C US ® Cop yright ©2009-2010 Goodman Manufacturing Co mpany, L.P. RT6612021 Rev. 3 August 2010 This manual is to be used by qualified, professionally trained HV AC technicians only . Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures performed by an unqualified person.
PRODUCT IDENTIFICA TION 2 The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit.
3 PRODUCT IDENTIFICA TION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information.
4 PRODUCT DESIGN installation (1 or 2 pipes). The optional Combustion Air Pipe is dependent on installation/code requirements and must be 2” or 3” diameter PVC. 2. Line voltage wiring can enter through the right or left side of the furnace. Low voltage wiring can enter through the right or left side of furnace.
5 PRODUCT DESIGN quired due to the natural reduction in the density of both the gas fuel and combustion air as altitude increases. The kit will provide the proper design certified input rate within the specified altitude range. High altitude kits are purchased according to the installa- tion altitude and usage of either natural or propane gas.
COMPONENT IDENTIFICA TION 6 Counterflow /Horizontal Upflow/Horizontal 1 Two-Stage Gas Valve 2 Gas Line Entrance (Alternate) 3 Pressure Switch(es) 4 Gas Manifold 5 Combustion Air Intake Connection 6 Ho.
7 PRODUCT DIMENSIONS GMVC95/AMVC95___X* NOTE: Airflow area will be reduced by approximately 18% if duct flanges are not unfolded. This could cause performance issues and noise issues.
PRODUCT DIMENSIONS 8 GCVC9/ACVC9_____X* NOTE: Airflow area will be reduced by approximately 18% if duct flanges are not unfolded. This could cause performance issues and noise issues.
9 PRODUCT DESIGN LOW F IR E HIGH FI R E LOW F IR E HI G H FIR E LOW FIRE HIGH FI R E LOW FIRE HI G H FIRE G MV C 95 0453 BX* G MV C 95 0704 CX* A M VC 9504 53BX * A M VC 9507 04CX * -0 . 45 - 0 . 9 0 -0 . 5 0 -0 .9 5 -0 . 25 - 0 . 2 5 -0. 25 -0 . 2 5 G MV C 95 0905 CX* A M VC 9509 05CX * - 0.
10 PRODUCT DESIGN LO W FIRE HI G H FIRE LO W FIR E HIG H FI RE LO W FIRE HIGH F IRE LO W FIR E HIGH F I RE G M VC 9504 53B X * G M VC 9507 04C X * AMV C95 0453 BX* AMV C95 0704 CX* - 0.10 - 0.1 0 20 1973 08 - 0 .30 - 0.75 111 7711 3 - 0.1 0 - 0. 10 - 0 .
11 PRODUCT DESIGN Pa rt N u m b e r 20 16 290 3 201 62 904 2 01 629 05 20 16 290 7 201 62 908 0 130 F 001 05 Open Setting (° F) 16 0 1 50 14 5 15 5 1 7 0 130 G MV C950 453B X* A MV C 95 0 4 53 B X* -.
12 PRODUCT DESIGN P art N um b e r 10 1235 34 101 2 3535 10 1235 37 1 012 3536 101 235 33 0130 F 000 38 Ope n Se t ting ( ° F) 220 1 50 190 18 0 200 12 0 G MV C95 045 3BX * AMV C 950 453 B X* - -- 2 .
13 PRODUCT DESIGN Coil Matches: A large array of Amana® brand coils are available for use with the GCVC9 and ACVC9 furnaces, in either counterflow or horizontal applications & with GMVC95 and AMVC95 furnaces, in either upflow or horizontal applications.
14 PRODUCT DESIGN Thermost at s: ComfortNet™ CTK01A* Thermostat Kit Filters: Filters are required with this furnace and must be provided by the installer.
15 PRODUCT DESIGN Counterflow Filters "A" Min Return Air Optional Ac ce ss Door Return air filters may be installated at the at the counterflow top return. A field supplied center filter support must be provided by the installer in order to use the top return.
FURNACE SPECIFICA TIONS 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level.
FURNACE SPECIFICA TIONS 17 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level.
FURNACE SPECIFICA TIONS 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level.
FURNACE SPECIFICA TIONS 19 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level.
FURNACE SPECIFICA TIONS 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level.
FURNACE SPECIFICA TIONS 21 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level.
BLOWER PERFORMANCE SPECIFICA TIONS 22 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 23 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 24 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 25 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 26 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 27 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 28 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 29 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 30 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 31 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 32 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
PERFORMANCE 33 30 40 50 60 70 80 90 1 1 0 12 0 100 13 0 14 0 150 100 90 80 70 60 50 40 30 20 10 OU TPUT B TU/ HR x 1 000 BTU OUTPUT vs T EM PERA TURE RISE CHAR T TE M PE R AT U R E R ISE 600 CFM 700 900 100 0 1 100 1200 1400 1600 180 0 2000 2200 2400 CFM FORM ULA S BTU OUTPUT = C FM x 1.
HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSONAL INJURY OR DEA TH. 34 WIRING DIAGRAMS Wiring is subject to change.
HI GH VO L T AGE! DISC ONNECT ALL POWE R BEFORE SERVICI NG OR INS T A LLING THIS UNIT . MUL TIPL E POW ER SOURCES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAG E, PERSONAL I NJURY OR DEA TH . 35 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSONAL INJURY OR DEA TH. 36 SCHEMA TICS BLOWER ASSEMBLY SCHEMATIC ACVC9/AMVC95/GCVC9/GMVC95_____X* MODEL FURNACES This schematic is for reference only.
HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSONAL INJURY OR DEA TH.
デバイスGoodman Mfg GCVC9/GMVC95の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Goodman Mfg GCVC9/GMVC95をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはGoodman Mfg GCVC9/GMVC95の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Goodman Mfg GCVC9/GMVC95の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Goodman Mfg GCVC9/GMVC95で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Goodman Mfg GCVC9/GMVC95を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はGoodman Mfg GCVC9/GMVC95の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Goodman Mfg GCVC9/GMVC95に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちGoodman Mfg GCVC9/GMVC95デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。