 1 4 , 0 7 , 5 " 1 9 0 , 5 1 0 , 3 " 2 6 2 , 0 O 0 , 3 .
HARDWARE 16 CIO Remote CAN Digital I/O Module GEK-106465A 3.2.2. REAR COVER DESCRIPTION Unit wiring is performed through the terminal blo cks located on the rear. The rest of the terminal blocks for power supply, input s/out puts, incorporate high quality connectors with the capacity to withstand a rated curre nt of 15 A at 300 V.
HARDWARE GEK-106465A CIO Remote CAN Digital I/O Module 17 3.3. WIRING 3.3.1. EXTERNAL CONNECTIO NS CIO units can hold up to two I/O modules. Each of these modules can be sele cted between the following op tions: Option 1: Board with 16 inputs and 8 outputs.
HARDWARE 18 CIO Remote CAN Digital I/O Module GEK-106465A FIGURE 3-6 WIRING DIAGRAM FOR MODEL CIOH1J1 (22 6B5113F2).
HARDWARE GEK-106465A CIO Remote CAN Digital I/O Module 19 3.4. BOARDS 3.4.1. BOARD OPTION 1 CIO I/O board option 1 includes 16 inputs grouped in two series of 8 inputs with a common, and 8 conventional inputs.
HARDWARE 20 CIO Remote CAN Digital I/O Module GEK-106465A 3.4.2. BOARD OPTION 2 Option 2 I/O board include s two groups of 4 input s with one common, in termina ls 9 to 10. It also in cludes 6 auxiliary outputs, in terminals 19 to 30 with normally open co ntacts and two current sen sing (latching) outputs.
HARDWARE GEK-106465A CIO Remote CAN Digital I/O Module 21 The following lines describe the different types of conne ction to create ea ch scheme in an easy way. As the supervision circuit s are identical, we will describe co nnection examples for the first gro up.
HARDWARE 22 CIO Remote CAN Digital I/O Module GEK-106465A 3.4.2.2. WITH CURRENT SUPERVISION (WITH SEAL-IN ) In this case, as shown on FIGURE 3-9, t he current su pervision circuit consists in a circuit con nected in series with the output contact, so that the external circuit is wired to terminals 34 an d 36.
HARDWARE GEK-106465A CIO Remote CAN Digital I/O Module 23 3.4.2.3. WITH SIMPLE VOLTAGE SUPERVISION FIGURE 3-10 SUPERVISION APPLICATIO N WITH AUX ILIARY CO NTACT 52A AND A RESISTOR (A6631F3).
HARDWARE 24 CIO Remote CAN Digital I/O Module GEK-106465A INTERNAL STATE V 52/a SUPERVISION 52 open ON Ok 52 cl osed ON Ok TRIP OFF Ok if t < 0.5 s TRIP with 52 open OFF Ok if t < 0.5 s There is a possibility to monitor the trip circuit and trip coil continuity.
HARDWARE GEK-106465A CIO Remote CAN Digital I/O Module 25 For the second case shown on the ta ble, open breaker, it s a uxiliary contact 52/a remains open, and current ca nnot flow through it for detecting contin uity. In order to correctl y monito r the circuit, a resistor must be used, not included i n the protection, connected in parall el.
HARDWARE 26 CIO Remote CAN Digital I/O Module GEK-106465A FIGURE 3-11 TRIP CIRCUIT AN D TRIP COIL SUPERVI SION USING AUXILIARY CONTACT 52/A. ONL Y WITH CLOSED BREAKE R (A6631F5).
HARDWARE GEK-106465A CIO Remote CAN Digital I/O Module 27 3.4.2.4. WITH DOUBLE VOLTAGE SUPERVISION FIGURE 3-12 SUPERVISION APPLICATION WITH AUXILIARY CONTACTS 52A AND 52B (A6631F4 ).
HARDWARE 28 CIO Remote CAN Digital I/O Module GEK-106465A INTERNAL STATE V 52/a V 52/b SUPERVISION 52 open ON ON OK 52 closed ON OFF OK TRIP OFF OFF Ok if t < 0.
USER INTERFACES GEK-106465A CIO Remote CAN Digital I/O Module 29 4. USER INTERF ACES 4.1. SOFTWARE CIO units need to be connecte d to a master unit, either an F650 or a n F600.
USER INTERFACES 30 CIO Remote CAN Digital I/O Module GEK-106465A.
I/O MODULE S DESCRIPT ION GEK-106465A CIO Remote CAN Digital I/O Module 31 5. INPUT/OUTPUT MODULES DESCRIPTION 5.1. CIRCUIT SUPERVISION AND CONTACT S EAL-IN CIRCUITS 5.
I/O MODULE S DESCRIPT ION 32 CIO Remote CAN Digital I/O Module GEK-106465A 5.2. CONTROL SETTING S FOR INPUTS/OUTPUTS This section explains the setting s related to CIO inputs/out put s. Modification of these values is perform ed using the master unit communication software, EnerVista F65 0Setup for F6 50, or GE-CONF for F600.
I/O MODULE S DESCRIPT ION GEK-106465A CIO Remote CAN Digital I/O Module 33 CC Y Is the name used for inputs in I/O boards Mixed, 16 digital inputs: CC1….CC16 Supervision: 8 digital inputs: CC1,..., CC8 0 Z Is the name used for the different outputs in I/O boa rds, 8 outputs available for any of the two types of board (01,….
I/O MODULE S DESCRIPT ION 34 CIO Remote CAN Digital I/O Module GEK-106465A Settings relative to Inputs: Input Activation Voltage Thresh old: This value can be from 0 to 255 volts. There is a single setting for all inputs in the same group (inputs sharing the sam e common).
I/O MODULE S DESCRIPT ION GEK-106465A CIO Remote CAN Digital I/O Module 35 Settings relative to Outputs : Output Logic_0X _XX : Type of logic applied to o utputs. Possible values are positive and negative . The default value is positive. Output Type_0X _XX: Type of output adjusted.
I/O MODULE S DESCRIPT ION 36 CIO Remote CAN Digital I/O Module GEK-106465A 5.2.2. INPUTS/OUTPUTS STATUS Signals associated to I/O boards are divided in seve ral groups: Input activation signals (Conta.
I/O MODULE S DESCRIPT ION GEK-106465A CIO Remote CAN Digital I/O Module 37 Contact Outputs activ ation signals: These are the signal s that mark the physical activation of contact output s, independently fr om their a ssociated logic.
I/O MODULE S DESCRIPT ION 38 CIO Remote CAN Digital I/O Module GEK-106465A Contact Output Reset Signals (Contact Ou tput Resets): These are the logic signals asso ciated t o the contact output reset, which produce the reset of those signal s previously configured as Latche d.
ACCEPTANCE TE STS GEK-106465A CIO Remote CAN Digital I/O Module 39 6. ACCEPT ANCE TESTS 6.1. VISUAL INSPECTION Verify that the relay has not suffered an y damage during transp orta tion, and that all screws are co rrectly fixed, and all relay terminal boards are in good conditi on.
ACCEPTANCE TE STS 40 CIO Remote CAN Digital I/O Module GEK-106465A 6.3. ISOLATION TESTS During all tests, the screw l ocate d on the rear of the relay must be grounded.
ACCEPTANCE TE STS GEK-106465A CIO Remote CAN Digital I/O Module 41 6.6. COMMUNICATION WI TH THE MASTER UNIT 1. Connect the master unit to the CIO. Verify that the BUS LED blinks indicating communication between both units. 2. Verify, using the master unit Setup program, that th e CIO board s setting options are available.
ACCEPTANCE TE STS 42 CIO Remote CAN Digital I/O Module GEK-106465A The inputs test is completed by group s of 4 inputs, as this type of board has 2 groups of 4 inputs with the same common. For the first 4 inputs, the voltage threshol d setti ng is determined by Voltage Th reshold A.
デバイスGE GEK-106465Aの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
GE GEK-106465Aをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはGE GEK-106465Aの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。GE GEK-106465Aの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。GE GEK-106465Aで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
GE GEK-106465Aを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はGE GEK-106465Aの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、GE GEK-106465Aに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちGE GEK-106465Aデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。